| Additional features |
| [Ui] Rated insulation voltage | 500 V AC 50/60 Hz |
| [Uimp] Rated impulse voltage withstand | 8 kV |
| [Ics] Rated operational short-circuit breaking capacity | 90 kA at 220/240 V AC 50/60 Hz complies with IEC 60947-2; 50 kA at 380/415 V AC 50/60 Hz complies with IEC 60947-2; 50 kA at 440 V AC 50/60 Hz complies with IEC 60947-2; 36 kA at 500 V AC 50/60 Hz complies with IEC 60947-2; 35 kA at 525 V AC 50/60 Hz complies with IEC 60947-2; 10 kA at 660/690 V AC 50/60 Hz complies with IEC 60947-2 |
| Mechanical life | 20000 cycles |
| Electrical lifetime | 20000 cycles at 440 V In/2; 10000 cycles at 440 V In; 10000 cycles at 690 V In/2; 5000 cycles at 690 V In |
| Power dissipation per pole | 25 W N; 25 W L1 and L3; 20.6 W L2 |
| Mounting bracket | Rear panel |
| Mounting position | Horizontal and vertical; lying on back |
| Connection on top side | front side |
| Connection on underside | front side |
| Terminal pitch | 35 mm |
| Degree of protection | L : for overload protection (long-time); SO : for short-time short-circuit protection with fixed delay; I : for instantaneous short-circuit protection; R : for earth fault protection |
| Trigger power | 160 A at 40 °C |
| [Ir] type of long-time pickup setting (thermal protection) | 9 adjustable settings |
| [Ir] Long-time protection pick-up adjustment range | 63 - 160 A |
| [tr] Type of long-time protection delay adjustment | Fixed |
| [tr] adjustable long-time delay range | 400 s at 1.5 x Ir; 16 s at 6 x Ir; 11 s at 7.2 x Ir |
| Thermal storage | 20 minutes before and after tripping |
| [Isd] type of short-time protection setting | Adjustable |
| [Isd] Short-time protection adjustment range | 1,5 - 10 x Ir |
| [tsd] Type of short-time protection delay adjustment | Fixed |
| [Ii] type of instantaneous short-circuit protection setting | Fixed |
| [Ii] setting range of instantaneous short-circuit protection | 2.400 A |
| Earth fault protection | Integrated |
| Earth fault protection class | Class A |
| [IΔn] type of residual current protection sensitivity setting | Adjustable |
| [IΔn] setting range of sensitivity for residual current protection | 30 mA; 100 mA; 300 mA; 500 mA; 1 A; 3 A; 5 A |
| Specific mode for earth fault protection | Off with the rotary switch ΙΔn |
| [Δt] Type of residual current protection time delay adjustment | Adjustable |
| [Δt] Adjustment range for earth fault protection time delay | 0 ms; 60 ms; 150 ms; 500 ms; 1 s |
| Zoneselective interlock ZSI | None |
| Number of sockets for electrical auxiliary devices | 5 socket (sockets) |
| Local signalling | Blinking LED (green) for ready; LED 105 % Ir (red) for overload; LED 90 % Ir (orange) for overload |
| Width (B) | 105 mm |
| Height (H) | 161 mm |
| Depth (T) | 86 mm |
| Product weight | 2,4 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Main features |
| Product series | ComPacT |
| Product name | ComPacT NSX |
| Device short name | NSX250N |
| Product or component type | Earth fault circuit breaker |
| Device application | Distribution |
| Pole description | 3P |
| Description of protected poles | 3D |
| [In] Rated current | 160 A at 40 °C |
| [Ue] Rated operational voltage | 440 V AC 50/60 Hz |
| Type of network | AC |
| Network frequency | 50/60 Hz |
| Suitability for insulation | Yes, complies with EN/IEC 60947-2 |
| Application category | Category A |
| Power class | N 50 kA 415 V AC |
| Trigger name | MicroLogic 4.2 |
| Trigger technology | Electronic |
| Tripping unit protection functions | LSoIR |
| Control type | Toggle switch |
| Mounting type of power switch | Fixed |
| Mounting |
| Standards | EN/IEC 60947-2 |
| Over voltage category | IV |
| Protection class for electric shocks | Class II on front |
| Pollution degree | 3 entspricht IEC 60664-1 |
| Degree of protection (IP) | IP40 complies with IEC 60529 |
| Degree of protection (IK) | IK07 corresponds to IEC 62262 |
| Operating ambient temperature | -25…70 °C |
| Ambient temperature during storage | -50…85 °C |
| Relative humidity | 0…95 % |
| Operating altitude | 0 - 2,000 m without power reduction; 2,000 - 5,000 m with power reduction |
| Packaging units |
| VPE 1 type | PCE |
| Number of devices per package | 1 |
| VPE 1 height | 14,000 cm |
| VPE 1 width | 11,500 cm |
| VPE 1 length | 19,000 cm |
| Packaging weight (Lbs) | 2,380 kg |
| VPE 2 type | S03 |
| VPE 2 quantity | 6 |
| VPE 2 height | 30,000 cm |
| VPE 2 width | 30,000 cm |
| VPE 2 length | 40,000 cm |
| VPE 2 weight | 13,282 kg |
This ComPacT NSX250N is a complete 3P 3d fixed circuit breaker designed to optimize space and breaking capacity. It is an optimal choice for all standard and special applications. The breaking capacity (Icu) is 50 kA rms at 415 VAC 50/60 Hz. The operating voltage is 440 VAC 50/60 Hz. This product features a MicroLogic 4.2 Vigi electronic trip unit rated at 160 A and integrated adjustable residual current protection. MicroLogic 4.2 Vigi also offers customizable long-term and short-term protection functions as well as fixed instantaneous protection. This 3-pole version (105 mm x 161 mm x 86 mm) comes with a wide range of optional features and accessories. It is compliant with international standards (IEC 60947), CCC, EAC and marine specifications. ComPacT NSX250N is part of Schneider Electric's EcoStruxure Power architecture.