| Additional features |
| [Ui] Rated insulation voltage | 800 V AC 50/60 Hz |
| [Uimp] Rated impulse voltage withstand | 8 kV |
| [Ics] Rated operational breaking capacity | 85 kA at 220/240 V AC 50/60 Hz corresponds to IEC 60947-2; 50 kA at 380/415 V AC 50/60 Hz corresponds to IEC 60947-2; 42 kA at 440 V AC 50/60 Hz corresponds to IEC 60947-2; 30 kA at 500 V AC 50/60 Hz corresponds to IEC 60947-2; 11 kA at 525 V AC 50/60 Hz corresponds to IEC 60947-2; 10 kA at 660/690 V AC 50/60 Hz corresponds to IEC 60947-2 |
| Mechanical life | 15000 cycles |
| Electrical lifetime | 8000 cycles at 440 V In/2; 4000 cycles at 440 V In; 6000 cycles at 690 V In/2; 2000 cycles at 690 V In |
| Power dissipation per pole | 39,7 W |
| Mounting bracket | Rear panel |
| Mounting position | Horizontal and vertical; lying on back |
| Connection on top side | front side |
| Connection on underside | front side |
| Terminal pitch | 45 mm |
| Degree of protection | L : for overload protection (long time); SO : for short-time short-circuit protection with fixed delay; I : for instantaneous short-circuit protection |
| Trigger power | 500 A at 65 °C |
| Motor release class | 10; 20; 5 |
| Additional motor protection | Phase unbalance |
| Long-time pick-up adjustment type Ir (thermal protection) | 9 adjustable settings |
| [Ir] Long-time protection pick-up adjustment range | 250 - 500 A |
| Long-time protection delay adjustment type tr | Fixed |
| [tr] setting range of long-time delay | 120 s at 1.5 x Ir for trip class 5; 6.5 s at 6 x Ir for trip class 5; 5 s at 7.2 x Ir for trip class 5; 240 s at 1.5 x Ir for trip class 10; 13.5 s at 6 x Ir for trip class 10; 10 s at 7.2 x Ir for trip class 10; 480 s at 1.5 x Ir for trip class 20; 26 s at 6 x Ir for trip class 20; 20 s at 7.2 x Ir for trip class 20 |
| Thermal storage | 20 minutes before and after tripping |
| Short-time protection pick-up adjustment type Isd | 9 adjustable settings |
| [Isd] Short-time protection pick-up adjustment range | 5 - 13 x Ir |
| Short-time protection delay adjustment type tsd | Fixed |
| Instantaneous protection pick-up adjustment type Ii | Fixed |
| [Ii] Instantaneous protection pick-up adjustment range | 6.500 A |
| Earth fault protection | None |
| Zoneselective interlock ZSI | None |
| Number of slots | 6 socket positions (socket positions) |
| Local signalling | Flashing LED (green) for ready to operate; LED 95 % Ith (red) for temperature above setpoint |
| Width (W) | 140 mm |
| Height (H) | 255 mm |
| Depth (D) | 110 mm |
| Product weight | 6,2 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Main features |
| Product series | ComPacT |
| Product name | ComPacT NSX |
| Device short name | NSX630N |
| Product or component type | Power-cut-out switch |
| Device application | Motor protection |
| Pole description | 3P |
| Description of protected poles | 3D |
| [In] Rated current | 500 A at 65 °C |
| [Ue] Rated operational voltage | 690 V AC 50/60 Hz |
| Type of network | AC |
| Network frequency | 50/60 Hz |
| Suitability for insulation | Yes, complies with EN/IEC 60947-2 |
| Application category | Category A |
| Breaking capacity | N 50 kA 415 V AC |
| Trigger name | MicroLogic 2.3 M |
| Trigger technology | Electronic |
| Tripping unit protection functions | LSoI |
| Control type | Toggle switch |
| Circuit breaker mounting mode | Fixed |
| Mounting |
| Standards | EN/IEC 60947-2 |
| Over voltage category | III |
| Protection class for electric shocks | Class II on front |
| Pollution degree | 3 entspricht IEC 60664-1 |
| Degree of protection (IP) | IP40 complies with IEC 60529 |
| Degree of protection (IK) | IK07 corresponds to IEC 62262 |
| Operating ambient temperature | -25…70 °C |
| Ambient temperature during storage | -50…85 °C |
| Relative humidity | 0…95 % |
| Operating altitude | 0 - 2,000 m without power reduction; 2,000 - 5,000 m with power reduction |
| Packaging units |
| VPE 1 type | PCE |
| Number of devices per package | 1 |
| VPE 1 height | 23,800 cm |
| VPE 1 width | 16,500 cm |
| VPE 1 length | 31,000 cm |
| Packaging weight (Lbs) | 5,777 kg |
| VPE 2 type | S04 |
| VPE 2 quantity | 2 |
| VPE 2 height | 30,000 cm |
| VPE 2 width | 40,000 cm |
| VPE 2 length | 60,000 cm |
| VPE 2 weight | 12,204 kg |
| VPE 3 type | P12 |
| VPE 3 quantity | 8 |
| VPE 3 height | 45,000 cm |
| VPE 3 width | 80,000 cm |
| VPE 3 length | 120,000 cm |
| VPE 3 weight | 60,816 kg |
This ComPacT NSX630N is a complete 3P 3d fixed circuit breaker designed to optimize space and breaking capacity. It is an optimal choice for motor protection applications. The breaking capacity (Icu) is 50 kA rms at 415 VAC, 50/60 Hz. The operating voltage is 690 VAC 50/60 Hz. This product features a MicroLogic 2.3 M electronic trip unit rated at 500 A. The MicroLogic 2.3 M trip unit offers adjustable long and short time protection functions and fixed instantaneous protection. This 3-pole version (140 mm x 255 mm x 110 mm) is supplied with a wide range of optional features and accessories. It is compliant with international standards (IEC 60947), CCC, EAC and marine specifications. ComPacT NSX630N is part of Schneider Electric’s EcoStruxure Power architecture.