Schneider Electric C25N42D250, EAN: 3606481998323

Schneider Electric C25N42D250 power circuit breaker

Industrial Material > Control devices / Pilot devices > Breakers and disconnectors

Schneider Electric C25N42D250 power circuit breaker

Lieske Part No. 1894647
Mfg Part No C25N42D250
EAN-Code 3606481998323
Manufacturer Schneider Electric
Here only 1.843,95 EUR
2.194,30 EUR incl. VAT

Further information for Schneider Electric C25N42D250 power circuit breaker

Additional features
[Ui] Rated insulation voltage800 V AC 50/60 Hz
[Uimp] Rated impulse voltage withstand8 kV
[Ics] Rated operational short-circuit breaking capacity90 kA at 220/240 V AC 50/60 Hz complies with IEC 60947-2; 50 kA at 380/415 V AC 50/60 Hz complies with IEC 60947-2; 50 kA at 440 V AC 50/60 Hz complies with IEC 60947-2; 36 kA at 500 V AC 50/60 Hz complies with IEC 60947-2; 35 kA at 525 V AC 50/60 Hz complies with IEC 60947-2; 10 kA at 660/690 V AC 50/60 Hz complies with IEC 60947-2
Mechanical life20000 cycles
Electrical lifetime20000 cycles at 440 V In/2; 10000 cycles at 440 V In; 10000 cycles at 690 V In/2; 5000 cycles at 690 V In
Power dissipation per pole17,6 W
Mounting bracketRear panel
Mounting positionHorizontal and vertical; lying on back
Connection on top sidefront side
Connection on undersidefront side
Terminal pitch35 mm
Degree of protectionL : for overload protection (long time); SO : for short-time short-circuit protection with fixed delay; I : for instantaneous short-circuit protection
Trigger power250 A at 40 °C
[Ir] type of long-time pickup setting (thermal protection)9 adjustable settings
[Ir] Long-time protection pick-up adjustment range100 - 250 A
[tr] Type of long-time protection delay adjustmentFixed
[tr] adjustable long-time delay range400 s at 1.5 x Ir; 16 s at 6 x Ir; 11 s at 7.2 x Ir
Neutral protection settings0.5 x Ir (3d + N/2); 1 x Ir (4D); No protection (3D)
Thermal storage20 minutes before and after tripping
[Isd] type of short-time protection setting9 adjustable settings
[Isd] Short-time protection adjustment range1,5 - 10 x Ir
[tsd] Type of short-time protection delay adjustmentFixed
[Ii] type of instantaneous short-circuit protection settingFixed
[Ii] setting range of instantaneous short-circuit protection3.000 A
Earth fault protectionNone
Zoneselective interlock ZSINone
Number of sockets for electrical auxiliary devices5 socket (sockets)
Local signallingBlinking LED (green) for ready; LED 105 % Ir (red) for overload; LED 90 % Ir (orange) for overload
Width (B)140 mm
Height (H)161 mm
Depth (T)86 mm
Product weight2,8 kg
Contractual warranty
Warranty (in months)18
Main features
Product seriesComPacT
Product nameComPacT NSX
Device short nameNSX250N
Product or component typePower-cut-out switch
Device applicationDistribution
Pole description4P
Description of protected poles4D; 3d + N/2; 3d + N/2
Neutral positionLeft
[In] Rated current250 A at 40 °C
[Ue] Rated operational voltage690 V AC 50/60 Hz
Type of networkAC
Network frequency50/60 Hz
Suitability for insulationYes, complies with EN/IEC 60947-2
Application categoryCategory A
Power classN 50 kA 415 V AC
Trigger nameMicroLogic 2.2
Trigger technologyElectronic
Tripping unit protection functionsLSoI
Control typeToggle switch
Mounting type of power switchFixed
Mounting
StandardsEN/IEC 60947-2
Over voltage categoryIII
Protection class for electric shocksClass II on front
Pollution degree3 entspricht IEC 60664-1
Degree of protection (IP)IP40 complies with IEC 60529
Degree of protection (IK)IK07 corresponds to IEC 62262
Operating ambient temperature-25…70 °C
Ambient temperature during storage-50…85 °C
Relative humidity0…95 %
Operating altitude0 - 2,000 m without power reduction; 2,000 - 5,000 m with power reduction
Packaging units
VPE 1 typePCE
Number of devices per package1
VPE 1 height14,200 cm
VPE 1 width15,000 cm
VPE 1 length19,500 cm
Packaging weight (Lbs)2,634 kg
VPE 2 typeS03
VPE 2 quantity6
VPE 2 height30,000 cm
VPE 2 width30,000 cm
VPE 2 length40,000 cm
VPE 2 weight16,180 kg
This ComPacT NSX250N is a complete 4P 4d fixed circuit breaker designed to optimize space and breaking capacity. It is an optimal choice for all standard and special applications. The breaking capacity (Icu) is 50 kA rms at 415 VAC, 50/60 Hz. The operating voltage is 690 VAC 50/60 Hz. This product features a MicroLogic 2.2 electronic trip unit rated at 250 A. The MicroLogic 2.2 trip unit offers customizable long and short time protection functions as well as fixed instantaneous protection. This 4-pole version (140 mm x 161 mm x 86 mm) comes with a wide range of optional features and accessories. It is compliant with international standards (IEC 60947), CCC, EAC and marine specifications. ComPacT NSX250N is part of Schneider Electric’s EcoStruxure Power architecture.