| Complementary |
| Motor tripping class | 10; 30; 5; 20 |
| Complementary motor protection | Protracted starting time; Stalled rotor; Current unbalance; Underload |
| Long-time pick-up adjustment type Ir (thermal protection) | Adjustable 9 settings |
| [Ir] long-time protection pick-up adjustment range | 35...80 A |
| Long-time protection delay adjustment type tr | Adjustable |
| [tr] long-time protection delay adjustment range | 120 s at 1.5 x Ir for trip class 5; 6.5 s at 6 x Ir for trip class 5; 5 s at 7.2 x Ir for trip class 5; 240 s at 1.5 x Ir for trip class 10; 13.5 s at 6 x Ir for trip class 10; 10 s at 7.2 x Ir for trip class 10; 480 s at 1.5 x Ir for trip class 20; 26 s at 6 x Ir for trip class 20; 20 s at 7.2 x Ir for trip class 20; 720 s at 1.5 x Ir for trip class 30 |
| Thermal memory | 20 minutes before and after tripping |
| Short-time protection pick-up adjustment type Isd | Adjustable 9 settings |
| [Isd] Short-time protection pick-up adjustment range | 5...13 x Ir |
| Short-time protection delay adjustment type tsd | Fixed |
| Instantaneous protection pick-up adjustment type Ii | Fixed |
| [Ii] instantaneous protection pick-up adjustment range | 1200 A |
| Ground-fault protection pick-up adjustment type Ig | Adjustable |
| [Ig] ground-fault protection pick-up adjustment range | 0.2...1 x In for In = 50 A; Ig enable on/off |
| Ground-fault protection time delay adjustment type tg | Adjustable |
| [tg] ground-fault protection time delay adjustment range | 0…0.4 s |
| Earth-leakage protection | Without |
| Zone selective interlocking ZSI | With |
| Local signalling | Flashing LED (green) for ready to operate; LED 95 % Ith (red) for temperature over set point |
| Display type | LCD display |
| Type of measurement | Energy meter |
| Communication of data | Energy metering; Protection and alarm settings; Time-stamped histories and event tables; Instantaneous and demand values; Maintenance indicators; Demand current and power; Power quality; Maximeters/minimeters |
| Electrical data recording | Maintenance indicators |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | EN/IEC 60947-2 |
| Electrical shock protection class | Class II |
| Pollution degree | 3 conforming to IEC 60947-1 |
| IP degree of protection | IP40 conforming to IEC 60529 |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -40…85 °C |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | ComPacT |
| Range of product | ComPacT NSX100...250 |
| Product or component type | Trip unit |
| Trip unit name | MicroLogic 6.2 E-M |
| Trip unit technology | Electronic |
| Range compatibility | ComPacT NSX100; ComPacT NSX160; ComPacT NSX250 |
| Device application | Motor |
| Poles description | 3P |
| Protected poles description | 3D |
| Trip unit protection functions | LSIG |
| Protection type | L : for overload protection (long time); S : for short time short-circuit protection with fixed delay; I : for instantaneous short-circuit protection; G : for ground fault protection |
| Trip unit rating | 80 A at 65 °C |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
| Network type | AC |
| Network frequency | 50/60 Hz |
| Circuit breaker mounting mode | Fixed |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 9.8 cm |
| Package 1 Width | 11.0 cm |
| Package 1 Length | 15.0 cm |
| Package 1 Weight | 540.0 g |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 11 |
| Package 2 Height | 30 cm |
| Package 2 Width | 30 cm |
| Package 2 Length | 40 cm |
| Package 2 Weight | 6.391 kg |
This MicroLogic 6.2 EM (Energy) 3-pole 3d electronic trip unit is an electronic trip unit used on ComPacT NSX 100/160/250 circuit breakers. This electronic trip unit with a rating of 80 A is an optimal choice for motor protection applications. It has customizable long-term protection against overloads. It also offers customizable short-term protection and fixed instantaneous short-circuit protection. It offers phase unbalance or phase loss protection and additional and customizable ground fault protection. MicroLogic 6.2 EM indicates overloads with alarm LEDs. The green Ready LED flashes when the circuit breaker is ready to trip. MicroLogic 6.2 EM is equipped with a display module that provides energy measurements and allows fine adjustment. This product is part of our EcoStruxure Power architecture when combined with the PowerTag NSX and ComPacT NSX basic switches.