| Additional features |
| Coil technology | Integrated bidirectional transient voltage suppressor diodes |
| [Ith] conventional thermal current in free air | 10 A (at 50 °C) |
| [Irms] Rated making capacity | 110 A complies with IEC 60947 |
| Associated fuse | 10 A gG compliant with IEC 60947; 10 A gG compliant with VDE 0660 |
| [Ui] Rated insulation voltage | 690 V corresponds to IEC 60947; 750 V corresponds to VDE 0110 Group C; 690 V corresponds to BS 5424; 600 V corresponds to CSA C22.2 No. 14 |
| Mounting bracket | Rail; Plate |
| Connections - terminals | Spring clamps 1 cable(s) 0.75…1.5 mm² solid; spring clamps 1 cable(s) 0.75…1.5 mm² stranded without cable end |
| Control circuit voltage limits | Operation: 0.8 - 1.15 Uc (at |
| Operating time | 10 ms coil de-energisation and NO opening; 30 - 40 ms coil energisation and NO closing; 15 ms coil de-energisation and NC closing; 25 - 35 ms coil energisation and NC opening |
| Mechanical life | 20 Mcycles |
| Max. operating rate | 10000 cyc/h |
| Immunity to interruptions | 2 ms |
| Absorption power in W | 3 W (at 20 °C) |
| Holding power consumption in W | 3 W at 20 °C |
| Heat emission | 3 W |
| Min. switching voltage | 17 V |
| Min. switching current | 5 mA |
| Non-overlapping distance | 0,5 mm |
| Insulation resistance | > 10 MΩ |
| Height | 58 mm |
| Width | 45 mm |
| Depth | 57 mm |
| Product weight | 0,225 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Main features |
| Product series | TeSys |
| Product name | TeSys CAK |
| Product or component type | Control relay |
| Device short name | CA3K |
| Application of contactor | Control circuit |
| Application category | DC-13; AC-15 |
| Composition of pole contact | 2 S + 2 Ö |
| Control circuit type | DC Standard |
| [Uc] control circuit voltage | 24 V DC |
| Mounting |
| Standards | EN/IEC 60947-5-1; GB/T 14048.5; UL 60947-5-1; CSA C22.2 No. 60947-5-1; JIS C8201-5-1 |
| Product certifications | CB certification; CCC; UL; CSA; EAC; CE; UKCA |
| Coating | TC corresponds to IEC 60068 |
| Operating ambient temperature | -25…50 °C |
| Ambient temperature during storage | -50…80 °C |
| Operating altitude | 2,000 m without derating |
| Flame retardancy | V1 corresponds to UL 94; Requirement 2 corresponds to NF F 16-101; Requirement 2 corresponds to NF F 16-102 |
| Mechanical robustness | Vibrations relay open: 2 Gn, 5 - 300 Hz according to IEC 60068-2-6; Vibrations relay closed: 4 Gn, 5 - 300 Hz according to IEC 60068-2-6; Shocks relay open: 10 Gn for 11 ms according to IEC 60068-2-27; Shocks relay closed: 15 Gn for 11 ms according to IEC 60068-2-27 |
| Packaging units |
| VPE 1 type | PCE |
| Number of devices per package | 1 |
| VPE 1 height | 4,8 cm |
| VPE 1 width | 6,2 cm |
| VPE 1 length | 6,5 cm |
| Packaging weight (Lbs) | 226,0 g |
| VPE 2 type | S02 |
| VPE 2 quantity | 40 |
| VPE 2 height | 15,0 cm |
| VPE 2 width | 30,0 cm |
| VPE 2 length | 40,0 cm |
| VPE 2 weight | 9,441 kg |
The Schneider Electric TeSys CAK auxiliary contactor, type CA3KN223BD3, is a control relay for use in control circuits. It features a 24 V DC coil with integrated bidirectional peak-limiting diode suppressor, serving as protective circuitry to minimize sparking and electrical interference in the control circuit. The device is designed for usage categories DC-13 and AC-15, with a rated insulation voltage up to 690 V (according to IEC 60947) and 600 V (according to CSA C22.2 No. 14). The contact configuration includes 2 normally open (S) and 2 normally closed (Oe) contacts, making it suitable for various control applications. Connections are made via spring-cage terminals, suitable for a cable cross-section of 0.75 to 1.5 mm² for both rigid and flexible conductors without cable ends.
Applications
This auxiliary contactor is designed for demanding industrial applications, particularly in control systems requiring high operating speeds. It is suitable for installations requiring a high switching frequency of up to 10,000 cycles per hour, such as in automation systems, machine controls, or process plants. The high mechanical life of 20 million switching cycles and robust construction ensure long-term operation under industrial conditions.
Functions and Equipment in Detail
The relay coil has an operating power of 3 W at 20 °C and a holding power consumption of also 3 W, resulting in a heat dissipation of 3 W. The operating time is defined: coil de-energization and NO opening occur within 10 ms, coil energization and NO closing between 30 and 40 ms, coil de-energization and NC closing in 15 ms, and coil energization and NC opening between 25 and 35 ms. The minimum switching voltage is 17 V, and the minimum switching current is 5 mA. The operating temperature ranges from -25 °C to 50 °C, and the storage temperature from -50 °C to 80 °C. The device can be used up to an operating altitude of 2,000 m without performance reduction.
Technology Explained Simply
The integrated protective circuit with bidirectional diodes suppresses voltage spikes that may occur when the coil is switched off. This protects not only the relay itself but also other components in the control circuit from damage. The spring-cage terminals allow for quick and secure connections without additional tools. The insulation resistance is greater than 10 MΩ, ensuring high electrical safety. Mechanical robustness is defined by vibration and shock resistance according to IEC 60068-2-6 and IEC 60068-2-27, with values varying depending on the contactor's state (open or closed).
Compatibility and Accessories
The auxiliary contactor is certified to various standards, including EN/IEC 60947-5-1, UL 60947-5-1, CSA C22.2 No. 60947-5-1, JIS C8201-5-1, GB/T 14048.5, as well as certifications such as CB Regulation, CCC, UL, CSA, EAC, CE, and UKCA. It is RoHS- and REACH-compliant. Suitable accessories include auxiliary contact blocks such as LA1KN043 (4 Oe), LA1KN133 (1 S 3 Oe), LA1KN313 (3 S 1 Oe), LA1KN403 (4 S), as well as the auxiliary contact block LA1KN223 (2 S) and identification plates such as LA9D90. These components can be used to extend the contact configuration or for labeling.
Mounting and Installation
Mounting is either on a rail or directly on a panel. Dimensions are 45 mm (width), 58 mm (height), and 57 mm (depth). The product weight is 0.225 kg. Mounting requires no additional tools, as the spring-cage terminals enable simple and secure connections. The ambient temperature during operation ranges from -25 °C to 50 °C, and during storage from -50 °C to 80 °C.
Operational Advantages
The relay is characterized by high reliability and durability, supported by a mechanical life of 20 million cycles and a maximum operating rate of 10,000 cycles per hour. The integrated protective circuit reduces interference in the control circuit. Certifications according to international standards ensure suitability for various markets. The compact design and easy mounting facilitate integration into existing systems.
Flame Retardancy and Coating
The device meets flame retardancy requirement V1 according to UL 94, as well as requirement 2 according to NF F 16-101 and NF F 16-102. The coating corresponds to TC according to IEC 60068, increasing resistance to environmental influences. The associated fuse rating is 10 A gG, according to IEC 60947 and VDE 0660.