| Complementary |
| [Ith] conventional free air thermal current | 10 A (at 55 °C) |
| Associated fuse rating | 10 A gL conforming to VDE 0660; 10 A gL conforming to IEC 60947 |
| [Ui] rated insulation voltage | 690 V conforming to IEC 60947; 690 V conforming to VDE 0110 group C; 690 V conforming to BS 5424; 690 V conforming to UL 508; 690 V conforming to CSA C22.2 No 14 |
| Mounting support | Rail; Plate |
| Connections - terminals | Screw clamp terminals 1 cable(s) 1.5…6 mm²solid; Screw clamp terminals 2 cable(s) 1.5…4 mm²solid; Screw clamp terminals 1 cable(s) 0.5…6 mm²flexible without cable end; Screw clamp terminals 1 cable(s) 0.35…6 mm²flexible with cable end; Screw clamp terminals 2 cable(s) 0.35…1.5 mm²flexible with cable end; Screw clamp terminals 2 cable(s) 0.35…2.5 mm²flexible without cable end |
| Tightening torque | 0.8 N.m - on screw clamp terminals pozidriv No 1 screw head |
| Control circuit voltage limits | Drop-out: 0.2...0.75 Uc (at |
| Operating time | 6...8 ms coil de-energisation and NO opening; 7...14 ms coil energisation and NO closing |
| Mechanical durability | 10 Mcycles |
| Maximum operating rate | 1200 cyc/h |
| Inrush power in VA | 16 VA (at 20 °C) |
| Hold-in power consumption in VA | 4.2 VA (at 20 °C) |
| Heat dissipation | 1.4 W |
| Height | 56 mm |
| Width | 27 mm |
| Depth | 55.5 mm |
| Net weight | 0.132 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | EN/IEC 60947-5-1; UL 60947-5-1; CSA C22.2 No 60947-5-1 |
| Product certifications | CB Scheme; cULus; EAC; CE; UKCA |
| IP degree of protection | IP2X |
| Protective treatment | TC conforming to IEC 60068 |
| Ambient air temperature for operation | -20…50 °C |
| Ambient air temperature for storage | -50…70 °C |
| Operating altitude | 2000 m without derating |
| Logistical informations |
| Country of origin | CZ |
| Main |
| Range | TeSys |
| Product name | TeSys CASK |
| Product or component type | Control relay |
| Device short name | CA2SK |
| Contactor application | Control circuit |
| Utilisation category | AC-15; DC-13 |
| Pole contact composition | 2 NO |
| Control circuit type | AC at 50/60 Hz |
| [Uc] control circuit voltage | 110 V AC 50/60 Hz |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 3.300 cm |
| Package 1 Width | 6.700 cm |
| Package 1 Length | 5.900 cm |
| Package 1 Weight | 121.000 g |
| Unit Type of Package 2 | S01 |
| Number of Units in Package 2 | 40 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 15.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 4.900 kg |
The
auxiliary contactor of the
TeSys series by
Schneider Electric, type
CA2SK20F7, is a
control relay for use in control circuits. It features two
closing contacts (2S) and a control coil with a rated voltage of
110 V AC at 50/60 Hz. The device is housed in a compact enclosure with a width of
27 mm and is suitable for applications requiring a high operating rate of up to
1200 cycles per hour. The mechanical life is
10 million operations, ensuring high reliability and durability in industrial environments.
Applications
This auxiliary contactor is designed for usage categories
AC-15 (up to 690 V) and
DC-13 (up to 440 V). It is used in control systems for signal transmission, interlocking switching operations, or controlling auxiliary functions in electrical installations. The rated insulation voltage of
690 V allows use in high-voltage systems, while approvals according to
IEC 60947,
VDE 0110,
BS 5424,
UL 508, and
CSA C22.2 No. 14 ensure safety in various regions. The operating altitude is up to
2,000 m without performance reduction, enabling use in high-altitude industrial facilities.
Functions and Equipment in Detail
The device features
screw terminals for connecting cables with cross-sections of
1.5 to 6 mm² (rigid) and
0.35 to 6 mm² (flexible, with or without cable end ferrules). The recommended tightening torque for the terminals is
0.8 Nm. The control circuit voltage limits are defined by a drop range of
0.2 to 0.75 Uc, ensuring reliable operation even under voltage fluctuations. The operating time is
6 to 8 ms for coil de-energization and NO opening, and
7 to 14 ms for coil energization and NO closing. The heat dissipation of the device is
1.4 W, requiring efficient cooling in the surrounding environment.
Technology Explained Simply
The control coil operates at
110 V AC and consumes
16 VA at pickup and
4.2 VA at holding at 20 °C. The conventional thermal current rating is
10 A at 55 °C, describing the thermal load in free air. The associated fuse protection is specified as
10 A GL according to
VDE 0660 and
IEC 60947, limiting short-circuit currents up to
5000 A rms at a maximum of
600 V. The protection class
IP2x protects against finger contact and solid foreign objects, but not against water or dust. The operating temperature range is
-20 °C to 50 °C, and the storage temperature range is
-50 °C to 70 °C.
Compatibility and Accessories
The auxiliary contactor is designed for mounting on a
rail or
plate. It can be combined with various accessories, including
overvoltage limiters such as
LA4SKE1E (varistor) or
LA4SKE1U (110–250 V AC/DC), and
auxiliary switches such as
LA1SK11 (1 closing, 1 opening) or
LA1SK20 (2S for CA2SK/LC1SK06). Additionally, a
label plate LA9D90 is available to clearly mark functions in the enclosure. Mounting on the rail is the recommended option; vertical mounting reduces the mechanical life by approximately 15%.
Mounting and Installation
Mounting is done either on a
rail (e.g. DIN rail) or directly on a
plate. Cable connections are made via screw terminals, and the recommended tightening torque of
0.8 Nm must be observed. Horizontal mounting is recommended; vertical mounting results in a reduction in mechanical life of approximately 15%. The devices are designed for industrial environments, where ambient temperature and air circulation must ensure sufficient cooling.
Operational Advantages
The auxiliary contactor offers high operational safety through certification according to
EN/IEC 60947-5-1,
UL 60947-5-1, and
CSA C22.2 No. 60947-5-1, as well as product certifications including
CB Scheme,
cULus,
EAC,
CE, and
UKCA. Compliance with
RoHS/REACH ensures environmentally compatible production. The high mechanical life and high operating rate make the device particularly suitable for applications in continuously operating systems. The compact design with a width of 27 mm enables dense mounting in enclosures.
Certifications and Standards
The device complies with standards
IEC 60947-5-1,
UL 60947-5-1, and
CSA C22.2 No. 60947-5-1. Certifications include
CB Scheme,
cULus,
EAC,
CE, and
UKCA. The coating complies with
IEC 60068, ensuring resistance to environmental influences such as humidity and temperature fluctuations. The devices are suitable for use in various industries, including marine technology, as indicated by the
Marine approval.