| Complementary |
| [Ith] conventional free air thermal current | 10 A (at 50 °C) |
| Irms rated making capacity | 110 A conforming to IEC 60947 |
| Associated fuse rating | 10 A gG conforming to IEC 60947; 10 A gG conforming to VDE 0660 |
| [Ui] rated insulation voltage | 690 V conforming to IEC 60947; 750 V conforming to VDE 0110 group C; 690 V conforming to BS 5424; 600 V conforming to CSA C22.2 No 14 |
| Mounting support | Rail; Plate |
| Connections - terminals | Screw clamp terminals 1 cable(s) 1.5…4 mm²solid; Screw clamp terminals 2 cable(s) 1.5…4 mm²solid; Screw clamp terminals 1 cable(s) 0.75…4 mm²flexible with cable end; Screw clamp terminals 2 cable(s) 0.75…4 mm²flexible without cable end; Screw clamp terminals 1 cable(s) 0.34…1.5 mm²flexible with cable end; Screw clamp terminals 2 cable(s) 0.34…1.5 mm²flexible without cable end |
| Tightening torque | 1.3 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm; 1.3 N.m - on screw clamp terminals - with screwdriver Philips No 26 mm; 1.3 N.m - on screw clamp terminals - with screwdriver pozidriv No 2 |
| Control circuit voltage limits | Drop-out: 0.2...0.75 Uc (at |
| Operating time | 10...20 ms coil de-energisation and NO opening; 10...20 ms coil energisation and NO closing; 15...25 ms coil de-energisation and NC closing; 5...15 ms coil energisation and NC opening |
| Mechanical durability | 10 Mcycles |
| Maximum operating rate | 10000 cyc/h |
| Immunity to microbreaks | 2 ms |
| Inrush power in VA | 30 VA (at 20 °C) |
| Hold-in power consumption in VA | 4.5 VA (at 20 °C) |
| Heat dissipation | 1.3 W |
| Minimum switching voltage | 17 V |
| Minimum switching current | 5 mA |
| Non overlap distance | 0.5 mm |
| Insulation resistance | > 10 MOhm |
| Height | 58 mm |
| Width | 45 mm |
| Depth | 57 mm |
| Net weight | 0.18 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | EN/IEC 60947-5-1; GB/T 14048.5; UL 60947-5-1; CSA C22.2 No 60947-5-1; JIS C8201-5-1 |
| Product certifications | CB Scheme; CCC; UL; CSA; EAC; CE; UKCA |
| IP degree of protection | IP2X |
| Protective treatment | TC conforming to IEC 60068 |
| Ambient air temperature for operation | -25…50 °C |
| Ambient air temperature for storage | -50…80 °C |
| Operating altitude | 2000 m without derating |
| Flame retardance | V1 conforming to UL 94; Requirement 2 conforming to NF F 16-101; Requirement 2 conforming to NF F 16-102 |
| Mechanical robustness | Vibrations contactor open: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6; Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6; Shocks contactor open: 10 Gn for 11 ms conforming to IEC 60068-2-27; Shocks contactor closed: 15 Gn for 11 ms conforming to IEC 60068-2-27 |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | TeSys |
| Product name | TeSys CAK |
| Product or component type | Control relay |
| Device short name | CA2K |
| Contactor application | Control circuit |
| Utilisation category | AC-15; DC-13 |
| Pole contact composition | 2 NO + 2 NC |
| Control circuit type | AC at 50/60 Hz |
| [Uc] control circuit voltage | 42 V AC 50/60 Hz |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 4.500 cm |
| Package 1 Width | 6.000 cm |
| Package 1 Length | 6.500 cm |
| Package 1 Weight | 180.600 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 50 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 9.272 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 800 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 80.000 cm |
| Package 3 Length | 60.000 cm |
| Package 3 Weight | 156.352 kg |
The Schneider Electric control relay CA2KN22D7 belongs to the TeSys series and is designed as an auxiliary contactor for control circuits. It features a contact configuration of 2 normally closed contacts and 2 normally open contacts (2S+2Oe) and is rated for a control circuit voltage of 42 V AC at 50/60 Hz. The device is suitable for use in industrial installations, where it is employed for signal transmission, controlling auxiliary functions, or interconnecting switching operations in electrical circuits. The compact design with dimensions of 45 mm (width) × 58 mm (height) × 57 mm (depth) allows for flexible mounting on rails or panels. The product is designed for operation in environments with temperatures ranging from -25 °C to 50 °C and can be used up to an operating altitude of 2,000 m without performance reduction.
Applications
The control relay CA2KN22D7 is used in industrial control and switching systems, particularly in applications requiring safe and reliable signal transmission. Typical applications include controlling auxiliary functions in machine controls, interconnecting switching operations in automation systems, or integrating into electrical circuit diagrams where multiple contacts must be connected in parallel or series. The usage categories AC-15 and DC-13 define the operating conditions for alternating and direct current applications, with AC-15 applicable for switching operations in control circuits with inductive loads and DC-13 for direct current applications with inductive loads.
Functions and Features in Detail
The relay features screw terminals for connecting cables with cross-sections from 0.34 to 4 mm², allowing both rigid and flexible conductors with or without wire end ferrules to be connected. The tightening torque is 1.3 Nm, and mounting can be done using a flat-head screwdriver (Ø 6 mm), a Phillips screwdriver (No. 2, 26 mm), or a positioning screwdriver (No. 2). The mechanical life expectancy is 10 million switching cycles, and the maximum operating rate is 10,000 switching operations per hour. The minimum switching voltage is 17 V, and the minimum switching current is 5 mA, ensuring reliability even with weak signals. The release voltage is between 0.2 and 0.75 times the rated voltage, enabling secure de-energization even during voltage fluctuations.
Technology Explained Simply
The relay operates using a coil that is magnetically energized when the control voltage (42 V AC) is applied, actuating the contacts. The contacts close or open depending on the switching operation — in this case, there are two normally open contacts (S) and two normally closed contacts (Oe). The rated make current is 110 A, indicating the relay’s ability to safely switch a current impulse of this magnitude. The rated insulation voltage is 690 V (as per IEC 60947), ensuring electrical insulation between the contacts and the coil. The heat dissipation of the device is 1.3 W, which should be considered when planning heat dissipation in enclosures. The holding power consumption is 4.5 VA at 20 °C, describing the energy consumption during operation.
Compatibility and Accessories
The relay can be combined with various accessories to extend its functionality. These include auxiliary switches such as the LA1KN22 (2S+2Oe, screw terminals), LA1KN31 (3S+1Oe), LA1KN13 (1S+3Oe), or LA1KN40 (4S). Additionally, auxiliary modules such as the LA4KE1E (varistor 32–48 V AC/DC) or nameplates such as the LA9D90 are available. These components can be used to extend the number of contacts, for signal transmission, or for marking switches. Combining the relay with other TeSys products enables seamless integration into existing control systems.
Mounting and Installation
The device can be mounted on a mounting rail (e.g., DIN rail) or directly onto a panel. Mounting is done via screw terminals, and the specified tightening torque (1.3 Nm) must be observed to ensure a secure and durable connection. The protection rating IP2x protects against finger contact and larger objects, but is not waterproof. The TC coating corresponds to IEC 60068 and ensures high corrosion resistance. Mechanical robustness is defined by vibration and shock resistance according to IEC 60068-2-6 and -2-27, with values varying depending on the operating state (open or closed).
Operational Advantages
The control relay CA2KN22D7 offers high operational reliability due to defined switching limits and high mechanical life. The low heat dissipation and compact design facilitate integration into enclosures. Certifications according to EN/IEC 60947-5-1, UL, CSA, CE, and UKCA ensure compliance with international safety and quality standards. Flame retardancy according to UL 94 (V1) and requirements according to NF F 16-101/102 enhance safety in case of fire. The high operating rate of 10,000 operations per hour makes the device suitable for dynamic applications. Use in combination with other TeSys components enables a modular and expandable system architecture.
Certifications and Standards
The device complies with standards EN/IEC 60947-5-1, GB/T 14048.5, UL 60947-5-1, CSA C22.2 No. 60947-5-1, and JIS C8201-5-1. Product certifications include CB scheme, CCC, UL, CSA, EAC, CE, and UKCA. The rated insulation voltage of 690 V (IEC 60947) and the ambient temperature range of -25 °C to 50 °C define the operating conditions. The operating altitude of 2,000 m without performance reduction allows use in mountainous regions or high-rise buildings. Insulation resistance values > 10 MΩ ensure safe electrical isolation between contacts and coil.
Accessories and Extensions
Various auxiliary switches and auxiliary modules are available to extend functionality. These include the LA1KN22 (2S+2Oe, screw terminals), LA1KN31 (3S+1Oe), LA1KN13 (1S+3Oe), LA1KN40 (4S), and LA1KN04 (4Oe). Additionally, the auxiliary module LA4KE1E (varistor 32–48 V AC/DC) and the nameplate LA9D90 are available. These components can be used to extend the number of contacts, for signal transmission, or for marking switches. Combining with other TeSys products enables seamless integration into existing control systems.