| Complementary |
| Utilisation category | AC-15; AC-14; DC-13 |
| Pole contact composition | 3 NO + 2 NC |
| Control circuit type | DC standard |
| [Uc] control circuit voltage | 12 V DC |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 |
| [Ith] conventional free air thermal current | 10 A (at 60 °C) |
| Irms rated making capacity | 140 A AC; 250 A DC |
| [Icw] rated short-time withstand current | 100 A - 1 s; 120 A - 500 ms; 140 A - 100 ms |
| Associated fuse rating | 10 A gG conforming to IEC 60947-5-1 |
| [Ui] rated insulation voltage | 690 V conforming to IEC 60947-5-1 |
| Mounting support | Rail; Plate |
| Connections - terminals | Snap-in terminal 1 cable(s) 0.5…4 mm²flexible without cable end; Snap-in terminal 2 cable(s) 0.5…4 mm²flexible without cable end; Snap-in terminal 1 cable(s) 0.5…2.5 mm²flexible with cable end; Snap-in terminal 2 cable(s) 0.5…2.5 mm²flexible with cable end |
| Control circuit voltage limits | 0.1...0.25 Uc (-40…70 °C):drop-out DC; 0.7...1.25 Uc (-40…60 °C):operational DC; 1...1.25 Uc (60…70 °C):operational DC |
| Operating time | 53...72 ms coil energisation and NO closing; 16...24 ms coil de-energisation and NO opening; 47...63 ms coil energisation and NC opening; 15...25 ms coil de-energisation and NC closing |
| Mechanical durability | 30 Mcycles |
| Maximum operating rate | 180 cyc/mn |
| Time constant | 28 ms |
| Inrush power in W | 5.4 W (at 20 °C) |
| Hold-in power consumption in W | 5.4 W at 20 °C |
| Minimum switching voltage | 17 V |
| Minimum switching current | 5 mA |
| Non-overlap time | 1.5 ms on energisation between NC and NO contact; 1.5 ms on de-energisation between NC and NO contact |
| Insulation resistance | > 10 MOhm |
| Mechanical robustness | Shocks control relay open: 10 Gn for 11 ms conforming to IEC 60068-2-27; Shocks control relay closed: 15 Gn for 11 ms conforming to IEC 60068-2-27; Vibrations control relay open: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6; Vibrations control relay closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 |
| Height | 107 mm |
| Width | 45 mm |
| Depth | 93 mm |
| Net weight | 562 g |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | EN/IEC 60947-5-1; UL 60947-5-1; CSA C22.2 No 60947-5-1; GB/T 14048.5; JIS C8201-5-1 |
| Product certifications | CB Scheme; CCC; cULus; CE; UKCA; EU-RO-MR by DNV |
| IP degree of protection | IP2X front face conforming to VDE 0106 |
| Protective treatment | TH conforming to IEC 60068 |
| Ambient air temperature for operation | -40…60 °C; 60…70 °C with derating |
| Ambient air temperature for storage | -60…80 °C |
| Operating altitude | 0...3000 m |
| Main |
| Range | TeSys |
| Product name | TeSys CAD |
| Product or component type | Control relay |
| Device short name | CAD |
| Contactor application | Control circuit |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 5.500 cm |
| Package 1 Width | 10.000 cm |
| Package 1 Length | 11.500 cm |
| Package 1 Weight | 578.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 15 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 8.973 kg |
The
control relay CAD32AJD from the
TeSys series by
Schneider Electric is an auxiliary contactor designed for use in control circuits. It features a
12 V DC coil and integrated auxiliary contacts configured as
3 normally closed (NO) + 2 normally open (NC). The device is designed for demanding industrial applications requiring high operating speeds and reliability. The mechanical life expectancy is
30 million switching cycles, and the maximum operating rate is
180 cycles per minute, equating to up to 10,800 cycles per hour. The contacts are rated for usage categories
AC-15, AC-14, and DC-13, with a rated insulation voltage of
690 V. The coil is designed for operating voltages between
0.7 and 1.25 times the nominal voltage (12 V DC), with operating voltages of 1 to 1.25 times allowed at temperatures of 60 to 70 °C. The minimum switching voltage is
17 V, and the minimum switching current is
5 mA. The coil’s pull-in and holding power is
5.4 W at 20 °C.
Applications
This relay is intended for use in control and switching systems in industrial environments, particularly in applications requiring high switching frequencies. The usage categories AC-15 and DC-13 indicate applications in electrical control systems, such as automation technology, machine control, or safety circuits. The mechanically coupled contacts and mirror contacts make the device suitable for safety applications where secure and reliable switching is required. The rated short-time current withstand capability is
100 A for 1 second, 120 A for 500 ms, and 140 A for 100 ms, ensuring suitability for environments with short-term current surges.
Functions and Features in Detail
The device includes
five integrated auxiliary contacts (3S + 2Ö), which are expandable. Expansion is achieved by adding auxiliary switch blocks, which can add up to nine additional contacts. Connections are made via
SnapIN terminals, enabling quick, secure, and maintenance-free electrical connections. The terminals are designed for flexible cables with cross-sections of
0.5 to 4 mm² without cable ends and
0.5 to 2.5 mm² with cable ends. The rated switching capacity is
140 A for alternating current (AC) and 250 A for direct current (DC). The conventional thermal current rating is
10 A at 60 °C in free air.
Technology Explained Simply
The relay coil is operated at
12 V DC and is designed for an operating voltage of 0.7 to 1.25 times the nominal voltage. The operating time is
53 to 72 ms for coil energization and NO closure, and
16 to 24 ms for coil de-energization and NO opening. The non-overlapping time between the closing and opening contacts is
1.5 ms, ensuring secure contact separation. The coil time constant is
28 ms. Insulation strength is ensured by a rated impulse voltage withstand of
6 kV (in accordance with IEC 60947). The insulation resistance is greater than
10 MΩ. Mechanical robustness is confirmed by shock and vibration tests according to IEC 60068-2-27 and IEC 60068-2-6, allowing shock loads of
10 Gn for open relays and
15 Gn for closed relays over 11 ms. Vibration loads are
2 Gn (open) and 4 Gn (closed) in the frequency range of 5 to 300 Hz.
Compatibility and Accessories
The relay is compatible with various accessories, including delayed auxiliary switch blocks such as the
LAD-R4 (10–180 seconds release-delayed) or the
LAD-S2 (1–30 seconds pickup-delayed). Time blocks such as
LADR0 (0.10–3.00 s),
LADT0 (0.10–3.00 s pickup-delayed), or
LADT4 (10.00–180.00 s pickup-delayed) allow adaptation to specific timing control tasks. Additional auxiliary switch blocks such as
LADN02A (2 NC),
LADN04A (4 NC),
LADN11A (1NO+1NC), or
LADN22A (2NO+2NC) extend the contact count. Mounting is on
rail or panel, with a protection rating of
IP2x front side (equivalent to VDE 0106). The operating temperature range is
-40 °C to 60 °C, with performance reduction required at temperatures of 60 to 70 °C. Storage temperature is
-60 °C to 80 °C, and the operating altitude is limited to
0 to 3,000 m.
Mounting and Installation
Mounting is either on a mounting rail or directly on a panel. The SnapIN connection terminals allow quick and secure connections without tools. Cable cross-sections must comply with specifications: flexible cables of
0.5 to 4 mm² without cable ends or
0.5 to 2.5 mm² with cable ends. Electrical insulation and mechanical strength of connections are critical for reliability. Installation must be performed by qualified personnel to meet safety requirements. Approvals include
EN/IEC 60947-5-1, UL 60947-5-1, CSA C22.2 No. 60947-5-1, GB/T 14048.5, and JIS C8201-5-1. Product certifications include
CB Scheme, CCC, cULus, CE, UKCA, and EU-RO-MR by DNV.
Operational Advantages
The relay offers high mechanical life and is designed for high operating rates, making it suitable for continuous and intensive use in industrial systems. The SnapIN terminals reduce installation time and increase connection reliability. Mechanically coupled contacts and mirror contacts ensure secure switching, especially in safety applications. Expandability up to nine additional contacts allows flexible adaptation to different switching requirements. The 12 V DC operating voltage is common in many control systems, facilitating integration into existing installations. The rated insulation voltage of 690 V and impulse voltage withstand of 6 kV ensure reliable operation in electrically demanding environments. International standard approvals guarantee suitability for various markets.