| Complementary |
| Discrete input number | 8 |
| Discrete input type | DI7, DI8 programmable as pulse input: 0…30 kHz, 24 V DC ( |
| Discrete input logic | 16 preset speeds |
| Discrete output number | 0 |
| Discrete output type | Relay outputs R1A, R1B, R1C 250 V AC 3000 mA; Relay outputs R1A, R1B, R1C 30 V DC 3000 mA; Relay outputs R2A, R2C 250 V AC 5000 mA; Relay outputs R2A, R2C 30 V DC 5000 mA; Relay outputs R3A, R3C 250 V AC 5000 mA; Relay outputs R3A, R3C 30 V DC 5000 mA |
| Analogue input number | 3 |
| Analogue input type | AI1, AI2, AI3 software-configurable voltage: 0...10 V DC, impedance: 31.5 kOhm, resolution 12 bits; AI1, AI2, AI3 software-configurable current: 0...20 mA, impedance: 250 Ohm, resolution 12 bits; AI2 voltage analog input: - 10...10 V DC, impedance: 31.5 kOhm, resolution 12 bits |
| Analogue output number | 2 |
| Analogue output type | Software-configurable voltage AQ1, AQ2: 0...10 V DC impedance 470 Ohm, resolution 10 bits; Software-configurable current AQ1, AQ2: 0...20 mA, resolution 10 bits; Software-configurable current DQ-, DQ+: 30 V DC; Software-configurable current DQ-, DQ+: 100 mA |
| Relay output number | 3 |
| Relay output type | Configurable relay logic R1: fault relay NO/NC electrical durability 100000 cycles; Configurable relay logic R2: sequence relay NO electrical durability 100000 cycles; Configurable relay logic R3: sequence relay NO electrical durability 100000 cycles |
| Maximum switching current | Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 250 V AC; Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 30 V DC; Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC; Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC |
| Minimum switching current | Relay output R1, R2, R3: 5 mA at 24 V DC |
| Network number of phases | 3 phases |
| Physical interface | Ethernet; 2-wire RS 485 |
| Method of access | Slave Modbus TCP |
| Transmission rate | 10, 100 Mbits; 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps |
| Transmission frame | RTU |
| Permissible temporary current boost | 1.1 x In during 60 s (normal duty); 1.5 x In during 60 s (heavy duty) |
| Data format | 8 bits, configurable odd, even or no parity |
| Type of polarization | No impedance |
| Frequency resolution | Display unit: 0.1 Hz; Analog input: 0.012/50 Hz |
| Electrical connection | Control: removable screw terminals 0.5...1.5 mm²/20 AWG...16 AWG; Line side: screw terminal 10...16 mm²/8 AWG...6 AWG; Motor: screw terminal 10...16 mm²/8 AWG...6 AWG |
| Connector type | RJ45 (on the remote graphic terminal) for Ethernet/Modbus TCP; RJ45 (on the remote graphic terminal) for Modbus serial |
| Exchange mode | Half duplex, full duplex, autonegotiation Ethernet/Modbus TCP |
| Number of addresses | 1…247 for Modbus serial |
| Supply | External supply for digital inputs: 24 V DC (19…30 V) |
| Local signalling | 3 LEDs for local diagnostic; 3 LEDs (dual colour) for embedded communication status; 4 LEDs (dual colour) for communication module status; 1 LED (red) for presence of voltage |
| Input compatibility | DI1...DI6: discrete input level 1 PLC conforming to IEC 61131-2; DI5, DI6: discrete input level 1 PLC conforming to IEC 65A-68; STOA, STOB: discrete input level 1 PLC conforming to IEC 61131-2 |
| Sampling duration | 2 ms +/- 0.5 ms (DI1...DI4) - discrete input; 5 ms +/- 1 ms (DI5, DI6) - discrete input; 5 ms +/- 0.1 ms (AI1, AI2, AI3) - analog input; 10 ms +/- 1 ms (AO1) - analog output |
| Accuracy | +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input; +/- 1 % AO1, AO2 for a temperature variation 60 °C analog output |
| Linearity error | AI1, AI2, AI3: +/- 0.15 % of maximum value for analog input; AO1, AO2: +/- 0.2 % for analog output |
| Refresh time | Relay output (R1, R2, R3): 5 ms (+/- 0.5 ms) |
| Isolation | Between power and control terminals |
| Power range | 15…25 kW at 380…440 V 3 phases; 15…25 kW at 480…500 V 3 phases |
| Enclosure mounting | With heat sink |
| 4 quadrant operation possible | False |
| Asynchronous motor control profile | Constant torque standard; Optimized torque mode; Variable torque standard |
| Synchronous motor control profile | Permanent magnet motor; Synchronous reluctance motor |
| Maximum output frequency | 500 kHz |
| Acceleration and deceleration ramps | Linear adjustable separately from 0.01...9999 s |
| Motor slip compensation | Adjustable; Can be suppressed; Not available in permanent magnet motor law; Automatic whatever the load |
| Switching frequency | 2...12 kHz adjustable; 4...12 kHz with derating factor |
| Nominal switching frequency | 4 kHz |
| Braking to standstill | By DC injection |
| Brake chopper integrated | False |
| Maximum input current | 33.4 A |
| Maximum output voltage | 480.0 V |
| Apparent power | 24 kVA at 480 V (normal duty); 20.3 kVA at 480 V (heavy duty) |
| Maximum transient current | 43.1 A during 60 s (normal duty); 47.6 A during 60 s (heavy duty) |
| Network frequency | 50...60 Hz |
| Prospective line Isc | 50 kA |
| Base load current at high overload | 31.7 A |
| Base load current at low overload | 39.2 A |
| Power dissipation in W | Natural convection: 67 W at 380 V, switching frequency 4 kHz; Forced convection: 460 W at 380 V, switching frequency 4 kHz |
| With safety function Safely Limited Speed (SLS) | False |
| With safety function Safe brake management (SBC/SBT) | False |
| With safety function Safe Operating Stop (SOS) | False |
| With safety function Safe Position (SP) | False |
| With safety function Safe programmable logic | False |
| With safety function Safe Speed Monitor (SSM) | False |
| With safety function Safe Stop 1 (SS1) | False |
| With sft fct Safe Stop 2 (SS2) | False |
| With safety function Safe torque off (STO) | True |
| With safety function Safely Limited Position (SLP) | False |
| With safety function Safe Direction (SDI) | False |
| Protection type | Thermal protection: motor; Safe torque off: motor; Motor phase break: motor; Thermal protection: drive; Safe torque off: drive; Overheating: drive; Overcurrent between output phases and earth: drive; Overload of output voltage: drive; Short-circuit protection: drive; Motor phase break: drive; Overvoltages on the DC bus: drive; Line supply overvoltage: drive; Line supply undervoltage: drive; Line supply phase loss: drive; Overspeed: drive; Break on the control circuit: drive |
| Quantity per set | 1 |
| Width | 195 mm |
| Height | 480 mm |
| Depth | 225.5 mm |
| Net weight | 13.6 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Insulation resistance | > 1 MOhm 500 V DC for 1 minute to earth |
| Noise level | 59.5 dB conforming to 86/188/EEC |
| Pollution degree | 2 conforming to IEC 61800-5-1 |
| Vibration resistance | 1.5 mm peak to peak (f= 2…13 Hz) conforming to IEC 60068-2-6; 1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6 |
| Shock resistance | 15 gn for 11 ms conforming to IEC 60068-2-27 |
| Relative humidity | 5…95 % without condensation conforming to IEC 60068-2-3 |
| Ambient air temperature for operation | -15…50 °C (without derating); 50…60 °C (with derating factor) |
| Operating position | Vertical +/- 10 degree |
| Product certifications | CSA; ATEX zone 2/22; ATEX INERIS; DNV-GL; UL; TÜV |
| Marking | CE |
| Standards | UL 508C; IEC 61800-3; IEC 61800-3 environment 1 category C2; EN/IEC 61800-3 environment 2 category C3; IEC 61800-5-1; IEC 61000-3-12; IEC 60721-3; IEC 61508; IEC 13849-1 |
| Assembly style | With heat sink |
| Electromagnetic compatibility | Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2; Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3; Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4; 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5; Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 |
| Environmental class (during operation) | Class 3C3 according to IEC 60721-3-3; Class 3S3 according to IEC 60721-3-3 |
| Maximum acceleration under shock impact (during operation) | 150 m/s² at 11 ms |
| Maximum acceleration under vibrational stress (during operation) | 10 m/s² at 13...200 Hz |
| Maximum deflection under vibratory load (during operation) | 1.5 mm at 2...13 Hz |
| Permitted relative humidity (during operation) | Class 3K5 according to EN 60721-3 |
| Volume of cooling air | 215 m3/h |
| Overvoltage category | III |
| Regulation loop | Adjustable PID regulator |
| Ambient air transport temperature | -40…70 °C |
| Ambient air temperature for storage | -40…70 °C |
| Logistical informations |
| Country of origin | CN |
| Main |
| Range of product | Altivar Process ATV600 |
| Product specific application | Process and utilities |
| Product or component type | Variable speed drive |
| Variant | Standard version |
| Device short name | ATV630 |
| Mounting mode | Cabinet mount |
| Communication port protocol | Modbus TCP; Modbus serial; Ethernet |
| [Us] rated supply voltage | 380...480 V - 15...10 % |
| Relative symmetric mains voltage tolerance | 10 % |
| Relative symmetric network frequency tolerance | 5 % |
| nominal output current | 39.2 A |
| IP degree of protection | IP21 |
| Product destination | Asynchronous motors; Synchronous motors |
| EMC filter | Integrated with 10 m conforming to IEC 61800-3 category C2; Integrated with 50 m conforming to IEC 61800-3 category C3; With EMC plate option |
| Type of cooling | Forced convection |
| Supply frequency | 50...60 Hz - 5...5 % |
| Motor power kW | 18.5 kW (normal duty); 15 kW (heavy duty) |
| Motor power hp | 25 hp normal duty; 20 hp heavy duty |
| Line current | 33.4 A at 380 V (normal duty); 28.9 A at 480 V (normal duty); 27.7 A at 380 V (heavy duty); 24.4 A at 480 V (heavy duty) |
| Continuous output current | 39.2 A at 4 kHz for normal duty; 31.7 A at 4 kHz for heavy duty |
| Speed drive output frequency | 0.1…500 Hz |
| Safety function | STO (safe torque off) SIL 3 |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 29.000 cm |
| Package 1 Width | 22.500 cm |
| Package 1 Length | 65.000 cm |
| Package 1 Weight | 15.282 kg |
| Unit Type of Package 2 | S06 |
| Number of Units in Package 2 | 2 |
| Package 2 Height | 75.000 cm |
| Package 2 Width | 60.000 cm |
| Package 2 Length | 80.000 cm |
| Package 2 Weight | 40.564 kg |
Altivar ATV630 frequency converter. 3 analog inputs, 2 analog outputs. 16 preset speeds, acceleration/deceleration linearly adjustable separately from 0.01-9999 s, motor power 18.5 kW, 380-480 V, nominal output current I2N- 39.2 A. Dimensions (WxH)- 195x480 mm, weight- 13.6 kg. Braking to standstill- through DC power supply, communication protocols- Modbus TCP, Modbus, serial, Ethernet. Frequency converter with integrated services such as current measurement and energy dashboard, process monitoring and control. Suitable for synchronous, asynchronous and special motors. Certifications- CSA, REACH, ATEX zone 2/22, ATEX INERIS, DNV-GL, UL, TÜV. Marking- CE, protection class- IP21.