| Additional features |
| Control channels | Programmable control loops |
| Motion control | Free axis CANopen |
| Capacity of communication module processor | 2 Ethernet communication module; 4 AS-Interface module |
| Integrated communication service | Network management (NMT) CANopen; Process Data Object (PDO) CANopen; Service Data Object (SDO) CANopen; Special functions (SYNC, EMCY, TIME) CANopen |
| Transmission speed | 1 Mbit/s 0…20 m 0…0.6 m; 125 Kbit/s 0…500 m 0…10 m; 20 Kbit/s 0…2500 m 0…300 m; 250 Kbit/s 0…250 m 0…10 m; 50 Kbit/s 0…1000 m 0…120 m; 500 Kbit/s 0…100 m 0…10 m; 800 Kbit/s 0…40 m 0…6 m |
| Bus type | CANopen M20 DS 301 V4.02 devices connected via Daisy-Chaining or branch connections CSMA/CA; CANopen M20 DS 303-2 devices connected via Daisy-Chaining or branch connections CSMA/CA; CANopen M20 DS 405 devices connected via Daisy-Chaining or branch connections CSMA/CA |
| Number of slaves | 63 CANopen |
| Number of devices per segment | 0…32 (character mode); 0…32 (Modbus); 0…16 for |
| Number of devices | 2 point-to-point character mode; 2 point-to-point Modbus |
| Bus length | 0…10 m serial line non-isolated character mode segment; 0…10 m serial line non-isolated Modbus segment; 0…1000 m serial line isolated character mode segment; 0…1000 m serial line isolated Modbus segment; 0…15 m character mode point-to-point; 0…15 m Modbus point-to-point |
| Number of addresses | 0…248 for character mode; 0…248 for Modbus |
| Requirements | 1 K data bytes per request character mode; 252 data bytes per RTU request Modbus; 504 data bytes per ASCII request Modbus |
| Control parameters | One CRC per frame (RTU) Modbus; One LRC per frame (ASCII) character mode; One LRC per frame (ASCII) Modbus |
| Memory description | Internal RAM 4096 kB; internal RAM 256 kB data; internal RAM 3584 kB program, constants and symbols |
| Maximum object surface size | 32634 %Mi localised internal bits; 32464 %MWi internal words; 32760 %KWi constant words |
| Standard object area size | 1024 %MWi internal words localized internal data; 256 %KWi constant words localized internal data; 512 %Mi localized internal bits |
| Application structure | 64 event tasks; no auxiliary task; 1 cyclic/periodic master task; 1 periodic fast task |
| Execution time per instruction | 0.12 µs Boolean; 0.17 µs words with double length; 0.25 µs words with single length; 1.16 µs floating point |
| Number of instructions per ms | 6.4 KInst/ms 65% boolean + 35% fixed-arithmetic; 8.1 KInst/ms 100% boolean |
| System overhead | 0.13 ms for Fast Task; 0.7 ms for Master Task |
| Electricity consumption | 90 mA at 24 V DC |
| Supply | Internal power supply via module carrier |
| Text | CE; UL; CSA; RCM; EAC; UKCA; China RoHS; WEEE; IEC |
| LED status indicator | 1 LED (green) integrated machine/bus installation ready (CAN RUN); 1 LED (green) processor in operation (RUN); 1 LED (red) I/O module error (I/O); 1 LED (red) error in integrated machine/bus installation (CAN ERR); 1 LED (red) memory card error (CARD ERR); 1 LED (red) processor or system error (ERR); 1 LED (yellow) Modbus activity (SER COM) |
| Product weight | 0,21 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Main features |
| Product series | Modicon M340 automation platform |
| Product or component type | Processor module |
| Operating conditions | Memory card required (not included) |
| Number of racks | 4 |
| Local I/O processor capacity (discrete) | 1.024 E/A |
| Analog I/O processor capacity | 256 E/A |
| Number of application-specific channels | 36 |
| Monitoring | Modbus diagnostic counter; Modbus event counter |
| Mounting |
| Operating ambient temperature | 0…60 °C |
| Relative humidity | 5…95 % condensation not permitted |
| Degree of protection (IP) | IP20 |
| Coating | TC |
| Policies | 2014/35/EU - Low Voltage Directive; 2014/30/EU - electromagnetic compatibility; 2012/19/EU - WEEE directive |
| Product certifications | CE; UL; CSA; RCM; EAC; UKCA; Commercial Marine; CCSAus HazLoc Class I Division 2 Group A; CCSAus HazLoc Class I Division 2 Group B; CCSAus HazLoc Class I Division 2 Group C; CCSAus HazLoc Class I Division 2 Group D |
| Standards | IEC 61131-2; IEC 61010-2-201; UL 61010-2-201; CSA C22.2 Nr. 61010-2-201; IACS E10; EN/IEC 61000-6-5, interface type 1 and type 2; EN/IEC 61850-3, location G |
| Packaging units |
| VPE 1 type | PCE |
| Number of devices per package | 1 |
| VPE 1 height | 5,5 cm |
| VPE 1 width | 11,0 cm |
| VPE 1 length | 12,0 cm |
| Packaging weight (Lbs) | 252,0 g |
| VPE 2 type | S02 |
| VPE 2 quantity | 15 |
| VPE 2 height | 15,0 cm |
| VPE 2 width | 30,0 cm |
| VPE 2 length | 40,0 cm |
| VPE 2 weight | 4,581 kg |
Processor modules Modicon M340 BMX P34. Memory card, max. 1024 digital. EAs 1024 digital I/O256 analog I/O36 int. channels, max. Network modules 2 networks Ethernet TCP/IP, memory 4096 KB integrated. Article number with H (Harsh) -25 to +70° C and protective coating.