| Complementary |
| Discrete input number | 8 |
| Discrete input type | DI7, DI8 programmable as pulse input: 0…30 kHz, 24 V DC ( |
| Discrete input logic | 16 preset speeds |
| Discrete output number | 0 |
| Discrete output type | Relay outputs R1A, R1B, R1C 250 V AC 3000 mA; Relay outputs R1A, R1B, R1C 30 V DC 3000 mA; Relay outputs R2A, R2C 250 V AC 5000 mA; Relay outputs R2A, R2C 30 V DC 5000 mA; Relay outputs R3A, R3C 250 V AC 5000 mA; Relay outputs R3A, R3C 30 V DC 5000 mA |
| Analogue input number | 3 |
| Analogue input type | AI1, AI2, AI3 software-configurable voltage: 0...10 V DC, impedance: 31.5 kOhm, resolution 12 bits; AI1, AI2, AI3 software-configurable current: 0...20 mA, impedance: 250 Ohm, resolution 12 bits; AI2 voltage analog input: - 10...10 V DC, impedance: 31.5 kOhm, resolution 12 bits |
| Analogue output number | 2 |
| Analogue output type | Software-configurable voltage AQ1, AQ2: 0...10 V DC impedance 470 Ohm, resolution 10 bits; Software-configurable current AQ1, AQ2: 0...20 mA, resolution 10 bits; Software-configurable current DQ-, DQ+: 30 V DC; Software-configurable current DQ-, DQ+: 100 mA |
| Relay output number | 3 |
| Relay output type | Configurable relay logic R1: fault relay NO/NC electrical durability 100000 cycles; Configurable relay logic R2: sequence relay NO electrical durability 100000 cycles; Configurable relay logic R3: sequence relay NO electrical durability 100000 cycles |
| Maximum switching current | Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 250 V AC; Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 30 V DC; Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC; Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC |
| Minimum switching current | Relay output R1, R2, R3: 5 mA at 24 V DC |
| Network number of phases | 3 phases |
| Physical interface | Ethernet; 2-wire RS 485 |
| Method of access | Slave Modbus TCP |
| Transmission rate | 10, 100 Mbits; 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps |
| Transmission frame | RTU |
| Permissible temporary current boost | 1.1 x In during 60 s (normal duty); 1.5 x In during 60 s (heavy duty) |
| Data format | 8 bits, configurable odd, even or no parity |
| Type of polarization | No impedance |
| Frequency resolution | Display unit: 0.1 Hz; Analog input: 0.012/50 Hz |
| Electrical connection | Control: removable screw terminals 0.5...1.5 mm²/20 AWG...16 AWG; Line side: screw terminal 2 x 95...3 x 120 mm²/2 x 3/0 AWG...2 x 300 kcmil; Motor: screw terminal 2 x 95...3 x 120 mm²/2 x 3/0 AWG...2 x 300 kcmil |
| Connector type | RJ45 (on the remote graphic terminal) for Ethernet/Modbus TCP; RJ45 (on the remote graphic terminal) for Modbus serial |
| Exchange mode | Half duplex, full duplex, autonegotiation Ethernet/Modbus TCP |
| Number of addresses | 1…247 for Modbus serial |
| Supply | External supply for digital inputs: 24 V DC (19…30 V) |
| Local signalling | 3 LEDs for local diagnostic; 3 LEDs (dual colour) for embedded communication status; 4 LEDs (dual colour) for communication module status; 1 LED (red) for presence of voltage |
| Input compatibility | DI1...DI6: discrete input level 1 PLC conforming to IEC 61131-2; DI5, DI6: discrete input level 1 PLC conforming to IEC 65A-68; STOA, STOB: discrete input level 1 PLC conforming to IEC 61131-2 |
| Sampling duration | 2 ms +/- 0.5 ms (DI1...DI4) - discrete input; 5 ms +/- 1 ms (DI5, DI6) - discrete input; 5 ms +/- 0.1 ms (AI1, AI2, AI3) - analog input; 10 ms +/- 1 ms (AO1) - analog output |
| Accuracy | +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input; +/- 1 % AO1, AO2 for a temperature variation 60 °C analog output |
| Linearity error | AI1, AI2, AI3: +/- 0.15 % of maximum value for analog input; AO1, AO2: +/- 0.2 % for analog output |
| Refresh time | Relay output (R1, R2, R3): 5 ms (+/- 0.5 ms) |
| Isolation | Between power and control terminals |
| Power range | 110…220 kW at 380…440 V 3 phases; 110…220 kW at 480…500 V 3 phases |
| Enclosure mounting | Wall mounted |
| 4 quadrant operation possible | False |
| Asynchronous motor control profile | Constant torque standard; Optimized torque mode; Variable torque standard |
| Synchronous motor control profile | Permanent magnet motor; Synchronous reluctance motor |
| Maximum output frequency | 500 kHz |
| Acceleration and deceleration ramps | Linear adjustable separately from 0.01...9999 s |
| Motor slip compensation | Adjustable; Can be suppressed; Not available in permanent magnet motor law; Automatic whatever the load |
| Switching frequency | 2.5...8 kHz with derating factor; 2...8 kHz adjustable |
| Nominal switching frequency | 2.5 kHz |
| Braking to standstill | By DC injection |
| Brake chopper integrated | False |
| Maximum input current | 284.0 A |
| Maximum output voltage | 480.0 V |
| Apparent power | 201.3 kVA at 480 V (normal duty); 161.4 kVA at 480 V (heavy duty) |
| Maximum transient current | 332.2 A during 60 s (normal duty); 375 A during 60 s (heavy duty) |
| Network frequency | 50...60 Hz |
| Prospective line Isc | 50 kA |
| Base load current at high overload | 250.0 A |
| Base load current at low overload | 302.0 A |
| Power dissipation in W | Forced convection: 3270 W at 380 V, switching frequency 2.5 kHz |
| With safety function Safely Limited Speed (SLS) | False |
| With safety function Safe brake management (SBC/SBT) | False |
| With safety function Safe Operating Stop (SOS) | False |
| With safety function Safe Position (SP) | False |
| With safety function Safe programmable logic | False |
| With safety function Safe Speed Monitor (SSM) | False |
| With safety function Safe Stop 1 (SS1) | False |
| With sft fct Safe Stop 2 (SS2) | False |
| With safety function Safe torque off (STO) | True |
| With safety function Safely Limited Position (SLP) | False |
| With safety function Safe Direction (SDI) | False |
| Protection type | Thermal protection: motor; Safe torque off: motor; Motor phase break: motor; Thermal protection: drive; Safe torque off: drive; Overheating: drive; Overcurrent between output phases and earth: drive; Overload of output voltage: drive; Short-circuit protection: drive; Motor phase break: drive; Overvoltages on the DC bus: drive; Line supply overvoltage: drive; Line supply undervoltage: drive; Line supply phase loss: drive; Overspeed: drive; Break on the control circuit: drive |
| Quantity per set | 1 |
| Width | 320 mm |
| Height | 852 mm |
| Depth | 390 mm |
| Net weight | 82 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Insulation resistance | > 1 MOhm 500 V DC for 1 minute to earth |
| Noise level | 69.9 dB conforming to 86/188/EEC |
| Pollution degree | 2 conforming to IEC 61800-5-1 |
| Vibration resistance | 1.5 mm peak to peak (f= 2…13 Hz) conforming to IEC 60068-2-6; 1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6 |
| Shock resistance | 15 gn for 11 ms conforming to IEC 60068-2-27 |
| Relative humidity | 5…95 % without condensation conforming to IEC 60068-2-3 |
| Ambient air temperature for operation | -15…50 °C (without derating); 50…60 °C (with derating factor) |
| Operating position | Vertical +/- 10 degree |
| Product certifications | ATEX INERIS; DNV-GL; CSA; TÜV; UL; ATEX zone 2/22 |
| Marking | CE |
| Standards | UL 508C; IEC 61800-3; IEC 61800-3 environment 1 category C2; EN/IEC 61800-3 environment 2 category C3; IEC 61800-5-1; IEC 61000-3-12; IEC 60721-3; IEC 61508; IEC 13849-1 |
| Electromagnetic compatibility | Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2; Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3; Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4; 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5; Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 |
| Environmental class (during operation) | Class 3C3 according to IEC 60721-3-3; Class 3S3 according to IEC 60721-3-3 |
| Maximum acceleration under shock impact (during operation) | 60 m/s² at 11 ms |
| Maximum acceleration under vibrational stress (during operation) | 10 m/s² at 13...200 Hz |
| Maximum deflection under vibratory load (during operation) | 1.5 mm at 2...13 Hz |
| Permitted relative humidity (during operation) | Class 3K5 according to EN 60721-3 |
| Volume of cooling air | 600 m3/h |
| Overvoltage category | III |
| Regulation loop | Adjustable PID regulator |
| Ambient air transport temperature | -40…70 °C |
| Ambient air temperature for storage | -40…70 °C |
| Logistical informations |
| Country of origin | IN |
| Main |
| Range of product | Altivar Process ATV600 |
| Product specific application | Process and utilities |
| Product or component type | Variable speed drive |
| Variant | Standard version |
| Device short name | ATV630 |
| Mounting mode | Wall mount |
| Communication port protocol | Modbus serial; Modbus TCP; Ethernet |
| [Us] rated supply voltage | 380...480 V - 15...10 % |
| Relative symmetric mains voltage tolerance | 10 % |
| Relative symmetric network frequency tolerance | 5 % |
| nominal output current | 302.0 A |
| IP degree of protection | IP21 |
| Product destination | Asynchronous motors; Synchronous motors |
| EMC filter | Integrated with 150 m conforming to IEC 61800-3 category C3 |
| Type of cooling | Forced convection |
| Supply frequency | 50...60 Hz - 5...5 % |
| Motor power kW | 160 kW (normal duty); 132 kW (heavy duty) |
| Motor power hp | 250 hp normal duty; 200 hp heavy duty |
| Line current | 284 A at 380 V (normal duty); 262 A at 480 V (normal duty); 237 A at 380 V (heavy duty); 213 A at 480 V (heavy duty) |
| Continuous output current | 302 A at 2.5 kHz for normal duty; 250 A at 2.5 kHz for heavy duty |
| Speed drive output frequency | 0.1…500 Hz |
| Safety function | STO (safe torque off) SIL 3 |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 65.000 cm |
| Package 1 Width | 47.000 cm |
| Package 1 Length | 103.000 cm |
| Package 1 Weight | 125.000 kg |
The frequency converter ATV630C16N4 from Schneider Electric belongs to the Altivar Process ATV600 series and is designed as a variable speed drive for use in industrial processes and auxiliary equipment. It is used for controlling and protecting asynchronous and synchronous motors, particularly in applications such as pump operation, where precise speed control and load adaptation are required. The device is rated for a nominal voltage of 380 to 480 V, with an allowable voltage tolerance of ±10 % and a network frequency of 50 to 60 Hz ±5 %. The protection class IP21 ensures protection against contact with fingers and against vertically falling water droplets, making it suitable for indoor installations. Mounting is done in surface-mounted mode, with dimensions of 320 mm (width) × 852 mm (height) × 390 mm (depth).
The frequency converter is specifically designed for process applications, particularly for pumps requiring variable speed to optimize energy consumption and operating costs. It is suitable for drives with constant, variable, or optimized torque, as well as for synchronous motors with permanent magnets (PM). The integrated safety function STO (Safe Torque Off) with SIL 3 certification enables safe torque shutdown, which is required in safety-critical installations. The maximum output frequency is 500 Hz, enabling even very high speeds to be achieved.
The device features 8 discrete inputs, with DI7 and DI8 programmable as pulse inputs (0 to 30 kHz, 24 V DC). The inputs support 16 preset speeds. There are 3 relay outputs (R1, R2, R3), each rated for 250 V AC/3000 mA or 30 V DC/3000 mA (R1), and 250 V AC/5000 mA or 30 V DC/5000 mA (R2 and R3). The maximum switching power is 3 A at 250 V AC or 3 A at 30 V DC on resistive load, and 2 A on inductive load (cos φ = 0.4, L/R = 7 ms). The minimum switching current is 5 mA at 24 V DC. The three analog inputs (AI1, AI2, AI3) are software-configurable for voltage (0–10 V DC, -10–10 V DC) or current (0–20 mA) with a resolution of 12 bits. The two analog outputs (AQ1, AQ2) are also software-configurable for voltage (0–10 V DC) or current (0–20 mA) with a resolution of 10 bits. Additionally, there are configurable current outputs DQ- and DQ+ with 30 V DC and 100 mA.
The frequency converter operates with forced convection cooling, ensuring continuous cooling during operation. The integrated EMC filtering complies with IEC 61800-3 Category C3 and is designed for cable lengths up to 150 m, ensuring compliance with electromagnetic compatibility requirements in industrial environments. The continuous output power is 160 kW in normal operation and 132 kW in heavy-duty operation, with output currents of 302 A (normal operation) and 250 A (heavy-duty operation) at a frequency of 2.5 kHz. The input currents are 284 A (380 V) and 262 A (480 V) in normal operation, and 237 A (380 V) and 213 A (480 V) in heavy-duty operation. The overload capacity is 110 % for 60 seconds in normal operation and 150 % for 60 seconds in high overload mode (with derating by one power class).
The frequency converter supports integrated communication protocols such as Modbus TCP over Ethernet and serial Modbus interface. Transmission speeds include 10/100 Mbit/s for Ethernet and 4,800 to 38,400 Baud for the serial interface. Access is provided as a slave in a Modbus TCP network. Available accessories include various Modbus cables (e.g. VW3-A1104R50, VW3A8306R03), T-distributors (e.g. VW3A8306TF03), mounting kits (e.g. VW3A1112, VW3A1115), and terminal boxes (e.g. VW3A9704), which facilitate installation and integration into existing systems. Configuration is performed via a decentralized graphical operator terminal, an integrated web server, DTM (Device Type Manager), and the SoMove software. Optional accessories include I/O expansion cards, relay output cards, and communication cards (e.g. EtherNet/IP, ProfiNet, CANopen).
Surface mounting is performed on a vertical wall or panel. Cooling is achieved through forced convection, requiring sufficient ventilation space and a clean environment. Installation requires compliance with electrical safety regulations and correct wiring of inputs and outputs. The integrated EMC filtering reduces network disturbances, enabling compatible installation in existing systems.
The frequency converter offers high operational reliability through the integrated STO function and robust EMC filtering. The flexible configuration of I/O interfaces allows adaptation to different applications. Support for multiple communication protocols (Modbus TCP, serial) simplifies integration into existing automation systems. The high output frequency of up to 500 Hz extends the application range to drives with high speeds. Continuous cooling and high overload capacity ensure reliable performance even under demanding operating conditions.