| Complementary |
| [Ith] conventional free air thermal current | 10 A (at 55 °C) |
| Associated fuse rating | 10 A gL conforming to VDE 0660; 10 A gL conforming to IEC 60947 |
| [Ui] rated insulation voltage | 690 V conforming to IEC 60947; 690 V conforming to VDE 0110 group C; 690 V conforming to BS 5424; 690 V conforming to UL 508; 690 V conforming to CSA C22.2 No 14 |
| Mounting support | Rail; Plate |
| Connections - terminals | Screw clamp terminals 1 cable(s) 1.5…6 mm²solid; Screw clamp terminals 2 cable(s) 1.5…4 mm²solid; Screw clamp terminals 1 cable(s) 0.5…6 mm²flexible without cable end; Screw clamp terminals 1 cable(s) 0.35…6 mm²flexible with cable end; Screw clamp terminals 2 cable(s) 0.35…1.5 mm²flexible with cable end; Screw clamp terminals 2 cable(s) 0.35…2.5 mm²flexible without cable end |
| Tightening torque | 0.8 N.m - on screw clamp terminals pozidriv No 1 screw head |
| Control circuit voltage limits | Operational: 0.85...1.1 Uc (at |
| Operating time | 4...6 ms coil de-energisation and NO opening; 8...12 ms coil energisation and NO closing |
| Mechanical durability | 10 Mcycles |
| Maximum operating rate | 1200 cyc/h |
| Inrush power in W | 2.2 W (at 20 °C) |
| Hold-in power consumption in W | 2.2 W at 20 °C |
| Heat dissipation | 2.2 W |
| Height | 56 mm |
| Width | 27 mm |
| Depth | 55.5 mm |
| Net weight | 0.132 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | EN/IEC 60947-5-1; UL 60947-5-1; CSA C22.2 No 60947-5-1 |
| Product certifications | CB Scheme; cULus; EAC; CE; UKCA |
| IP degree of protection | IP2X |
| Protective treatment | TC conforming to IEC 60068 |
| Ambient air temperature for operation | -20…50 °C |
| Ambient air temperature for storage | -50…70 °C |
| Operating altitude | 2000 m without derating |
| Logistical informations |
| Country of origin | CZ |
| Main |
| Range | TeSys |
| Product name | TeSys CASK |
| Product or component type | Control relay |
| Device short name | CA3SK |
| Contactor application | Control circuit |
| Utilisation category | DC-13; AC-15 |
| Pole contact composition | 2 NO |
| Control circuit type | DC standard |
| [Uc] control circuit voltage | 24 V DC |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 6.000 cm |
| Package 1 Width | 6.600 cm |
| Package 1 Length | 3.300 cm |
| Package 1 Weight | 124.000 g |
| Unit Type of Package 2 | S01 |
| Number of Units in Package 2 | 40 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 15.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 5.157 kg |
TeSys mini auxiliary contactors. Auxiliary contactor, DC voltage operated 24V DC. Connection screw terminals, auxiliary switch 2 NO, MTZ 12. Device width 27 mm, snap-on mounting. Two integrated auxiliary contacts, expandable by up to four auxiliary contacts.