| Complementary |
| [Ui] rated insulation voltage | 750 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947-2 |
| [Ics] rated service breaking capacity | 85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2; 25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2; 25 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2; 18 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2; 8 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2; 85 kA at 250 V DC 50/60 Hz conforming to IEC 60947-2; 85 kA at 500 V DC 50/60 Hz conforming to IEC 60947-2 |
| Mechanical durability | 20000 cycles |
| Electrical durability | 20000 cycles at 277 V In/2; 10000 cycles at 277 V In |
| Power dissipation per pole | 13.95 W |
| Mounting support | Backplate |
| Mounting position | Horizontal and vertical; Flat on the back |
| Upside connection | Front |
| Downside connection | Front |
| Connection pitch | 35 mm |
| Protection type | L : for overload protection (thermal); I : for short-circuit protection (magnetic) |
| Trip unit rating | 160 A at 40 °C |
| Long-time pick-up adjustment type Ir (thermal protection) | Fixed |
| [Ir] long-time protection pick-up adjustment range | 1 x In |
| Long-time protection delay adjustment type tr | Fixed |
| Instantaneous protection pick-up adjustment type Ii | Fixed |
| [Ii] instantaneous protection pick-up adjustment range | 1250 A |
| Earth-leakage protection | Without |
| Width (W) | 70 mm |
| Height (H) | 161 mm |
| Depth (D) | 86 mm |
| Net weight | 1.2 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | EN/IEC 60947-2 |
| Overvoltage category | III |
| Electrical shock protection class | Class II on front face |
| Pollution degree | 3 conforming to IEC 60664-1 |
| IP degree of protection | IP40 conforming to IEC 60529 |
| IK degree of protection | IK07 conforming to IEC 62262 |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -50…85 °C |
| Relative humidity | 0…95 % |
| Operating altitude | 0...2000 m without derating; 2000 m...5000 m with derating |
| Logistical informations |
| Country of origin | PL |
| Main |
| Range | ComPacT |
| Product name | ComPacT NSX |
| Device short name | NSX160M |
| Product or component type | Circuit breaker |
| Device application | Distribution |
| Poles description | 2P |
| Protected poles description | 2D |
| [In] rated current | 160 A at 40 °C |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz; 500 V DC |
| Network type | AC; DC |
| Network frequency | 50/60 Hz |
| Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
| Utilisation category | Category A |
| Breaking capacity | 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2; 25 kA Icu at 380/415 V AC 50/60 Hz 1P conforming to IEC 60947-2; 25 kA Icu at 440 V AC 50/60 Hz 1P conforming to IEC 60947-2; 18 kA Icu at 500/525 V AC 50/60 Hz 2P conforming to IEC 60947-2; 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2; 85 kA Icu at 250 V DC 50/60 Hz 1 pole conforming to IEC 60947-2; 85 kA Icu at 500 V DC 50/60 Hz 2 poles in series conforming to IEC 60947-2 |
| Breaking capacity code | M 25 kA 415 V AC |
| Trip unit name | TM-D |
| Trip unit technology | Thermal-magnetic |
| Trip unit protection functions | LI |
| Control type | Toggle |
| Circuit breaker mounting mode | Fixed |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 8.100 cm |
| Package 1 Width | 13.000 cm |
| Package 1 Length | 17.500 cm |
| Package 1 Weight | 1.280 kg |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 12 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 15.950 kg |
ComPacT NSX 160M ist ein kompletter, fest eingebauter 2-poliger Leistungsschalter zur Optimierung von Platz und Ausschaltvermögen. Es ist eine optimale Wahl für alle Standard- und Sonderanwendungen. Das Ausschaltvermögen (Icu) beträgt 25 kA eff. bei 240 VAC, 50/60 Hz. Die Betriebsspannung beträgt 277 VAC 50/60 Hz. Dieses Produkt verfügt über ein thermo-magnetisches Auslösegerät (TMD) mit einer Nennleistung von 160 A. Das Auslösegerät TMD bietet einen festen thermischen Überlastschutz und einen festen magnetischen Schutz. Die Abmessungen betragen 161 mm x 70 mm x 86 mm (H x B x T). Sie ist konform mit internationalen Normen (EN/IEC 60947), CCC, EAC und Marinespezifikationen.