| Complementary |
| Coil technology | Built-in bidirectional peak limiting diode suppressor |
| [Ith] conventional free air thermal current | 10 A (at 50 °C) |
| Irms rated making capacity | 110 A conforming to IEC 60947 |
| Associated fuse rating | 10 A gG conforming to IEC 60947; 10 A gG conforming to VDE 0660 |
| [Ui] rated insulation voltage | 690 V conforming to IEC 60947; 750 V conforming to VDE 0110 group C; 690 V conforming to BS 5424; 600 V conforming to CSA C22.2 No 14 |
| Mounting support | Plate; Rail |
| Connections - terminals | Spring terminals 1 cable(s) 0.75…1.5 mm²solid; Spring terminals 1 cable(s) 0.75…1.5 mm²flexible without cable end |
| Control circuit voltage limits | Drop-out: 0.1...0.75 Uc (at |
| Operating time | 10...20 ms coil de-energisation and NO opening; 30...40 ms coil energisation and NO closing |
| Mechanical durability | 30 Mcycles |
| Maximum operating rate | 6000 cyc/h |
| Immunity to microbreaks | 2 ms |
| Inrush power in W | 1.8 W (at 20 °C) |
| Hold-in power consumption in W | 1.8 W at 20 °C |
| Heat dissipation | 1.8 W |
| Minimum switching voltage | 17 V |
| Minimum switching current | 5 mA |
| Non overlap distance | 0.5 mm |
| Insulation resistance | > 10 MOhm |
| Height | 58 mm |
| Width | 45 mm |
| Depth | 57 mm |
| Net weight | 0.235 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | EN/IEC 60947-5-1; GB/T 14048.5; UL 60947-5-1; CSA C22.2 No 60947-5-1; JIS C8201-5-1 |
| Product certifications | CB Scheme; CCC; UL; CSA; EAC; CE; UKCA |
| Protective treatment | TC conforming to IEC 60068 |
| Ambient air temperature for operation | -25…50 °C |
| Ambient air temperature for storage | -50…80 °C |
| Operating altitude | 2000 m without derating |
| Flame retardance | V1 conforming to UL 94; Requirement 2 conforming to NF F 16-101; Requirement 2 conforming to NF F 16-102 |
| Mechanical robustness | Vibrations contactor open: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6; Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6; Shocks contactor open: 10 Gn for 11 ms conforming to IEC 60068-2-27; Shocks contactor closed: 15 Gn for 11 ms conforming to IEC 60068-2-27 |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | TeSys |
| Product name | TeSys CAK |
| Product or component type | Control relay |
| Device short name | CA4K |
| Contactor application | Control circuit |
| Utilisation category | AC-15; DC-13 |
| Pole contact composition | 4 NO |
| Control circuit type | DC low consumption |
| [Uc] control circuit voltage | 24 V DC |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 4.8 cm |
| Package 1 Width | 6.2 cm |
| Package 1 Length | 6.5 cm |
| Package 1 Weight | 227.0 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 40 |
| Package 2 Height | 15.0 cm |
| Package 2 Width | 30.0 cm |
| Package 2 Length | 40.0 cm |
| Package 2 Weight | 9.324 kg |
TeSys K contactor relay for use categories AC-15 to 690V and DC-13 to 600V. It has 4 contacts (4 NO), a 24 V DC coil with low consumption and integrated suppression, connection via spring terminals. It is designed for demanding applications with high operating speeds up to 6, 00 operations/hour and offers high reliability and durability. Certified with several standards (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHs/Reach).