| Additional features |
| [Ir] type of long-time pickup setting (thermal protection) | 9 adjustable settings |
| [Ir] Long-time protection pick-up adjustment range | 40 - 100 A |
| [tr] Type of long-time protection delay adjustment | Adjustable |
| [tr] adjustable long-time delay range | 15…400 s at 1.5 x Ir; 0.35…11 s at 7.2 x Ir; 0.5…16 s at 6 x Ir |
| Thermal storage | 20 minutes before and after tripping |
| [Isd] type of short-time protection setting | 9 adjustable settings |
| [Isd] Short-time protection adjustment range | 1,5 - 10 x Ir |
| [tsd] Type of short-time protection delay adjustment | Adjustable |
| [tsd] Short-time delay adjustment range | 0…0.4 s I²t=off; 0.1…0.4 s I²t=on |
| [Ii] type of instantaneous short-circuit protection setting | Adjustable |
| [Ii] setting range of instantaneous short-circuit protection | 1,5 - 12 x In |
| Earth fault protection | None |
| Zoneselective interlock ZSI | With |
| Local signalling | Blinking LED (green) for ready; LED 105 % Ir (red) for overload; LED 90 % Ir (orange) for overload |
| Display type | LCD display |
| Measured value type | Ammeter |
| Data transmission | Energy consumption measurement; protection and alarm settings; time-stamped trends and event logs; instantaneous and requested values; maintenance indicators; current and line query; power supply quality; maximeter/minimeter |
| Electrical data recording | Maintenance indicators |
| Contractual warranty |
| Warranty (in months) | 18 |
| Main features |
| Product series | ComPacT |
| Product or component type | Trip unit |
| Trigger name | MicroLogic 5.2 A-Z |
| Trigger technology | Electronic |
| Compatible product family | ComPacT NSX100; ComPacT NSX160; ComPacT NSX250 |
| Device application | 16 Hz 2/3 networks |
| Pole description | 3P |
| Description of protected poles | 3D |
| Tripping unit protection functions | LSI |
| Degree of protection | L : for overload protection (long-time); S : for short-time short-circuit protection; I : for instantaneous short-circuit protection |
| Rated value of tripping unit | 100 A at 40 °C |
| [Ue] Rated operational voltage | 250/500 V AC 16 Hz 2/3 |
| Mounting type of power switch | Fixed |
| Mounting |
| Standards | EN/IEC 60947-2 |
| Protection class for electric shocks | Class II |
| Pollution degree | 3 corresponds to IEC 60947-1 |
| Degree of protection (IP) | IP40 complies with IEC 60529 |
| Operating ambient temperature | -25…70 °C |
| Ambient temperature during storage | -40…85 °C |
| Packaging units |
| VPE 1 type | PCE |
| Number of devices per package | 1 |
| VPE 1 height | 9,000 cm |
| VPE 1 width | 11,000 cm |
| VPE 1 length | 15,000 cm |
| Packaging weight (Lbs) | 547,000 g |
| VPE 2 type | S03 |
| VPE 2 quantity | 11 |
| VPE 2 height | 30 cm |
| VPE 2 width | 30 cm |
| VPE 2 length | 40 cm |
| VPE 2 weight | 6,437 kg |
| VPE 3 type | P12 |
| VPE 3 quantity | 88 |
| VPE 3 height | 45,000 cm |
| VPE 3 width | 80,000 cm |
| VPE 3 length | 120,000 cm |
| VPE 3 weight | 63,496 kg |
This MicroLogic 5.2 AZ 3-pole 3d electronic trip unit is an electronic trip unit used with ComPacT NSX 100/160/250 circuit breakers. This electronic trip unit with a rating of 100 A is used in special 2/3 distribution systems at 16 Hz for railway applications. It has adjustable long-term protection against overload. It also offers adjustable short-time delayed short-circuit protection and instantaneous short-circuit protection. MicroLogic 5.2 AZ indicates overloads with alarm LEDs. The green Ready LED flashes when the circuit breaker is ready to trip. MicroLogic 5.2 AZ is equipped with a display module that provides current measurements and allows fine adjustments. This product is part of our EcoStruxure Power architecture when combined with the PowerTag NSX and ComPacT NSX basic switch.