| Complementary |
| [Ui] rated insulation voltage | 800 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947-2 |
| [Ics] rated service breaking capacity | 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2; 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2; 36 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2; 90 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 |
| Mechanical durability | 40000 cycles conforming to IEC 60947-2 |
| Electrical durability | 40000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2; 15000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2; 20000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2; 7500 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2 |
| Mounting support | Backplate |
| Upside connection | Front |
| Downside connection | Front |
| Connection pitch | 35 mm |
| Protection type | Without protection |
| Width (W) | 105 mm |
| Height (H) | 161 mm |
| Depth (D) | 86 mm |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | EN/IEC 60947-2; UL 60947-4-1 |
| Overvoltage category | III |
| Electrical shock protection class | Class II on front face |
| Pollution degree | 3 conforming to IEC 60664-1 |
| IP degree of protection | IP40 conforming to IEC 60529 |
| IK degree of protection | IK07 conforming to IEC 62262 |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -50…85 °C |
| Logistical informations |
| Country of origin | PL |
| Main |
| Range | ComPacT |
| Product name | ComPacT NSX |
| Device short name | NSX160N |
| Product or component type | Basic frame |
| Device application | Distribution |
| Poles description | 3P |
| [In] rated current | 160 A at 40 °C |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Network type | AC |
| Network frequency | 50/60 Hz |
| Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
| Utilisation category | Category A |
| Breaking capacity code | N 50 kA 415 V AC |
| Control type | Toggle |
| Mounting mode | Fixed |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 14.000 cm |
| Package 1 Width | 11.200 cm |
| Package 1 Length | 19.200 cm |
| Package 1 Weight | 1.492 kg |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 7 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 10.847 kg |
| Unit Type of Package 3 | P12 |
| Number of Units in Package 3 | 56 |
| Package 3 Height | 42.500 cm |
| Package 3 Width | 80.000 cm |
| Package 3 Length | 120.000 cm |
| Package 3 Weight | 97.574 kg |
This is a 3-pole basic switch for ComPacT NSX160N. ComPacT NSX is designed to optimize space and breaking capacity for all standard and special applications. This basic switch is supplied without trip unit and is compatible with all types of trip units that must be ordered separately. The breaking capacity Icu is 50 kA at 415 VAC 50/60 Hz. The operating voltage is 690 VAC 50/60 Hz (limited to 440 VAC 50/60 Hz if residual current protection is present). It can be equipped with a wide range of optional features and accessories. The dimensions are 105 mm x 161 mm x 86 mm. It ensures compliance with international standards (IEC 60947), CCC, EAC and marine specifications. ComPacT NSX160N is part of Schneider Electric's EcoStruxure Power architecture.