| Complementary |
| [Ith] conventional free air thermal current | 10 A (at 50 °C) |
| Irms rated making capacity | 110 A conforming to IEC 60947 |
| Associated fuse rating | 10 A gG conforming to IEC 60947; 10 A gG conforming to VDE 0660 |
| [Ui] rated insulation voltage | 690 V conforming to IEC 60947; 750 V conforming to VDE 0110 group C; 690 V conforming to BS 5424; 600 V conforming to CSA C22.2 No 14 |
| Mounting support | Rail; Plate |
| Connections - terminals | Screw clamp terminals 1 cable(s) 1.5…4 mm²solid; Screw clamp terminals 2 cable(s) 1.5…4 mm²solid; Screw clamp terminals 1 cable(s) 0.75…4 mm²flexible with cable end; Screw clamp terminals 2 cable(s) 0.75…4 mm²flexible without cable end; Screw clamp terminals 1 cable(s) 0.34…1.5 mm²flexible with cable end; Screw clamp terminals 2 cable(s) 0.34…1.5 mm²flexible without cable end |
| Tightening torque | 1.3 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm; 1.3 N.m - on screw clamp terminals - with screwdriver Philips No 26 mm; 1.3 N.m - on screw clamp terminals - with screwdriver pozidriv No 2 |
| Control circuit voltage limits | Operational: 0.8...1.15 Uc (at |
| Operating time | 10 ms coil de-energisation and NO opening; 30...40 ms coil energisation and NO closing |
| Mechanical durability | 20 Mcycles |
| Maximum operating rate | 10000 cyc/h |
| Immunity to microbreaks | 2 ms |
| Inrush power in W | 3 W (at 20 °C) |
| Hold-in power consumption in W | 3 W at 20 °C |
| Heat dissipation | 3 W |
| Minimum switching voltage | 17 V |
| Minimum switching current | 5 mA |
| Non overlap distance | 0.5 mm |
| Insulation resistance | > 10 MOhm |
| Height | 58 mm |
| Width | 45 mm |
| Depth | 57 mm |
| Net weight | 0.225 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | EN/IEC 60947-5-1; GB/T 14048.5; UL 60947-5-1; CSA C22.2 No 60947-5-1; JIS C8201-5-1 |
| Product certifications | CB Scheme; CCC; UL; CSA; EAC; CE; UKCA |
| IP degree of protection | IP2X |
| Protective treatment | TC conforming to IEC 60068 |
| Ambient air temperature for operation | -25…50 °C |
| Ambient air temperature for storage | -50…80 °C |
| Operating altitude | 2000 m without derating |
| Flame retardance | V1 conforming to UL 94; Requirement 2 conforming to NF F 16-101; Requirement 2 conforming to NF F 16-102 |
| Mechanical robustness | Vibrations contactor open: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6; Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6; Shocks contactor open: 10 Gn for 11 ms conforming to IEC 60068-2-27; Shocks contactor closed: 15 Gn for 11 ms conforming to IEC 60068-2-27 |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | TeSys |
| Product name | TeSys CAK |
| Product or component type | Control relay |
| Device short name | CA3K |
| Contactor application | Control circuit |
| Utilisation category | AC-15; DC-13 |
| Pole contact composition | 4 NO |
| Control circuit type | DC standard |
| [Uc] control circuit voltage | 220 V DC |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 4.500 cm |
| Package 1 Width | 6.000 cm |
| Package 1 Length | 6.500 cm |
| Package 1 Weight | 211.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 40 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 8.674 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 640 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 80.000 cm |
| Package 3 Length | 60.000 cm |
| Package 3 Weight | 146.784 kg |
The
control relay CA3KN40MD from the
TeSys series by
Schneider Electric is an
auxiliary contactor designed for use in control circuits. It features a
4-pole closing contact configuration (4S) and is rated for a
control circuit voltage of 220 V DC. The device is used for electrical control and signal transmission in industrial applications, such as automation systems, machine controls, or for actuating auxiliary functions. The
application categories AC-15 and DC-13 define its scope for alternating and direct current applications, with the DC-13 category applicable for switching direct current loads such as electric motors or heaters.
Application areas include integration into controls for machine tools, material handling systems, packaging machines, or industrial process plants. The relay is designed for a
rated switching capacity of 110 A according to IEC 60947, enabling high switching capability under transient loads. The
conventional thermal current rating is 10 A at 50 °C, defining its load capacity under realistic ambient conditions. The
rated insulation voltage is 690 V (IEC 60947), making the device suitable for applications with high voltages. The
associated fuse protection is specified as 10 A gG according to IEC 60947 and VDE 0660, defining the necessary protective measure for the control circuit.
Functions and equipment in detail include a
screw terminal connection for various cable cross-sections: rigid 1.5 to 4 mm², flexible 0.75 to 4 mm² with cable end ferrule, and flexible 0.34 to 1.5 mm² with and without cable end ferrule. The
torque requirement is 1.3 Nm, with mounting possible using a flat-head screwdriver (Ø 6 mm), Phillips screwdriver No. 2 (26 mm), or positioning screwdriver No. 2. The
operating time is 10 ms for coil de-energization and NO opening, and 30–40 ms for coil energization and NO closing, ensuring fast response. The
mechanical life is 20 million switching cycles, and the
maximum operating rate is 10,000 operations per hour, suitable for high stress in continuous processes.
Technology explained simply shows that the device has
immunity to interruptions of 2 ms, increasing reliability during brief voltage drops. The
pickup power and holding power consumption are each 3 W at 20 °C, enabling efficient energy use. The
heat dissipation is also 3 W, defining the thermal load during operation. The
minimum switching voltage is 17 V, and the
minimum switching current is 5 mA, ensuring operational safety with weak signals. The
non-overlapping clearance is 0.5 mm, and the
insulation resistance is greater than 10 MΩ, enhancing electrical safety.
Compatibility and accessories include use with various auxiliary switch blocks such as LA1KN04 (4 openers), LA1KN13 (1 closer, 3 openers), LA1KN40 (4 closers), or LA1KN22 (2S+2O). An
overvoltage limiter 250 V (LA4KE1UG) can be used as protective measure against voltage surges. Mounting is on
rail or panel, with dimensions of 45 mm (width), 58 mm (height), and 57 mm (depth). The
weight is 0.225 kg.
Mounting and installation must comply with standards EN/IEC 60947-5-1, GB/T 14048.5, UL 60947-5-1, CSA C22.2 No. 60947-5-1, and JIS C8201-5-1. The
protection rating IP2x protects against finger contact and solid foreign objects, but not against water. The
operating ambient temperature ranges from -25 °C to 50 °C, and the
storage temperature ranges from -50 °C to 80 °C. The
operating altitude is up to 2,000 m without performance reduction. The
flame resistance corresponds to V1 according to UL 94, defining its fire behavior tolerance. The
mechanical robustness is defined by vibration stress (2 Gn open, 4 Gn closed) and shock stress (10 Gn open, 15 Gn closed) according to IEC 60068-2-6 and -2-27.
Operational advantages include high service life, fast switching time, compact design, and universal mounting capability. The
certifications CB Regulation, CCC, UL, CSA, EAC, CE, UKCA confirm compliance with international safety and quality standards. The device is designed for use in industrial environments with high demands on reliability and performance. The
TC coating according to IEC 60068 ensures high corrosion resistance.
Key terms in the text:
control relay,
auxiliary contactor,
TeSys,
4S,
220 V DC,
IP2x.