| Complementary |
| [Ui] rated insulation voltage | 750 V DC conforming to IEC 60947-2 |
| [Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947-2 |
| [Ics] rated service breaking capacity | 36 kA at 250 V DC conforming to IEC 60947-2 (1P); 36 kA at 24...125 V DC conforming to IEC 60947-2 (1P); 36 kA at 500 V DC conforming to IEC 60947-2 (2P); 36 kA at 750 V DC conforming to IEC 60947-2 (3P) |
| Maximum breaking time | 10 ms |
| Mechanical durability | 10000 cycles conforming to IEC 60947-2 |
| Electrical durability | 10000 cycles 250 V DC In/2 conforming to IEC 60947-2; 10000 cycles 500 V DC In/2 conforming to IEC 60947-2; 10000 cycles 750 V DC In/2 conforming to IEC 60947-2; 5000 cycles 250 V DC In conforming to IEC 60947-2; 5000 cycles 500 V DC In conforming to IEC 60947-2; 5000 cycles 750 V DC In conforming to IEC 60947-2 |
| Mounting support | Backplate |
| Upside connection | Front |
| Downside connection | Front |
| Connection pitch | 35 mm |
| Protection type | Without protection |
| Width (W) | 105 mm |
| Height (H) | 161 mm |
| Depth (D) | 86 mm |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | EN/IEC 60947-2 |
| Overvoltage category | III |
| Electrical shock protection class | Class II on front face |
| Pollution degree | 3 conforming to IEC 60664-1 |
| IP degree of protection | IP40 conforming to IEC 60529 |
| IK degree of protection | IK07 conforming to EN 50102 |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -50…85 °C |
| Logistical informations |
| Country of origin | PL |
| Main |
| Range | ComPacT |
| Product name | ComPacT NSX DC |
| Device short name | NSX100F DC |
| Product or component type | Basic frame |
| Device application | Distribution |
| Poles description | 3P |
| [In] rated current | 100 A at 40 °C |
| [Ue] rated operational voltage | 750 V DC conforming to IEC 60947-2 |
| Network type | DC |
| Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
| Utilisation category | Category A |
| Breaking capacity | 36 kA Icu at 250 V DC 1P conforming to IEC 60947-2; 36 kA Icu at 24...125 V DC 1P conforming to IEC 60947-2; 36 kA Icu at 500 V DC 2P conforming to IEC 60947-2; 36 kA Icu at 750 V DC 3P conforming to IEC 60947-2 |
| Breaking capacity code | F 36 kA 750 V DC |
| Control type | Toggle |
| Mounting mode | Fixed |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 14.000 cm |
| Package 1 Width | 11.300 cm |
| Package 1 Length | 19.400 cm |
| Package 1 Weight | 1.503 kg |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 7 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 10.924 kg |
This is a 3-pole basic switch for the ComPacT NSX 100F DC circuit breaker, designed to optimize space and breaking capacity. It is an optimal choice for applications using DC voltages. The breaking capacity (Icu) is 36 kA rms at 750 VDC. The rated current is 100 A and the operating voltage is 750 VDC. This basic switch is supplied without a trip unit (to be ordered separately) and can be equipped with a wide range of optional features and accessories. The dimensions are 161x105x86 mm (H x W x D). It is compliant with international standards (IEC 60947), CCC, EAC and marine specifications.