| Complementary |
| Control channels | Programmable loops |
| Motion control | Independent axis CANopen |
| Communication module processor capacity | 2 Ethernet communication module; 4 AS-Interface module |
| embedded communication service | Network management (NMT) CANopen; Process Data Object (PDO) CANopen; Service Data Object (SDO) CANopen; Special functions (SYNC, EMCY, TIME) CANopen |
| Transmission rate | 1 Mbit/s 0…20 m 0…0.6 m; 125 kbit/s 0…500 m 0…10 m; 20 kbit/s 0…2500 m 0…300 m; 250 kbit/s 0…250 m 0…10 m; 50 kbit/s 0…1000 m 0…120 m; 500 kbit/s 0…100 m 0…10 m; 800 kbit/s 0…40 m 0…6 m |
| Bus type | CANopen M20 DS 301 V4.02 devices linked by daisy-chaining or tap junctions CSMA/CA; CANopen M20 DS 303-2 devices linked by daisy-chaining or tap junctions CSMA/CA; CANopen M20 DS 405 devices linked by daisy-chaining or tap junctions CSMA/CA |
| Number of server device(s) | 63 CANopen |
| Number of devices per segment | 0…32 (character mode); 0…32 (Modbus); 0…16 for |
| Number of devices | 2 point-to-point character mode; 2 point-to-point Modbus |
| Bus length | 0…10 m serial link non isolated character mode segment; 0…10 m serial link non isolated Modbus segment; 0…1000 m serial link isolated character mode segment; 0…1000 m serial link isolated Modbus segment; 0…15 m character mode point-to-point; 0…15 m Modbus point-to-point |
| Number of addresses | 0…248 for character mode; 0…248 for Modbus |
| Requests | 1 K data bytes per request character mode; 252 data bytes per RTU request Modbus; 504 data bytes per ASCII request Modbus |
| Control parameter | One CRC on each frame (RTU) Modbus; One LRC on each frame (ASCII) character mode; One LRC on each frame (ASCII) Modbus |
| Memory description | Supplied memory card (BMXRMS008MP) backup of programs, constants, symbols and data; Internal RAM 4096 kB; Internal RAM 256 kB data; Internal RAM 3584 kB program constants and symbols |
| Maximum size of object areas | 32634 %Mi located internal bits; 32464 %MWi internal words; 32760 %KWi constant words |
| Default size of object areas | 1024 %MWi internal words located internal data; 256 %KWi constant words located internal data; 512 %Mi located internal bits |
| Application structure | No auxiliary task; 1 cyclic/periodic master task; 1 periodic fast task; 64 event tasks |
| Execution time per instruction | 0.12 µs Boolean; 0.17 µs double-length words; 0.25 µs single-length words; 1.16 µs floating points |
| Number of instructions per ms | 6.4 Kinst/ms 65 % Boolean + 35 % fixed arithmetic; 8.1 Kinst/ms 100 % Boolean |
| System overhead | 0.13 ms for fast task; 0.7 ms for master task |
| Current consumption | 90 mA at 24 V DC |
| Supply | Internal power supply via rack |
| Marking | CE; UL; CSA; RCM; EAC; UKCA; China RoHS; WEEE; IEC |
| Status LED | 1 LED (green) integrated machine/installation bus operational (CAN RUN); 1 LED (green) processor running (RUN); 1 LED (red) I/O module fault (I/O); 1 LED (red) integrated machine/installation bus fault (CAN ERR); 1 LED (red) memory card fault (CARD ERR); 1 LED (red) processor or system fault (ERR); 1 LED (yellow) activity on Modbus (SER COM) |
| Net weight | 0.21 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Ambient air temperature for operation | 0…60 °C |
| Relative humidity | 5…95 % without condensation |
| IP degree of protection | IP20 |
| Protective treatment | TC |
| Directives | 2014/35/EU - low voltage directive; 2014/30/EU - electromagnetic compatibility; 2012/19/EU - WEEE directive |
| Product certifications | CE; UL; CSA; RCM; EAC; UKCA; Merchant Navy; CCSAus HazLoc Class I Division 2 Group A; CCSAus HazLoc Class I Division 2 Group B; CCSAus HazLoc Class I Division 2 Group C; CCSAus HazLoc Class I Division 2 Group D |
| Standards | IEC 61131-2; IEC 61010-2-201; UL 61010-2-201; CSA C22.2 No 61010-2-201; IACS E10; EN/IEC 61000-6-5, interface type 1 and type 2; EN/IEC 61850-3, location G |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range of product | Modicon M340 automation platform |
| Product or component type | Processor module |
| Concept | Modbus; CANopen |
| Number of racks | 4 |
| Local I/O processor capacity (discrete) | 1024 I/O |
| Analogue I/O processor capacity | 256 I/O |
| Number of application specific channel | 36 |
| Monitoring | Diagnostic counters Modbus; Event counters Modbus |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 5.400 cm |
| Package 1 Width | 11.500 cm |
| Package 1 Length | 12.400 cm |
| Package 1 Weight | 249.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 15 |
| Package 2 Height | 15 cm |
| Package 2 Width | 30 cm |
| Package 2 Length | 40 cm |
| Package 2 Weight | 4.058 kg |
This processor module is part of the Modicon M340 range, a range of programmable logic controllers (PLCs). It offers a maximum configuration of 4 module racks, 36 application-specific channels, 63 CANopen slaves and 11 slots. It is a processor module with a current consumption of 90mA at 24V DC, works with internal power supply. The interfaces of the communication processor module are 2 Ethernet modules and 4 AS-Interface modules. It is supplied with a memory card for backing up programs, constants, symbols and data. It is an IP20 protection product. The module has a discrete I/O processor capacity of 1024 multi-rack, 704 single-rack configurations and an analog I/O processor capacity of 256 multi-rack, 66 single-rack configurations. It supports transfer rate up to 800kbps 0m to 40m, 0m to 6m. It is suitable for applications in process industries, renewable energy, water, cement, manufacturing, infrastructure and machinery. This product is certified by CE. It complies with EN 61131-2, EN 61000-6-4, EN 61000-6-2 and EN 61010-2-201 standards. It comes with a memory card (BMXRMS008MP) to back up programs, constants, symbols and data, internal RAM 4096kB, internal RAM 256kB data, internal RAM 3584kB program constants and symbols. The compact Modicon M340 offers flexibility and integrated features in a small housing. At the core of the process, it offers you plug-and-work solutions with both Schneider Electric and third-party devices.