| Complementary |
| [Ui] rated insulation voltage | 750 V DC conforming to IEC 60947-2 |
| [Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947-2 |
| [Ics] rated service breaking capacity | 12.5 kA at 24...300 V DC conforming to IEC 60947-2; 12.5 kA at 300...600 V DC conforming to IEC 60947-2 |
| Mechanical durability | 5000 cycles |
| Electrical durability | 2000 cycles at 600 V In/2; 1000 cycles at 600 V In |
| Mounting support | Backplate |
| Mounting position | Horizontal and vertical; Flat on the back |
| Upside connection | Front |
| Downside connection | Front |
| Connection pitch | 45 mm |
| Protection type | L : for overload protection (thermal); I : for short-circuit protection (magnetic) |
| Trip unit rating | 800 A at 40 °C |
| Long-time pick-up adjustment type Ir (thermal protection) | Adjustable |
| [Ir] long-time protection pick-up adjustment range | 0.7...1 x In |
| Long-time protection delay adjustment type tr | Fixed |
| Instantaneous protection pick-up adjustment type Ii | Adjustable |
| [Ii] instantaneous protection pick-up adjustment range | 2.5...5 x In |
| Earth-leakage protection | Without |
| Number of slots | 6 slot(s) |
| Width (W) | 185 mm |
| Height (H) | 485 mm |
| Depth (D) | 110 mm |
| Net weight | 9.4 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | EN/IEC 60947-2 |
| Overvoltage category | III |
| Electrical shock protection class | Class II on front face |
| Pollution degree | 3 conforming to IEC 60664-1 |
| IP degree of protection | IP40 conforming to IEC 60529 |
| IK degree of protection | IK07 conforming to IEC 62262 |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -50…85 °C |
| Relative humidity | 0…95 % |
| Operating altitude | 0...2000 m without derating; 2000 m...5000 m with derating |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | ComPacT |
| Product name | ComPacT NSX DC |
| Device short name | NSX1200 DC |
| Product or component type | Circuit breaker |
| Device application | Distribution |
| Poles description | 2P |
| Protected poles description | 2D |
| [In] rated current | 800 A at 40 °C |
| [Ue] rated operational voltage | 600 V DC |
| Network type | DC |
| Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
| Utilisation category | Category A |
| Breaking capacity | 50 kA Icu at 24...300 V DC 1 pole conforming to IEC 60947-2; 50 kA Icu at 300...600 V DC 2 poles in series conforming to IEC 60947-2 |
| Breaking capacity code | N 50 kA 600 V DC |
| Trip unit name | TM-DC |
| Trip unit technology | Thermal-magnetic |
| Trip unit protection functions | LI |
| Control type | Toggle |
| Circuit breaker mounting mode | Fixed |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 30.0 cm |
| Package 1 Width | 40.0 cm |
| Package 1 Length | 60.0 cm |
| Package 1 Weight | 10.182 kg |
ComPacT NSX1200N DC is a complete fixed 2-pole circuit breaker designed to optimize space and breaking capacity. It is an optimal choice for applications using DC voltages. The breaking capacity (Icu) is 50 kA rms at 600 VDC. The operating voltage is 600 VDC. This product has a thermal-magnetic trip device (TM-DC) with a rating of 800 A. The TM-DC trip device provides adjustable thermal overload protection and adjustable magnetic protection. The dimensions are 350 mm x 185 mm x 110 mm (H x W x D). It is compliant with international standards (EN/IEC 60947), CCC, EAC and marine specifications.