| Complementary |
| Primary voltage limit | 85...264 V |
| Network frequency | 50/60 Hz |
| Network frequency limits | 47…63 Hz |
| Apparent power | 0.13 kVA |
| Input current | 0.55 A 240 V; 1.01 A 115 V |
| Inrush current | 30 A 120 V; 60 A 240 V |
| I²t on activation | 1 A².s 120 V; 3 A².s 240 V |
| It on activation | 0.05 A.s 120 V; 0.07 A.s 240 V |
| MTBF reliability | 792000 H |
| Protection type | Internal fuse not accessible for primary circuit; Overload protection for secondary circuit; Overvoltage protection for secondary circuit; Short-circuit protection for secondary circuit |
| Current at secondary voltage | 5.5 A 3.3 V DC I/O module logic power supply; 1.67 A 24 V DC I/O module power supply and processor |
| Maximum power dissipation in W | 8.5 W |
| Status LED | 1 LED (green) presence of voltages (OK); 1 LED (green) redundancy OK; 1 LED (green) power supply status |
| Control type | RESET push-button cold restart |
| Electrical connection | 1 connector 2 pin(s)alarm relay; 1 connector 5 pin(s)line supply, protective earth |
| Insulation resistance | >= 100 MOhm primary/ground; >= 100 MOhm primary/secondary |
| Net weight | 0.51 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Immunity to microbreaks | 1 ms |
| Dielectric strength | 1500 V primary/secondary I/O module logic power supply; 1500 V primary/secondary I/O module power supply and processor; 2300 V primary/secondary sensor power supply; 1500 V primary/ground; 500 V 24 V sensor output/ground |
| Vibration resistance | 3 gn |
| Shock resistance | 30 gn |
| IP degree of protection | IP20 |
| Directives | 2014/35/EU - low voltage directive; 2014/30/EU - electromagnetic compatibility |
| Product certifications | CE; UL; CSA; RCM; EAC; Merchant Navy |
| Standards | IEC 61131-2; IEC 61010-2-201; UL 61010-2-201; CSA C22.2 No 61010-2-201; IACS E10; EN/IEC 61000-6-5, interface type 1 and type 2; EN/IEC 61850-3, location G |
| Environmental characteristic | Gas resistant class Gx conforming to ISA S71.04; Gas resistant class 3C4 conforming to IEC 60721-3-3; Dust resistant class 3S4 conforming to IEC 60721-3-3; Sand resistant class 3S4 conforming to IEC 60721-3-3; Salt resistant level 2 conforming to IEC 68252; Mold growth resistant class 3B2 conforming to IEC 60721-3-3; Fungal spore resistant class 3B2 conforming to IEC 60721-3-3; Hazardous location class I division 2 |
| Ambient air temperature for storage | -40…85 °C |
| Ambient air temperature for operation | -25…70 °C |
| Relative humidity | 5…95 % at 55 °C without condensation |
| Protective treatment | Conformal coating |
| Operating altitude | 0...2000 m; 2000...5000 m with derating factor |
| Logistical informations |
| Country of origin | ID |
| Main |
| Range of product | Modicon X80 |
| Product or component type | Power supply module |
| backplane compatibility | All backplane |
| Product specific application | For severe environments |
| advanced diagnostics available via network | Remaining lifetime; Temperature sensing; Redundancy test; Redundancy information; Uptime duration |
| Primary voltage | 100...240 V |
| Supply circuit type | AC |
| Secondary power | 18 W 3.3 V DC at -25…70 °C I/O module logic power supply; 40 W 24 V DC at -25…70 °C I/O module power supply and processor if 3.3 V not loaded |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 9.000 cm |
| Package 1 Width | 18.000 cm |
| Package 1 Length | 25.000 cm |
| Package 1 Weight | 615.000 g |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 6 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 4.480 kg |
This harsh environment power supply is part of the Modicon X80 range, a range of common inputs and outputs for Modicon M340 and Modicon M580. This power supply module has a primary voltage of 100V to 240V AC for harsh environments to build redundant architectures. This robust product can be used in harsher environments and operate in an extended temperature range of -25°C to +70°C. It is equipped with a 2-pin connector for the alarm relay, a 5-pin connector for the mains supply and a protective conductor for the electrical connection. It is an IP20 certified product. This product is certified by ATEX, IEC-Ex, CE, RCM, Merchant Navy, CSA, EAC and UL. It complies with EN 61131-2, EN 61000-6-4, EN 61000-6-2 and EN 61010-2-201. A set of two removable cage terminal blocks (5-way and 2-way) is included with the power supply. The product must be installed in an X80 module carrier and secured with 2 screws.