Schneider Electric C12E6TM160B, EAN: 3606481989857

Schneider Electric C12E6TM160B circuit breaker 160A

Schneider Electric C12E6TM160B circuit breaker 160A

Lieske Part No. 700445
Mfg Part No C12E6TM160B
EAN-Code 3606481989857
Manufacturer Schneider Electric
Here only 576,89 EUR
686,50 EUR incl. VAT

Further information for Schneider Electric C12E6TM160B circuit breaker 160A

Additional features
[Ui] Rated insulation voltage800 V AC 50/60 Hz
[Uimp] Rated impulse voltage withstand8 kV
[Ics] Rated operational short-circuit breaking capacity25 kA at 220 - 240 V AC 50/60 Hz corresponds to IEC 60947-2; 16 kA at 380 - 415 V AC 50/60 Hz corresponds to IEC 60947-2; 10 kA at 440 V AC 50/60 Hz corresponds to IEC 60947-2
Mechanical life20000 cycles
Electrical lifetime20000 cycles at 440 V In/2; 10000 cycles at 440 V In
Power dissipation per pole13,7 W
Mounting bracketRear panel
Mounting positionHorizontal and vertical; lying on back
Connection on top sidefront side
Connection on undersidefront side
Terminal clampsCable lug/busbar
Terminal pitch35 mm with terminal extensions; 27 mm without terminal extensions
9-mm pitch12 modules
Trigger power160 A at 40 °C
[Ir] type of long-time pickup setting (thermal protection)Adjustable
[Ir] Long-time protection pick-up adjustment range0,7 - 1 x In
[tr] Type of long-time protection delay adjustmentFixed
Neutral conductor protection settingNo protection (3D)
[Ii] type of instantaneous short-circuit protection settingFixed
[Ii] setting range of instantaneous short-circuit protection1.250 A
Earth fault protectionNone
Number of sockets for electrical auxiliary devices1 socket (sockets) for auxiliary switch OF; 1 socket (sockets) for alarm switch SD; 1 socket (sockets) for voltage release MN or MX
Local signallingGreen status bit for auxiliary switch available
Width (B)108 mm
Height (H)137 mm
Depth (T)80 mm
Product weight1,42 kg
ColourGrey (RAL 7016)
Contractual warranty
Warranty (in months)18
Main features
Product seriesComPacT
Product nameComPacT NSXm
Device short nameNSXm 160E
Product or component typePower-cut-out switch
Device applicationDistribution
Pole description4P
Description of protected poles3D
Neutral positionLeft
[In] Rated current160 A at 40 °C
[Ue] Rated operational voltage440 V AC 50/60 Hz
Type of networkAC
Network frequency50/60 Hz
Suitability for insulationYes, complies with IEC 60947-2
Application categoryCategory A
[Icu] Rated short-circuit breaking capacity25 kA Icu at 220 - 240 V AC 50/60 Hz corresponds to IEC 60947-2; 16 kA Icu at 380 - 415 V AC 50/60 Hz corresponds to IEC 60947-2; 10 kA Icu at 440 V AC 50/60 Hz corresponds to IEC 60947-2
Power classE 16 kA 415 V AC
Trigger nameTM-D
Trigger technologyThermal-magnetic
Tripping unit protection functionsLI
Control typeToggle switch
Mounting type of power switchFixed
Mounting
StandardsEN/IEC 60947-2
Over voltage categoryIII
Protection class for electric shocksClass II on front
Pollution degree3 entspricht IEC 60664-1
Degree of protection (IP)IP40 complies with IEC 60529
Degree of protection (IK)IK07 corresponds to IEC 62262
Operating ambient temperature-25…70 °C
Ambient temperature during storage-50…85 °C
Relative humidity0…95 %
Operating altitude2000 m without power reduction; 5000 m with power reduction
Packaging units
VPE 1 typePCE
Number of devices per package1
VPE 1 height12,0 cm
VPE 1 width11,5 cm
VPE 1 length21,0 cm
Packaging weight (Lbs)1,388 kg
VPE 2 typeS03
VPE 2 quantity6
VPE 2 height30,0 cm
VPE 2 width30,0 cm
VPE 2 length40,0 cm
VPE 2 weight8,704 kg
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/700445
qrcode für Schneider Electric C12E6TM160B circuit breaker 160A