| Complementary |
| Primary voltage limit | 100...150 V |
| Input current | 600 mA 125 V |
| Inrush current | 60 A 125 V |
| I²t on activation | 2.5 A².s 125 V |
| It on activation | 0.09 A.s 125 V |
| MTBF reliability | 830000 H |
| Protection type | Internal fuse not accessible for primary circuit; Overload protection for secondary circuit; Overvoltage protection for secondary circuit; Short-circuit protection for secondary circuit |
| Current at secondary voltage | 1.67 A 24 V DC I/O module power supply and processor; 5 A 3.3 V DC I/O module logic power supply |
| Maximum power dissipation in W | 8.5 W |
| Status LED | 1 LED (green) presence of voltages (OK); 1 LED (green) redundancy OK; 1 LED (green) power supply status |
| Control type | RESET push-button cold restart |
| Electrical connection | 1 connector 2 pin(s)alarm relay; 1 connector 5 pin(s)line supply, protective earth |
| Insulation resistance | >= 100 MOhm primary/ground; >= 100 MOhm primary/secondary |
| Net weight | 0.61 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Immunity to microbreaks | 1 ms |
| Dielectric strength | 1500 V primary/secondary I/O module logic power supply; 1500 V primary/secondary I/O module power supply and processor; 2300 V primary/secondary sensor power supply; 1500 V primary/ground |
| IP degree of protection | IP20 |
| Directives | 2014/35/EU - low voltage directive; 2014/30/EU - electromagnetic compatibility |
| Product certifications | CE; UL; CSA; RCM; EAC; Merchant Navy |
| Standards | IEC 61131-2; IEC 61010-2-201; UL 61010-2-201; CSA C22.2 No 61010-2-201; IACS E10; EN/IEC 61000-6-5, interface type 1 and type 2; EN/IEC 61850-3, location G |
| Environmental characteristic | Gas resistant class Gx conforming to ISA S71.04; Gas resistant class 3C4 conforming to IEC 60721-3-3; Dust resistant class 3S4 conforming to IEC 60721-3-3; Sand resistant class 3S4 conforming to IEC 60721-3-3; Salt resistant level 2 conforming to IEC 68252; Mold growth resistant class 3B2 conforming to IEC 60721-3-3; Fungal spore resistant class 3B2 conforming to IEC 60721-3-3; Hazardous location class I division 2 |
| Ambient air temperature for storage | -40…85 °C |
| Ambient air temperature for operation | -25…70 °C |
| Relative humidity | 10…95 % without condensation |
| Protective treatment | Conformal coating |
| Main |
| Range of product | Modicon X80 |
| Product or component type | Power supply module |
| backplane compatibility | All backplane |
| Product specific application | For severe environments |
| advanced diagnostics available via network | Temperature sensing; Redundancy information; Redundancy test; Uptime duration; Remaining lifetime |
| Primary voltage | 125 V |
| Supply circuit type | DC |
| Secondary power | 18 W 3.3 V DC at -25…70 °C I/O module logic power supply; 40 W 24 V DC at -25…70 °C I/O module power supply and processor if 3.3 V not loaded |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 9.000 cm |
| Package 1 Width | 18.000 cm |
| Package 1 Length | 25.000 cm |
| Package 1 Weight | 621.000 g |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 6 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 4.509 kg |