| Complementary |
| Long-time pick-up adjustment type Ir (thermal protection) | Adjustable 9 settings |
| [Ir] long-time protection pick-up adjustment range | 18...40 A |
| Long-time protection delay adjustment type tr | Adjustable |
| [tr] long-time protection delay adjustment range | 15…400 s at 1.5 x Ir; 0.35…11 s at 7.2 x Ir; 0.5…16 s at 6 x Ir |
| Neutral protection settings | 0.5 x Ir (3D + N/2); 1 x Ir (4D); 1.6 x Ir (3D + OSN); No protection (3D) |
| Thermal memory | 20 minutes before and after tripping |
| Short-time protection pick-up adjustment type Isd | Adjustable |
| [Isd] Short-time protection pick-up adjustment range | 1.5...10 x Ir |
| Short-time protection delay adjustment type tsd | Adjustable |
| [tsd] Short-time protection delay adjustment range | 0…0.4 s I²t=off; 0.1…0.4 s I²t=on |
| Instantaneous protection pick-up adjustment type Ii | Adjustable |
| [Ii] instantaneous protection pick-up adjustment range | 1.5...15 x In |
| Earth-leakage protection | Integrated |
| Earth-leakage protection class | Class A |
| Earth-leakage protection sensitity adjustment type IΔn | Adjustable |
| [IΔn] earth-leakage protection sensitivity adjustment range | 0.03 A; 0.1 A; 0.3 A; 0.5 A; 1 A; 3 A; 5 A |
| Earth-leakage protection specific mode | OFF using the IΔn rotary switch |
| Earth-leakage protection time delay adjustement type Δt | Adjustable |
| [Δt] Earth-leakage protection time delay adjustment range | 0 ms; 60 ms; 150 ms; 500 ms; 1 s |
| Zone selective interlocking ZSI | Without |
| Local signalling | Flashing LED (green) for ready to operate; LED 105 % Ir (red) for overload; LED 90 % Ir (orange) for overload |
| Display type | LCD display |
| Type of measurement | Energy meter |
| Communication of data | Maintenance indicators; Instantaneous and demand values; Time-stamped histories and event tables; Maximeters/minimeters; Earth leakage current; Demand current and power; Power quality; Test reports; Protection and alarm settings; Energy metering |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | EN/IEC 60947-2 |
| Electrical shock protection class | Class II |
| Pollution degree | 3 conforming to IEC 60947-1 |
| IP degree of protection | IP40 conforming to IEC 60529 |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -40…85 °C |
| Logistical informations |
| Country of origin | CN |
| Main |
| Range | ComPacT |
| Range of product | ComPacT NSX100...250 |
| Product or component type | Trip unit |
| Trip unit name | MicroLogic 7.2 E |
| Trip unit technology | Electronic |
| Range compatibility | ComPacT NSX160; ComPacT NSX100; ComPacT NSX250 |
| Device application | Distribution |
| Poles description | 4P |
| Protected poles description | 3D + N/2; 4D; 3D + OSN; 3D |
| Neutral position | Left |
| Trip unit protection functions | LSIR |
| Protection type | L : for overload protection (long time); S : for short time short-circuit protection; I : for instantaneous short-circuit protection; R : for earth-leakage protection |
| Trip unit rating | 40 A at 40 °C |
| [Ue] rated operational voltage | 440 V AC 50/60 Hz |
| Network type | AC |
| Network frequency | 50/60 Hz |
| Circuit breaker mounting mode | Fixed |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 10.0 cm |
| Package 1 Width | 11.0 cm |
| Package 1 Length | 15.0 cm |
| Package 1 Weight | 795.0 g |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 10 |
| Package 2 Height | 30 cm |
| Package 2 Width | 30 cm |
| Package 2 Length | 40 cm |
| Package 2 Weight | 8.324 kg |
This MicroLogic 7.2 E (Energy) 4-pole 4d electronic trip unit is an electronic trip unit used on ComPacT NSX 100/160/250 circuit breakers. This electronic trip unit with a rating of 40 A is an optimal choice for all standard and special applications. It has customizable long-term protection against overloads. It also offers customizable short-time delayed short-circuit protection and instantaneous short-circuit protection. The Vigi MicroLogic 7.2 E trip unit offers integrated, adjustable residual current protection. MicroLogic 7.2 E indicates overloads with alarm LEDs. The green Ready LED flashes when the circuit breaker is ready to trip. MicroLogic 7.2 E is equipped with a display module that provides energy measurements and allows fine adjustment. A residual current pre-alarm can be available remotely by installing the optional SDx module (LV429532). This product is part of our EcoStruxure Power architecture when combined with the PowerTag NSX and ComPacT NSX basic switch.