| Additional features |
| Application category | DC-13; AC-14; AC-15 |
| Composition of pole contact | 3 NO + 2 NC |
| Control circuit type | AC at 50/60 Hz |
| [Uc] control circuit voltage | 400 V AC 50/60 Hz |
| [Uimp] Rated impulse voltage withstand | 6 kV corresponds to IEC 60947 |
| [Ith] conventional thermal current in free air | 10 A (at 60 °C) |
| [Irms] Rated making capacity | 140 A AC according to IEC 60947-5-1; 250 A DC according to IEC 60947-5-1 |
| [Icw] rated short-time current withstand | 100 A - 1 s; 120 A - 500 ms; 140 A - 100 ms |
| Associated fuse | 10 A gG according to IEC 60947-5-1 |
| [Ui] Rated insulation voltage | 600 V UL certified; 600 V CSA certified; 690 V complies with IEC 60947-5-1 |
| Mounting bracket | Rail; Plate |
| Connections - terminals | Ring terminal connectors (outer diameter: 8 mm) |
| Control circuit voltage limits | 0.3 - 0.6 Uc (-40…70 °C): drop-out voltage AC 50/60 Hz; 0.8 - 1.1 Uc (-40…60 °C): operation AC 50 Hz; 0.85 - 1.1 Uc (-40…60 °C): operation AC 60 Hz; 1 - 1.1 Uc (60…70 °C): operation AC 50/60 Hz |
| Operating time | 12 - 22 ms coil energizing and NO closing; 4 - 12 ms coil de-energizing and NO opening; 4 - 19 ms coil energizing and NC opening; 6 - 17 ms coil de-energizing and NC closing |
| Mechanical life | 30 Mcycles |
| Max. operating rate | 180 cyc/mn |
| Input power in VA | 70 VA 50 Hz (at 20 °C) |
| Hold power consumption in VA | 8 VA 50 Hz (at 20 °C) |
| Min. switching voltage | 17 V |
| Min. switching current | 5 mA |
| Non-overlapping time | 1.5 ms when actuated between normally open contact and normally closed contact; 1.5 ms when de-energized between normally open contact and normally closed contact |
| Insulation resistance | > 10 MΩ |
| Mechanical robustness | Shocks control relay open: 10 Gn for 11 ms according to IEC 60068-2-27; Shocks control relay closed: 15 Gn for 11 ms according to IEC 60068-2-27; Vibrations control relay open: 2 Gn, 5 - 300 Hz according to IEC 60068-2-6; Vibrations control relay closed: 4 Gn, 5 - 300 Hz according to IEC 60068-2-6 |
| Height | 77 mm |
| Width | 45 mm |
| Depth | 84 mm |
| Product weight | 0,58 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Main features |
| Product series | TeSys; TeSys Deca |
| Product name | TeSys CAD |
| Product or component type | Control relay |
| Device short name | CAD |
| Application of contactor | Control circuit |
| Mounting |
| Standards | EN/IEC 60947-5-1; GB/T 14048.5; UL 60947-5-1; CSA C22.2 No. 60947-5-1; JIS C8201-5-1 |
| Product certifications | CB; CCC; UL; CSA; EAC; CE; UKCA |
| Degree of protection (IP) | IP2x front panel complies with VDE 0106 |
| Coating | TH corresponds to IEC 60068 |
| Operating ambient temperature | -40…60 °C; 60…70 °C with power reduction |
| Ambient temperature during storage | -60…80 °C |
| Operating altitude | 0 - 3.000 m |
| Packaging units |
| VPE 1 type | PCE |
| Number of devices per package | 1 |
| VPE 1 height | 5,700 cm |
| VPE 1 width | 11,900 cm |
| VPE 1 length | 9,700 cm |
| Packaging weight (Lbs) | 362,000 g |
TeSys D contactor relay for the AC-15 to 690V and DC-13 to 440V usage categories. It offers 5 contacts (3NO + 2NC), a 400V 50/60Hz AC coil, connection via ring lug screw terminals. It ensures high reliability and durability for demanding applications with high operating speeds up to 10800 cycles/hour. It has multiple standards (IEC, UL, CSA, CCC, EAC, Marine) and Green Premium compliance (RoHs/Reach).