| Complementary |
| Discrete input number | 7 |
| Discrete input type | STO safe torque off, 24 V DC, impedance: 1.5 kOhm; DI1...DI6 logic inputs, 24 V DC (30 V); DI5 programmable as pulse input: 0…30 kHz, 24 V DC (30 V) |
| Discrete input logic | Positive logic (source); Negative logic (sink) |
| Discrete output number | 3 |
| Discrete output type | Open collector DQ+ 0…1 kHz 30 V DC 100 mA; Open collector DQ- 0…1 kHz 30 V DC 100 mA |
| Analogue input number | 3 |
| Analogue input type | AI1 voltage: 0...10 V DC, impedance: 30 kOhm, resolution 10 bits; AI2 bipolar differential voltage: +/- 10 V DC, impedance: 30 kOhm, resolution 10 bits; AI3 current: 0...20 mA (or 4-20 mA, x-20 mA, 20-x mA or other patterns by configuration), impedance: 250 Ohm, resolution 10 bits |
| Analogue output number | 1 |
| Analogue output type | Software-configurable current AQ1: 0...20 mA impedance 800 Ohm, resolution 10 bits; Software-configurable voltage AQ1: 0...10 V DC impedance 470 Ohm, resolution 10 bits |
| Relay output type | Configurable relay logic R1A 1 NO electrical durability 100000 cycles; Configurable relay logic R1B 1 NC electrical durability 100000 cycles; Configurable relay logic R1C; Configurable relay logic R2A 1 NO electrical durability 100000 cycles; Configurable relay logic R2C |
| Maximum switching current | Relay output R1A, R1B, R1C on resistive load, cos phi = 1: 3 A at 250 V AC; Relay output R1A, R1B, R1C on resistive load, cos phi = 1: 3 A at 30 V DC; Relay output R1A, R1B, R1C, R2A, R2C on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC; Relay output R1A, R1B, R1C, R2A, R2C on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC; Relay output R2A, R2C on resistive load, cos phi = 1: 5 A at 250 V AC; Relay output R2A, R2C on resistive load, cos phi = 1: 5 A at 30 V DC |
| Minimum switching current | Relay output R1A, R1B, R1C, R2A, R2C: 5 mA at 24 V DC |
| Method of access | Slave CANopen |
| 4 quadrant operation possible | True |
| Asynchronous motor control profile | Voltage/frequency ratio, 5 points; Flux vector control without sensor, standard; Voltage/frequency ratio - Energy Saving, quadratic U/f; Flux vector control without sensor - Energy Saving; Voltage/frequency ratio, 2 points |
| Synchronous motor control profile | Vector control without sensor |
| Maximum output frequency | 0.599 kHz |
| Acceleration and deceleration ramps | Linear; U; S; CUS; Ramp switching; Acceleration/deceleration ramp adaptation; Acceleration/deceleration automatic stop with DC injection |
| Motor slip compensation | Automatic whatever the load; Adjustable 0...300 %; Not available in voltage/frequency ratio (2 or 5 points) |
| Switching frequency | 2...16 kHz adjustable; 4...16 kHz with derating factor |
| Nominal switching frequency | 4 kHz |
| Braking to standstill | By DC injection |
| Brake chopper integrated | True |
| Line current | 8.7 A at 380 V (heavy duty); 6.6 A at 500 V (heavy duty) |
| Maximum input current | 8.7 A |
| Maximum output voltage | 500 V |
| Apparent power | 5.7 kVA at 500 V (heavy duty) |
| Network frequency | 50...60 Hz |
| Relative symmetric network frequency tolerance | 5 % |
| Prospective line Isc | 5 kA |
| Base load current at high overload | 8.0 A |
| Power dissipation in W | Fan: 74.0 W at 380 V, switching frequency 4 kHz |
| With safety function Safely Limited Speed (SLS) | True |
| With safety function Safe brake management (SBC/SBT) | False |
| With safety function Safe Operating Stop (SOS) | False |
| With safety function Safe Position (SP) | False |
| With safety function Safe programmable logic | False |
| With safety function Safe Speed Monitor (SSM) | False |
| With safety function Safe Stop 1 (SS1) | True |
| With sft fct Safe Stop 2 (SS2) | False |
| With safety function Safe torque off (STO) | True |
| With safety function Safely Limited Position (SLP) | False |
| With safety function Safe Direction (SDI) | False |
| Protection type | Input phase breaks: drive; Overcurrent between output phases and earth: drive; Overheating protection: drive; Short-circuit between motor phases: drive; Thermal protection: drive |
| Width | 140 mm |
| Height | 184.0 mm |
| Depth | 158.0 mm |
| Net weight | 2.1 kg |
| Transient overtorque | 170…200 % of nominal motor torque |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Operating position | Vertical +/- 10 degree |
| Product certifications | CE; ATEX; NOM; GOST; EAC; RCM; KC |
| Marking | CE; ATEX; UL; CSA; EAC; RCM |
| Standards | IEC 61800-5-1 |
| Electromagnetic compatibility | Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2; Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3; Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4; 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5; Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6; Voltage dips and interruptions immunity test conforming to IEC 61000-4-11 |
| Environmental class (during operation) | Class 3C3 according to IEC 60721-3-3; Class 3S2 according to IEC 60721-3-3 |
| Maximum acceleration under shock impact (during operation) | 150 m/s² at 11 ms |
| Maximum acceleration under vibrational stress (during operation) | 10 m/s² at 13...200 Hz |
| Maximum deflection under vibratory load (during operation) | 1.5 mm at 2...13 Hz |
| Permitted relative humidity (during operation) | Class 3K5 according to EN 60721-3 |
| Volume of cooling air | 37.7 m3/h |
| Overvoltage category | III |
| Regulation loop | Adjustable PID regulator |
| Speed accuracy | +/- 10 % of nominal slip 0.2 Tn to Tn |
| Pollution degree | 2 |
| Ambient air transport temperature | -25…70 °C |
| Ambient air temperature for operation | -10…50 °C without derating; 50…60 °C with derating factor |
| Ambient air temperature for storage | -25…70 °C |
| Logistical informations |
| Country of origin | LV |
| Main |
| Range of product | Altivar Machine ATV320 |
| Product or component type | Variable speed drive |
| Product specific application | Complex machines |
| Variant | Standard version; With disconnect switch |
| Format of the drive | Compact |
| Mounting mode | Wall mount |
| Communication port protocol | Modbus serial; CANopen |
| Option card | Communication module, CANopen; Communication module, EtherCAT; Communication module, Profibus DP V1; Communication module, PROFINET; Communication module, Ethernet Powerlink; Communication module, EtherNet/IP; Communication module, DeviceNet |
| [Us] rated supply voltage | 380...500 V - 15...10 % |
| nominal output current | 5.5 A |
| Motor power kW | 2.2 kW for heavy duty |
| Motor power hp | 3 hp |
| EMC filter | Class C2 EMC filter integrated |
| IP degree of protection | IP20 |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 24.500 cm |
| Package 1 Width | 19.500 cm |
| Package 1 Length | 26.700 cm |
| Package 1 Weight | 2.652 kg |
| Unit Type of Package 2 | P06 |
| Number of Units in Package 2 | 12 |
| Package 2 Height | 75.000 cm |
| Package 2 Width | 60.000 cm |
| Package 2 Length | 80.000 cm |
| Package 2 Weight | 45.280 kg |
Frequency converter ATV320, compact. Dimensions 140 x 228 x 158 (with EMC plate) mm, power KW 2.2 kW. Supply voltage 3-phase 380-500 V 50/60 Hz, with integrated EMC filter. Rated supply voltage, min. U1, max. U2 200 (U1)-240 V (U2), 380 (U1)-500 V (U2). Converters are supplied with an integrated EMC filter of category C2. The filter can be switched off. Converters are supplied with an EMC plate for assembly by the customer. Description Integrated safety technology with 5 functions safe torque off (STO), safe stop1 (SS1), safe reduced speed (SLS), safe contactor door locking (GDL), safe maximum speed (SMS). Operation of asynchronous and synchronous motors in open loop. SVC control (sensorless vector control) provides the highest speed quality and stability U/F control, U/F2 control, energy saving function. Max. frequency 599 Hz. Extremely simple commissioning, intuitive operation and thanks to Plug & Drive, preset to the most common applications. Options for loading, editing and saving the inverter configurations with tools such as the SoMove commissioning software, the decentralized terminals and the -Simple-Loader- and -Multi-Loader- configuration tools. Class A radio interference filter integrated, can be deactivated. For operation on IT networks. 6 logic inputs can be assigned multiple functions, 3 analog inputs, 2 of which can be switched to digital inputs. Integrated brake module enables 4-quadrant operation without retrofitting.