| Complementary |
| Analog/digital conversion | Sigma delta 16 bits |
| Analogue input resolution | 15 bits + sign |
| Permitted overload on inputs | +/- 7.5 V +/- 1.28 V; +/- 7.5 V +/- 160 mV; +/- 7.5 V +/- 320 mV; +/- 7.5 V +/- 40 mV; +/- 7.5 V +/- 640 mV; +/- 7.5 V +/- 80 mV |
| Common mode rejection | 120 dB 50/60 Hz |
| Differential mode rejection | 60 dB 50/60 Hz |
| Cold junction compensation | External by Pt100 probe |
| Type of filter | First order digital filtering |
| Nominal read cycle time | 400 ms with temperature probe; 200 ms with thermocouple |
| Recalibration | Internal |
| Detection type | Open circuit Cu 10; Open circuit Ni 100; Open circuit Ni 1000; Open circuit Pt 100; Open circuit Pt 1000; Open circuit thermocouple B; Open circuit thermocouple E; Open circuit thermocouple J; Open circuit thermocouple K; Open circuit thermocouple L; Open circuit thermocouple N; Open circuit thermocouple R; Open circuit thermocouple S; Open circuit thermocouple T; Open circuit thermocouple U |
| Maximum wiring resistance | 20 Ohm 2 wires Cu 10; 20 Ohm 2 wires Ni 100; 20 Ohm 2 wires Pt 100; 20 Ohm 3 wires Cu 10; 20 Ohm 3 wires Ni 100; 20 Ohm 3 wires Pt 100; 200 Ohm 2 wires Ni 1000; 200 Ohm 2 wires Pt 1000; 200 Ohm 3 wires Ni 1000; 200 Ohm 3 wires Pt 1000; 50 Ohm 4 wires Cu 10; 50 Ohm 4 wires Ni 100; 50 Ohm 4 wires Pt 100; 500 Ohm 4 wires Ni 1000; 500 Ohm 4 wires Pt 1000 |
| Measurement resolution | 0.1 °C Cu 10; 0.1 °C Ni 100; 0.1 °C Ni 1000; 0.1 °C Pt 100; 0.1 °C Pt 1000; 0.1 °C thermocouple B; 0.1 °C thermocouple E; 0.1 °C thermocouple J; 0.1 °C thermocouple K; 0.1 °C thermocouple L; 0.1 °C thermocouple N; 0.1 °C thermocouple R; 0.1 °C thermocouple S; 0.1 °C thermocouple T; 0.1 °C thermocouple U; 1280/2exp14 mV +/- 1.28 V; 160/2exp14 mV +/- 160 mV; 320/2exp14 mV +/- 320 mV; 40/2exp14 mV +/- 40 mV; 12.5 mOhm 400 Ohm; 125 mOhm 4000 Ohm; 640/2exp14 mV +/- 640 mV; 80/2exp14 mV +/- 80 mV |
| Maximum conversion value | +/- 100 % 400 Ohm; +/- 100 % 4000 Ohm; +/- 102.5 % +/- 1.28 V; +/- 102.5 % +/- 160 mV; +/- 102.5 % +/- 320 mV; +/- 102.5 % +/- 40 mV; +/- 102.5 % +/- 640 mV; +/- 102.5 % +/- 80 mV |
| MTBF reliability | 900000 H |
| Operating altitude | 0...2000 m; 2000...5000 m with derating factor |
| Status LED | 1 LED (green) RUN; 1 LED per channel (green) channel diagnostic; 1 LED (red) ERR; 1 LED (red) I/O |
| Net weight | 0.165 kg |
| Current consumption | 150 mA at 3.3 V DC; 50 mA at 24 V DC |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Vibration resistance | 3 gn |
| Shock resistance | 30 gn |
| Ambient air temperature for storage | -40…85 °C |
| Ambient air temperature for operation | 0…60 °C |
| Relative humidity | 5…95 % at 55 °C without condensation |
| IP degree of protection | IP20 |
| Directives | 2014/35/EU - low voltage directive; 2014/30/EU - electromagnetic compatibility |
| Product certifications | CE; EAC; UL; CSA; Merchant Navy; RCM |
| Standards | IEC 61131-2; IEC 61000-6-4; IEC 61000-6-2; EN 61010-2-201 |
| Environmental characteristic | 3C3 conforming to IEC 60721-3-3; 3C4 conforming to IEC 60721-3-3 |
| Protective treatment | Standard version |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range of product | Modicon X80 |
| Product or component type | Analog input module |
| Electrical connection | 40 ways 2 connectors |
| Isolation between channels | Isolated |
| Input level | Low level |
| Analogue input number | 8 |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 5.600 cm |
| Package 1 Width | 11.300 cm |
| Package 1 Length | 12.000 cm |
| Package 1 Weight | 209.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 15 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 3.449 kg |
This analog isolated input module is part of the Modicon X80 range, a range of common input/output and communication modules, power supplies and module carriers for Modicon M340 and Modicon M580. This product consists of 8 input channels. This product meets the TC treatment requirements (treatment for all climates) and can operate in a temperature range of 0°C to +60°C/32°F to 140°F. Modicon X80 modules provide a unified environment for the use of I/O modules in automation architectures by reducing spare parts inventory, maintenance and training costs. It is equipped with a 40-pin connector for electrical connection. This product has an IP20 protection rating and offers an MTBF of 904,111 hours. This product is certified by CE, UL, CSA, RCM, EAC, UKCA and Merchant Navy and complies with EN 61000-6-5 and EN 61850-3. This module is compatible with Modicon M340, M580 (Local or Remote I/O) PLCs with a 40-pin connector. The product must be installed in the module carrier and secured with 2 screws.