| Complementary |
| Primary voltage limit | 85...264 V |
| Network frequency | 50/60 Hz |
| Network frequency limits | 47…63 Hz |
| Apparent power | 0.07 kVA |
| Input current | 0.31 A 240 V; 0.61 A 115 V |
| Inrush current | 30 A 120 V; 60 A 240 V |
| I²t on activation | 12 A².s 240 V |
| It on activation | 0.06 A.s 240 V; 0.03 A.s 120 V |
| MTBF reliability | 4638000 H |
| Protection type | Internal fuse not accessible for primary circuit; Overload protection for secondary circuit; Overvoltage protection for secondary circuit; Short-circuit protection for secondary circuit |
| Current at secondary voltage | 0.45 A 24 V DC sensor power supply; 0.7 A 24 V DC I/O module power supply and processor; 2.5 A 3.3 V DC I/O module logic power supply |
| Maximum power dissipation in W | 8.5 W |
| Status LED | 1 LED (green) rack voltage OK; 1 LED (green) sensor voltage |
| Control type | RESET push-button cold restart |
| Electrical connection | 1 connector 2 pin(s)alarm relay; 1 connector 5 pin(s)line supply, protective earth, 24 V DC input sensor |
| Insulation resistance | >= 100 MOhm primary/ground; >= 100 MOhm primary/secondary |
| Net weight | 0.3 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Immunity to microbreaks | 1 ms |
| Dielectric strength | 1500 V primary/secondary I/O module logic power supply; 1500 V primary/secondary I/O module power supply and processor; 2300 V primary/secondary sensor power supply; 1500 V primary/ground; 500 V 24 V sensor output/ground |
| Vibration resistance | 3 gn |
| Shock resistance | 30 gn |
| IP degree of protection | IP20 |
| Directives | 2014/35/EU - low voltage directive; 2014/30/EU - electromagnetic compatibility |
| Ambient air temperature for storage | -40…85 °C |
| Ambient air temperature for operation | 0…60 °C |
| Relative humidity | 5…95 % at 55 °C without condensation |
| Protective treatment | TC |
| Operating altitude | 0...2000 m; 2000...5000 m with derating factor |
| Logistical informations |
| Country of origin | ID |
| Main |
| Range of product | Modicon X80 |
| Product or component type | Power supply module |
| backplane compatibility | Not compatible with BMEXBP..02 |
| Primary voltage | 100...240 V |
| Supply circuit type | AC |
| Secondary power | 10.8 W 24 V DC sensor power supply; 16.8 W 24 V DC I/O module power supply and processor; 8.3 W 3.3 V DC I/O module logic power supply |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 13.500 cm |
| Package 1 Width | 15.400 cm |
| Package 1 Length | 16.400 cm |
| Package 1 Weight | 481.000 g |
| Unit Type of Package 2 | S04 |
| Number of Units in Package 2 | 12 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 40.000 cm |
| Package 2 Length | 60.000 cm |
| Package 2 Weight | 6.438 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 48 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 60.000 cm |
| Package 3 Length | 80.000 cm |
| Package 3 Weight | 35.804 kg |
The
power supply module BMXCPS2000 from
Schneider Electric belongs to the
Modicon X80 product series and serves as central power supply for small PLC systems, particularly for Modicon M340 and M580 platforms. It is designed to supply E/A modules, processors, and sensors within an automation architecture with stable voltages. The module is intended for use in industrial control systems, where reliable and efficient power supply is critical for the entire control unit's functionality.
Applications
The module is suitable for use in industrial automation systems, where it is integrated as part of a modular system into X80 module carriers. It is compatible with all X80 module carriers and enables a uniform environment for E/A modules, simplifying maintenance, training, and spare parts management. Its use in decentralized control systems, as commonly found in Modicon M580 systems, is also intended. The X80 series allows standardized integration, regardless of whether the system is centralized or decentralized.
Functions and Features in Detail
The module provides multiple voltage levels: 24 V DC for sensor power supply (10.8 W), 24 V DC for E/A modules and processor (16.8 W), and 3.3 V DC for logic supply of E/A modules (8.3 W). The total power output is thus 20 W. Power input is supplied via a primary voltage of 100 to 240 V AC, with voltage limits ranging from 85 to 264 V. The network frequency is 50/60 Hz, with an allowable range of 47 to 63 Hz. Input currents are 0.31 A at 240 V and 0.61 A at 115 V. Maximum power dissipation is 8.5 W.
For monitoring operational status, two
LED status indicators are integrated: one green LED indicates that the chassis voltage is normal, and the second green LED signals that the sensor voltage is correctly supplied. A RESET button allows for a cold start of the module. Electrical connections are made via a 2-pole connector for the alarm relay and a 5-pole connector for the power supply line, protective earth connection, and 24 V DC input for the sensor.
Technology Explained Simply
The module features an internal protection mechanism that safeguards the primary circuit against access. For the secondary circuit, overload protection, overvoltage protection, and short-circuit protection are integrated to protect connected components. Insulation resistance is at least 100 MΩ between primary circuit and earth, as well as between primary and secondary circuits. Dielectric strength is 1500 V between primary and secondary circuits (for E/A module logic and power supply), 2300 V for sensor power supply, 1500 V between primary circuit and earth, and 500 V between 24 V sensor output and ground. The MTBF (mean time between failures) is 4,638,000 hours, indicating high reliability.
Compatibility and Accessories
The module is compatible with all X80 module carriers, but not with the rear panel BMEXBP..02. It is part of a modular system that can be combined with various processor modules, such as BMXP341000, BMXP342020, BMEP581020, or BMEP584040. These modules are designed for different application scenarios in automation technology, with the power supply module providing the necessary energy for their operation.
Mounting and Installation
The module is installed into the module carrier and secured with two screws. Installation takes place in a closed housing with protection rating
IP20. This means the device is protected against contact with fingers and against solid foreign objects, but not against water or dust. Operating temperature ranges from 0 to 60 °C, and storage temperature ranges from -40 to 85 °C. Relative humidity may reach 95 %, with no condensation allowed at 55 °C. The operating altitude is up to 2,000 m; beyond that, power derating is required.
Operational Advantages
The modular design enables flexible expansion and maintenance of the control system. Uniform power supply for various components reduces complexity and the number of required parts. Integrated protection functions increase system safety and lifespan. Certifications according to CE, RCM, Merchant Navy, CSA, EAC, and UL, along with compliance with standards EN 61131-2, EN 61000-6-4, EN 61000-6-2, and EN 61010-2-201, ensure conformity with international standards. Vibration resistance (3 Gn) and shock resistance (30 gn) make the module suitable for industrial environments. Operational reliability is supported by immunity to interruptions of 1 ms duration.