| Complementary |
| [Ui] rated insulation voltage | 800 V AC 50/60 Hz |
| [Uimp] rated impulse withstand voltage | 8 kV |
| [Ics] rated service breaking capacity | 85 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2; 80 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2; 75 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Mechanical durability | 20000 cycles |
| Electrical durability | 20000 cycles at 440 V In/2; 10000 cycles at 440 V In; 10000 cycles at 690 V In/2; 5000 cycles at 690 V In |
| Power dissipation per pole | 17.6 W |
| Mounting support | Backplate |
| Mounting position | Horizontal and vertical; Flat on the back |
| Upside connection | Front |
| Downside connection | Front |
| Connection pitch | 35 mm |
| Protection type | L : for overload protection (long time); S : for short time short-circuit protection; I : for instantaneous short-circuit protection |
| Trip unit rating | 100 A at 40 °C |
| Long-time pick-up adjustment type Ir (thermal protection) | Adjustable 9 settings |
| [Ir] long-time protection pick-up adjustment range | 40...100 A |
| Long-time protection delay adjustment type tr | Adjustable |
| [tr] long-time delay adjustment range | 15…400 s at 1.5 x Ir; 0.5…16 s at 6 x Ir; 0.35…11 s at 7.2 x Ir |
| Thermal memory | 20 minutes before and after tripping |
| Short-time protection pick-up adjustment type Isd | Adjustable 9 settings |
| [Isd] Short-time protection pick-up adjustment range | 1.5...10 x Ir |
| Short-time protection delay adjustment type tsd | Adjustable 5 settings |
| [tsd] short-time delay adjustment range | 0…0.4 s I²t=off; 0.1…0.4 s I²t=on |
| Instantaneous protection pick-up adjustment type Ii | Adjustable |
| [Ii] instantaneous protection pick-up adjustment range | 1.5...15 x In |
| Earth-leakage protection | Without |
| Zone selective interlocking ZSI | With |
| Number of slots | 5 slot(s) |
| Local signalling | Flashing LED (green) for ready to operate; LED 105 % Ir (red) for overload; LED 90 % Ir (orange) for overload |
| Display type | LCD display |
| Type of measurement | Energy meter |
| Communication of data | Energy metering; Instantaneous and demand values; Maximeters/minimeters; Time-stamped histories and event tables; Maintenance indicators; Protection and alarm settings; Demand current and power; Power quality |
| Width (W) | 105 mm |
| Height (H) | 161 mm |
| Depth (D) | 86 mm |
| Net weight | 2.4 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | EN/IEC 60947-2 |
| Overvoltage category | III |
| Electrical shock protection class | Class II on front face |
| Pollution degree | 3 conforming to IEC 60664-1 |
| IP degree of protection | IP40 conforming to IEC 60529 |
| IK degree of protection | IK07 conforming to IEC 62262 |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -40…85 °C |
| Relative humidity | 0…95 % |
| Operating altitude | 0...2000 m without derating; 2000 m...5000 m with derating |
| Main |
| Range | ComPacT |
| Product name | ComPacT NSX |
| Device short name | NSX250HB1 |
| Product or component type | Circuit breaker |
| Device application | Distribution |
| Poles description | 3P |
| Protected poles description | 3D |
| [In] rated current | 100 A at 40 °C |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
| Network type | AC |
| Network frequency | 50/60 Hz |
| Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
| Utilisation category | Category A |
| Breaking capacity | 85 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2; 80 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2; 75 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Breaking capacity code | HB1 75 kA 690 V AC |
| Trip unit name | MicroLogic 5.2 E |
| Trip unit technology | Electronic |
| Trip unit protection functions | LSI |
| Control type | Toggle |
| Circuit breaker mounting mode | Fixed |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 11.000 cm |
| Package 1 Width | 14.000 cm |
| Package 1 Length | 20.000 cm |
| Package 1 Weight | 2.139 kg |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 4 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 8.976 kg |
| Unit Type of Package 3 | P12 |
| Number of Units in Package 3 | 32 |
| Package 3 Height | 45.000 cm |
| Package 3 Width | 80.000 cm |
| Package 3 Length | 120.000 cm |
| Package 3 Weight | 83.808 kg |
This ComPacT NSX250HB1 is a complete 3P 3d fixed circuit breaker designed to optimize space and breaking capacity. It is an optimal choice for all standard and special applications. The breaking capacity (Icu) is 85 kA rms at 500 VAC 50/60 Hz and 75 kA rms at 690 VAC 50/60 Hz. The operating voltage is 690 VAC 50/60 Hz. This product has a MicroLogic 5.2 E electronic trip unit with a rating of 100 A. The MicroLogic 5.2 E trip unit offers adjustable long-term, short-term and instantaneous protection. MicroLogic 5.2 E has an integrated display for fine adjustment and display of the energy meter. This 3-pole version (105 mm x 161 mm x 86 mm) comes with a wide range of optional features and accessories. It is compliant with international standards (IEC 60947), CCC, EAC and marine specifications. ComPacT NSX250HB1 is part of Schneider Electric's EcoStruxure Power architecture.