| Complementary |
| Utilisation category | DC-13; AC-15; AC-14 |
| Pole contact composition | 3 NO + 2 NC |
| Control circuit type | AC at 50/60 Hz |
| [Uc] control circuit voltage | 230 V AC 50/60 Hz |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 |
| [Ith] conventional free air thermal current | 10 A (at 60 °C) |
| Irms rated making capacity | 140 A AC conforming to IEC 60947-5-1; 250 A DC conforming to IEC 60947-5-1 |
| [Icw] rated short-time withstand current | 100 A - 1 s; 120 A - 500 ms; 140 A - 100 ms |
| Associated fuse rating | 10 A gG conforming to IEC 60947-5-1 |
| [Ui] rated insulation voltage | 600 V UL certified; 600 V CSA certified; 690 V conforming to IEC 60947-5-1 |
| Mounting support | Rail; Plate |
| Connections - terminals | Screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end; Screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end; Screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end; Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end; Screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end; Screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end |
| Tightening torque | 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2; 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm; 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2 |
| Control circuit voltage limits | 0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz; 0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz; 0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz; 1...1.1 Uc (60…70 °C):operational AC 50/60 Hz |
| Operating time | 12...22 ms coil energisation and NO closing; 4...12 ms coil de-energisation and NO opening; 4...19 ms coil energisation and NC opening; 6...17 ms coil de-energisation and NC closing |
| Mechanical durability | 30 Mcycles |
| Maximum operating rate | 180 cyc/mn |
| Inrush power in VA | 70 VA 50 Hz (at 20 °C) |
| Hold-in power consumption in VA | 8 VA 50 Hz (at 20 °C) |
| Minimum switching voltage | 17 V |
| Minimum switching current | 5 mA |
| Non-overlap time | 1.5 ms on energisation between NC and NO contact; 1.5 ms on de-energisation between NC and NO contact |
| Insulation resistance | > 10 MOhm |
| Mechanical robustness | Shocks control relay open: 10 Gn for 11 ms conforming to IEC 60068-2-27; Shocks control relay closed: 15 Gn for 11 ms conforming to IEC 60068-2-27; Vibrations control relay open: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6; Vibrations control relay closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 |
| Height | 77 mm |
| Width | 45 mm |
| Depth | 84 mm |
| Net weight | 0.58 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | EN/IEC 60947-5-1; GB/T 14048.5; UL 60947-5-1; CSA C22.2 No 60947-5-1; JIS C8201-5-1 |
| Product certifications | CB; CCC; UL; CSA; EAC; CE; UKCA |
| IP degree of protection | IP2X front face conforming to VDE 0106 |
| Protective treatment | TH conforming to IEC 60068 |
| Ambient air temperature for operation | -40…60 °C; 60…70 °C with derating |
| Ambient air temperature for storage | -60…80 °C |
| Operating altitude | 0...3000 m |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | TeSys; TeSys Deca |
| Product name | TeSys CAD |
| Product or component type | Control relay |
| Device short name | CAD |
| Contactor application | Control circuit |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 5 cm |
| Package 1 Width | 9.2 cm |
| Package 1 Length | 11.2 cm |
| Package 1 Weight | 343 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 20 |
| Package 2 Height | 15 cm |
| Package 2 Width | 30 cm |
| Package 2 Length | 40 cm |
| Package 2 Weight | 7.146 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 320 |
| Package 3 Height | 75 cm |
| Package 3 Width | 60 cm |
| Package 3 Length | 80 cm |
| Package 3 Weight | 125.44 kg |
The Schneider Electric TeSys CAD32P7 is a control relay from the TeSys Deca series, specifically designed for use in control circuits. It is used for electrical control and signal transmission in industrial installations and operates on an alternating voltage of 230 V AC at 50/60 Hz. The device features five integrated auxiliary contacts – consisting of three normally open (NO) contacts and two normally closed (NC) contacts – and is expandable by up to nine additional auxiliary contacts. Mounting is either on a rail or directly on a plate, with a device width of 45 mm. Connections are made via screw terminals, designed for flexible and rigid cable cross-sections from 1 to 4 mm², with maximum cross-sections limited to 2.5 mm² (flexible) or 4 mm² (rigid) for cables with wire end ferrules. The tightening torque is 1.7 Nm, and mounting can be done using a Phillips screwdriver No. 2, flat Ø 6, or position No. 2.
Applications
This control relay is intended for use in industrial control systems and switchgear, particularly in applications requiring reliable signal transmission and switching functions. It is approved for usage categories DC-13, AC-15, and AC-14, enabling its use in various circuits with direct and alternating current. The rated insulation voltage is 690 V according to IEC 60947-5-1, and the devices are also UL- and CSA-certified (600 V). The rated surge voltage withstand is 6 kV, ensuring high electrical strength even under transient voltage stresses.
Functions and Equipment in Detail
The device has a conventional thermal current rating of 10 A at 60 °C in free air. The rated switching capacity is 140 A for alternating current and 250 A for direct current, according to IEC 60947-5-1. The rated short-time current withstand is 100 A for 1 second, 120 A for 500 ms, and 140 A for 100 ms. The associated fuse is a 10 A gG fuse, ensuring protection of the control circuit. The operating time is 12 to 22 ms for coil energization and NO closing, and 4 to 12 ms for coil de-energization and NO opening. The mechanical life is 30 million switching cycles, and the maximum operating rate is 180 operations per minute.
Technology Explained Simply
The control circuit voltage is 230 V AC at 50/60 Hz, with operating voltage ranges between 0.8 and 1.1 times the nominal voltage (at -40 to 60 °C). At temperatures from 60 to 70 °C, the operating voltage is limited to 1 to 1.1 times the nominal voltage. The minimum switching voltage is 17 V, and the minimum switching current is 5 mA. The pickup power is 70 VA at 50 Hz (at 20 °C), and the holding power consumption is 8 VA. The non-overlapping time between the closing and opening contacts is 1.5 ms, ensuring safe contact separation during switching operations. The insulation resistance is greater than 10 MΩ, ensuring high electrical insulation.
Compatibility and Accessories
The device is expandable with various accessories, including auxiliary switch blocks such as LADN11 (1S1Ö), LADN31 (3S1Ö), LADN22 (2S+2Ö), LADN04 (4Ö), LADN40 (4S), LA1DX02 (2Ö), LA1DX20 (2S), LA1DZ40 (4S), LAD8N20 (2S), LAD8N11 (1S+1Ö), as well as delayed time blocks such as LAD-S2 (1–30 seconds delayed pickup) and LADT4 (1S+1Ö, 10–180 seconds delayed pickup). Additionally, interlocking blocks (e.g. LAD6K10F for 110–127 VAC/DC, LAD6K10E for 42–48 VAC/DC), varistors (LAD-4VU, 110–240 V), and protective covers (e.g. LAD9ET1, LAD9ET1S) are available, enhancing the relay’s functionality and safety.
Mounting and Installation
Mounting is on a rail or directly on a plate. The device dimensions are 45 mm (width), 77 mm (height), and 84 mm (depth). The product weight is 0.58 kg. The operating ambient temperature ranges from -40 °C to 60 °C, with performance reduction required at temperatures from 60 to 70 °C. The storage temperature can range from -60 °C to 80 °C. The operating altitude is limited to 0 to 3,000 m above sea level. The protection rating is IP2x on the front according to VDE 0106, providing protection against contact with fingers and larger solid objects. Mechanical robustness is certified according to IEC 60068-2-27 and IEC 60068-2-6, allowing shocks of 10 Gn (open) or 15 Gn (closed) and vibrations of 2 Gn or 4 Gn (depending on state).
Advantages in Operation
The TeSys CAD32P7 offers high reliability due to its long mechanical life and high switching frequency. The integrated auxiliary contacts allow direct integration into control circuits, while the expandability by up to nine additional contacts increases flexibility in system design. Approvals according to EN/IEC 60947-5-1, UL, CSA, CCC, CB, EAC, CE, and UKCA ensure international usability. The screw terminals enable secure and easy wiring, with specified tightening torques ensuring reliable connections. The operating temperature ranges and mechanical robustness make the device suitable for industrial applications in various environments.