| Complementary |
| [Ith] conventional free air thermal current | 10 A (at 55 °C) |
| Associated fuse rating | 10 A gL conforming to VDE 0660; 10 A gL conforming to IEC 60947 |
| [Ui] rated insulation voltage | 690 V conforming to IEC 60947; 690 V conforming to VDE 0110 group C; 690 V conforming to BS 5424; 690 V conforming to UL 508; 690 V conforming to CSA C22.2 No 14 |
| Mounting support | Plate; Rail |
| Connections - terminals | Screw clamp terminals 1 cable(s) 1.5…6 mm²solid; Screw clamp terminals 2 cable(s) 1.5…4 mm²solid; Screw clamp terminals 1 cable(s) 0.5…6 mm²flexible without cable end; Screw clamp terminals 1 cable(s) 0.35…6 mm²flexible with cable end; Screw clamp terminals 2 cable(s) 0.35…1.5 mm²flexible with cable end; Screw clamp terminals 2 cable(s) 0.35…2.5 mm²flexible without cable end |
| Tightening torque | 0.8 N.m - on screw clamp terminals pozidriv No 1 screw head |
| Control circuit voltage limits | Drop-out: 0.2...0.75 Uc (at |
| Operating time | 6...8 ms coil de-energisation and NO opening; 7...14 ms coil energisation and NO closing |
| Mechanical durability | 10 Mcycles |
| Maximum operating rate | 1200 cyc/h |
| Inrush power in VA | 16 VA (at 20 °C) |
| Hold-in power consumption in VA | 4.2 VA (at 20 °C) |
| Heat dissipation | 1.4 W |
| Height | 56 mm |
| Width | 27 mm |
| Depth | 55.5 mm |
| Net weight | 0.132 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | EN/IEC 60947-5-1; UL 60947-5-1; CSA C22.2 No 60947-5-1; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ |
| Product certifications | CB Scheme; cULus; EAC; CE; UKCA |
| IP degree of protection | IP2X |
| Protective treatment | TC conforming to IEC 60068 |
| Ambient air temperature for operation | -20…50 °C |
| Ambient air temperature for storage | -50…70 °C |
| Operating altitude | 2000 m without derating |
| Logistical informations |
| Country of origin | CZ |
| Main |
| Range | TeSys |
| Product name | TeSys CASK |
| Product or component type | Control relay |
| Device short name | CA2SK |
| Contactor application | Control circuit |
| Utilisation category | DC-13; AC-15 |
| Pole contact composition | 2 NO |
| Control circuit type | AC at 50/60 Hz |
| [Uc] control circuit voltage | 230 V AC 50/60 Hz |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 3.500 cm |
| Package 1 Width | 6.000 cm |
| Package 1 Length | 6.500 cm |
| Package 1 Weight | 125.000 g |
| Unit Type of Package 2 | S01 |
| Number of Units in Package 2 | 40 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 15.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 5.137 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 1280 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 80.000 cm |
| Package 3 Length | 60.000 cm |
| Package 3 Weight | 172.384 kg |
The
control relay CA2SK20P7 from the
TeSys series by
Schneider Electric is a compact
auxiliary contactor designed for use in
control circuits. It is used for signal transmission and logic control in industrial systems and operates on an alternating voltage of 230 V AC at 50/60 Hz. The device features two integrated
auxiliary contacts in the configuration
2 S (two normally open contacts) and is designed for mounting on a
plate or
rail. The device width is 27 mm, enabling compact installation in enclosures. The snap-in mounting facilitates easy installation and replacement.
Applications
The CA2SK20P7 is designed for use in
industrial control systems, particularly in applications requiring safe and reliable signal transmission. It is commonly used in conjunction with main power contactors, motors, or other control components to implement auxiliary functions such as feedback, interlock logic, or status indication. The application categories
DC-13 and
AC-15 define the usage areas for direct and alternating current circuits with corresponding loads. The rated insulation voltage of 690 V allows use in systems with high voltage levels, with safety and reliability ensured by standards
IEC 60947-5-1,
UL 60947-5-1, and
CSA C22.2 No. 60947-5-1.
Functions and Equipment in Detail
The device features
screw terminals for connecting cables with cross-sections from 0.35 to 6 mm², allowing both rigid and flexible conductors with or without wire end ferrules to be connected. The tightening torque is 0.8 Nm, ensuring a secure and durable connection. The integrated auxiliary contacts can be expanded by up to four additional auxiliary contacts, allowing functionality to be adapted to individual requirements. The control circuit voltage is 230 V AC, with a release voltage between 0.2 and 0.75 Uc, ensuring reliable de-energization even during voltage fluctuations.
Technology Explained Simply
The coil de-energization time is within 6 to 8 ms, and coil energization and NO closing occur within 7 to 14 ms, enabling fast response to control commands. The mechanical life is 10 million operations, and the maximum operating rate is 1200 operations per hour. The pickup power is 16 VA at 20 °C, and the holding power consumption is 4.2 VA, ensuring efficient power supply during operation. The heat dissipation is 1.4 W, resulting in low thermal load on the surrounding environment. The operating temperature range is from -20 °C to 50 °C, and the storage temperature range is from -50 °C to 70 °C, making the device suitable for use in demanding climatic conditions. The operating altitude is up to 2000 m without performance reduction.
Compatibility and Accessories
The CA2SK20P7 is expandable with various accessories, including
auxiliary switches such as LA1SK20 (2S for CA2SK LC1SK06) or LA1SK11 (1 normally open, 1 normally closed), and
overvoltage limiters such as LA4SKE1E (varistor) or LA4SKE1U (110–250 V AC/DC). These components allow adaptation to specific protection and control requirements. The associated fuse rating is 10 A GL, in accordance with standards VDE 0660 and IEC 60947.
Mounting and Installation
Mounting is done via snap-in fastening on a mounting plate or on a 35-mm rail. The screw terminals allow flexible wiring with various cable types. The dimensions (height 56 mm, width 27 mm, depth 55.5 mm) and weight of 0.132 kg are designed for use in compact enclosures. The protection rating IP2x protects against finger contact and larger objects, but not against dust or water.
Operational Advantages
The CA2SK20P7 offers high operational reliability through compliance with international standards and certifications such as
CE,
cULus,
EAC, and
UKCA. The long mechanical life and high operating rate make it suitable for continuously operated systems. The expandability of auxiliary contacts allows flexible adaptation to different control logics. The low heat dissipation and robust construction ensure reliable performance even under industrial conditions. The operating altitude of 2000 m without performance reduction extends the application range to mountainous or elevated installations.
The
TC coating complies with IEC 60068, ensuring resistance to environmental influences such as humidity, temperature changes, and corrosion. The devices are designed for industrial environments, with an operating temperature range of -20 °C to 50 °C. The storage temperature range is from -50 °C to 70 °C, allowing flexible storage. The warranty period is 18 months.
The product designation
TeSys CASK and the short designation
CA2SK identify the device within the series. The application categories
DC-13 and
AC-15 define the electrical load types for which the device is designed. The rated insulation voltage of 690 V allows use in high-voltage systems, with electrical safety ensured by standards
IEC 60947,
VDE 0110,
BS 5424,
UL 508, and
CSA C22.2 No. 14. The mounting bracket enables flexible installation on a plate or rail. The screw terminals are designed for various cable cross-sections, with a tightening torque of 0.8 Nm ensuring a secure connection. The operating time of 6–8 ms for coil de-energization and 7–14 ms for coil energization ensures fast response. The mechanical life of 10 million operations and maximum operating rate of 1200 operations per hour make the device suitable for continuous operation. The pickup power of 16 VA and holding power consumption of 4.2 VA at 20 °C are relevant for power supply during operation. The heat dissipation of 1.4 W is low and does not burden the environment. The operating altitude of 2000 m without performance reduction extends the application range. The operating temperature range is -20 °C to 50 °C, and the storage temperature range is -50 °C to 70 °C. The protection rating IP2x protects against contact, but not against dust or water. The TC coating complies with IEC 60068, ensuring resistance to environmental influences. The warranty period is 18 months.
Accessories such as
LA4SKE1E,
LA9D90,
LA1SK20,
LA1SK11,
LA4SKC1U, and
LA4SKE1U allow expansion of functionality, particularly through additional auxiliary contacts or overvoltage protection. The associated fuse rating of 10 A GL complies with standards VDE 0660 and IEC 60947, ensuring safety in fault conditions. Mounting on a plate or rail, along with snap-in fastening, simplifies installation. The dimensions and weight are designed for use in compact enclosures. The operating and storage temperature ranges define the operating conditions. The operating altitude of 2000 m without performance reduction extends the application range. The protection rating IP2x protects against contact, but not against dust or water. The TC coating complies with IEC 60068, ensuring resistance to environmental influences. The warranty period is 18 months.