| Additional features |
| Application category | AC-14; AC-15; DC-13 |
| Composition of pole contact | 3 NO + 2 NC |
| Control circuit type | DC Standard |
| [Uc] control circuit voltage | 125 V DC |
| [Uimp] Rated impulse voltage withstand | 6 kV corresponds to IEC 60947 |
| [Ith] conventional thermal current in free air | 10 A (at 60 °C) |
| [Irms] Rated making capacity | 140 A AC according to IEC 60947-5-1; 250 A DC according to IEC 60947-5-1 |
| [Icw] rated short-time current withstand | 100 A - 1 s; 120 A - 500 ms; 140 A - 100 ms |
| Associated fuse | 10 A gG according to IEC 60947-5-1 |
| [Ui] Rated insulation voltage | 600 V UL certified; 600 V CSA certified; 690 V complies with IEC 60947-5-1 |
| Mounting bracket | Rail; Plate |
| Connections - terminals | Ring terminal connectors (outer diameter: 8 mm) |
| Control circuit voltage limits | 0.1 - 0.25 Uc (-40…70 °C): drop voltage DC; 0.7 - 1.25 Uc (-40…60 °C): operation DC; 1 - 1.25 Uc (60…70 °C): operation DC |
| Operating time | 53 - 72 ms coil energization and NO closing; 16 - 24 ms coil de-energization and NO opening; 47 - 63 ms coil energization and NC opening; 15 - 25 ms coil de-energization and NC closing |
| Mechanical life | 30 Mcycles |
| Max. operating rate | 180 cyc/mn |
| Time constant | 28 ms |
| Absorption power in W | 5.4 W (at 20 °C) |
| Holding power consumption in W | 5.4 W at 20 °C |
| Min. switching voltage | 17 V |
| Min. switching current | 5 mA |
| Non-overlapping time | 1.5 ms when actuated between normally open contact and normally closed contact; 1.5 ms when de-energized between normally open contact and normally closed contact |
| Insulation resistance | > 10 MΩ |
| Mechanical robustness | Shocks control relay open: 10 Gn for 11 ms according to IEC 60068-2-27; Shocks control relay closed: 15 Gn for 11 ms according to IEC 60068-2-27; Vibrations control relay open: 2 Gn, 5 - 300 Hz according to IEC 60068-2-6; Vibrations control relay closed: 4 Gn, 5 - 300 Hz according to IEC 60068-2-6 |
| Height | 77 mm |
| Width | 45 mm |
| Depth | 93 mm |
| Product weight | 0,58 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Main features |
| Product series | TeSys; TeSys Deca |
| Product name | TeSys CAD |
| Product or component type | Control relay |
| Device short name | CAD |
| Application of contactor | Control circuit |
| Mounting |
| Standards | EN/IEC 60947-5-1; GB/T 14048.5; UL 60947-5-1; CSA C22.2 No. 60947-5-1; JIS C8201-5-1 |
| Product certifications | CB; CCC; UL; CSA; EAC; CE; UKCA |
| Degree of protection (IP) | IP2x front panel complies with VDE 0106 |
| Coating | TH corresponds to IEC 60068 |
| Operating ambient temperature | -40…60 °C; 60…70 °C with power reduction |
| Ambient temperature during storage | -60…80 °C |
| Operating altitude | 0 - 3.000 m |
| Packaging units |
| VPE 1 type | PCE |
| Number of devices per package | 1 |
| VPE 1 height | 4,900 cm |
| VPE 1 width | 14,800 cm |
| VPE 1 length | 13,200 cm |
| Packaging weight (Lbs) | 533,000 g |
| VPE 2 type | S02 |
| VPE 2 quantity | 16 |
| VPE 2 height | 15,000 cm |
| VPE 2 width | 30,000 cm |
| VPE 2 length | 40,000 cm |
| VPE 2 weight | 8,308 kg |
| VPE 3 type | P12 |
| VPE 3 quantity | 256 |
| VPE 3 height | 45,000 cm |
| VPE 3 width | 80,000 cm |
| VPE 3 length | 120,000 cm |
| VPE 3 weight | 140,928 kg |
TeSys D contactor relay for the AC-15 to 690V and DC-13 to 440V usage categories. It has 5 contacts (3NO + 2NC), a 125V DC coil with an integrated overvoltage protection module, connection via ring lug screw terminals. It ensures high reliability and durability for demanding applications with high operating speeds up to 10800 cycles/hour. It has multiple standards (IEC, UL, CSA, CCC, EAC, Marine) and Green Premium compliance (RoHs/Reach).