| Complementary |
| Long-time pick-up adjustment type Ir (thermal protection) | Adjustable |
| [Ir] long-time protection pick-up adjustment range | 0.7...1 x In |
| Long-time protection delay adjustment type tr | Fixed |
| Instantaneous protection pick-up adjustment type Ii | Fixed |
| [Ii] instantaneous protection pick-up adjustment range | 800 A |
| Earth-leakage protection | Without |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | EN/IEC 60947-2 |
| Electrical shock protection class | Class II |
| Pollution degree | 3 conforming to IEC 60947-1 |
| IP degree of protection | IP40 conforming to IEC 60529 |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -50…85 °C |
| Logistical informations |
| Country of origin | PL |
| Main |
| Range | ComPacT |
| Range of product | ComPacT NSX100...250 DC |
| Product or component type | Trip unit |
| Trip unit name | TM-D |
| Trip unit technology | Thermal-magnetic |
| Range compatibility | ComPacT NSX100 DC |
| Device application | Distribution |
| Poles description | 3P |
| Protected poles description | 3D |
| Trip unit protection functions | LI |
| Protection type | L : for overload protection (thermal); I : for short-circuit protection (magnetic) |
| Trip unit rating | 80 A at 40 °C |
| [Ue] rated operational voltage | 750 V DC |
| Network type | DC |
| Circuit breaker mounting mode | Fixed |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 7.000 cm |
| Package 1 Width | 10.000 cm |
| Package 1 Length | 11.500 cm |
| Package 1 Weight | 414.000 g |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 28 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 12.068 kg |
The TM80DC is a 3-pole thermal-magnetic trip unit used on ComPacT NSX 100DC circuit breakers. This 80A rated thermal-magnetic trip unit is an optimal choice for all distribution applications. It features adjustable thermal overload protection and fixed magnetic protection against short circuits. The rated current is 80A and the operating voltage is 750VDC. It complies with international standards (IEC 60947), CCC, EAC and marine specifications.