| Complementary |
| Discrete input number | 7 |
| Discrete input type | STO safe torque off, 24 V DC, impedance: 1.5 kOhm; DI1...DI6 logic inputs, 24 V DC (30 V); DI5 programmable as pulse input: 0…30 kHz, 24 V DC (30 V) |
| Discrete input logic | Positive logic (source); Negative logic (sink) |
| Discrete output number | 3 |
| Discrete output type | Open collector DQ+ 0…1 kHz 30 V DC 100 mA; Open collector DQ- 0…1 kHz 30 V DC 100 mA |
| Analogue input number | 3 |
| Analogue input type | AI1 voltage: 0...10 V DC, impedance: 30 kOhm, resolution 10 bits; AI2 bipolar differential voltage: +/- 10 V DC, impedance: 30 kOhm, resolution 10 bits; AI3 current: 0...20 mA (or 4-20 mA, x-20 mA, 20-x mA or other patterns by configuration), impedance: 250 Ohm, resolution 10 bits |
| Analogue output number | 1 |
| Analogue output type | Software-configurable current AQ1: 0...20 mA impedance 800 Ohm, resolution 10 bits; Software-configurable voltage AQ1: 0...10 V DC impedance 470 Ohm, resolution 10 bits |
| Relay output type | Configurable relay logic R1A 1 NO electrical durability 100000 cycles; Configurable relay logic R1B 1 NC electrical durability 100000 cycles; Configurable relay logic R1C; Configurable relay logic R2A 1 NO electrical durability 100000 cycles; Configurable relay logic R2C |
| Maximum switching current | Relay output R1A, R1B, R1C on resistive load, cos phi = 1: 3 A at 250 V AC; Relay output R1A, R1B, R1C on resistive load, cos phi = 1: 3 A at 30 V DC; Relay output R1A, R1B, R1C, R2A, R2C on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC; Relay output R1A, R1B, R1C, R2A, R2C on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC; Relay output R2A, R2C on resistive load, cos phi = 1: 5 A at 250 V AC; Relay output R2A, R2C on resistive load, cos phi = 1: 5 A at 30 V DC |
| Minimum switching current | Relay output R1A, R1B, R1C, R2A, R2C: 5 mA at 24 V DC |
| Method of access | Slave CANopen |
| 4 quadrant operation possible | True |
| Asynchronous motor control profile | Voltage/frequency ratio, 5 points; Flux vector control without sensor, standard; Voltage/frequency ratio - Energy Saving, quadratic U/f; Flux vector control without sensor - Energy Saving; Voltage/frequency ratio, 2 points |
| Synchronous motor control profile | Vector control without sensor |
| Maximum output frequency | 0.599 kHz |
| Acceleration and deceleration ramps | Linear; U; S; CUS; Ramp switching; Acceleration/deceleration ramp adaptation; Acceleration/deceleration automatic stop with DC injection |
| Motor slip compensation | Automatic whatever the load; Adjustable 0...300 %; Not available in voltage/frequency ratio (2 or 5 points) |
| Switching frequency | 2...16 kHz adjustable; 4...16 kHz with derating factor |
| Nominal switching frequency | 4 kHz |
| Braking to standstill | By DC injection |
| Brake chopper integrated | True |
| Line current | 5.0 A at 380 V (heavy duty); 3.8 A at 500 V (heavy duty) |
| Maximum input current | 5.0 A |
| Maximum output voltage | 500 V |
| Apparent power | 3.3 kVA at 500 V (heavy duty) |
| Network frequency | 50...60 Hz |
| Relative symmetric network frequency tolerance | 5 % |
| Prospective line Isc | 5 kA |
| Base load current at high overload | 9.0 A |
| Power dissipation in W | Fan: 41 W at 380 V, switching frequency 4 kHz |
| With safety function Safely Limited Speed (SLS) | True |
| With safety function Safe brake management (SBC/SBT) | False |
| With safety function Safe Operating Stop (SOS) | False |
| With safety function Safe Position (SP) | False |
| With safety function Safe programmable logic | False |
| With safety function Safe Speed Monitor (SSM) | False |
| With safety function Safe Stop 1 (SS1) | True |
| With sft fct Safe Stop 2 (SS2) | False |
| With safety function Safe torque off (STO) | True |
| With safety function Safely Limited Position (SLP) | False |
| With safety function Safe Direction (SDI) | False |
| Protection type | Input phase breaks: drive; Overcurrent between output phases and earth: drive; Overheating protection: drive; Short-circuit between motor phases: drive; Thermal protection: drive |
| Width | 45.0 mm |
| Height | 325.0 mm |
| Depth | 245.0 mm |
| Net weight | 2.5 kg |
| Transient overtorque | 170…200 % of nominal motor torque |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Operating position | Vertical +/- 10 degree |
| Product certifications | CE; ATEX; NOM; GOST; EAC; RCM; KC |
| Marking | CE; ATEX; UL; CSA; EAC; RCM |
| Standards | IEC 61800-5-1 |
| Electromagnetic compatibility | Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2; Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3; Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4; 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5; Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6; Voltage dips and interruptions immunity test conforming to IEC 61000-4-11 |
| Environmental class (during operation) | Class 3C3 according to IEC 60721-3-3; Class 3S2 according to IEC 60721-3-3 |
| Maximum acceleration under shock impact (during operation) | 150 m/s² at 11 ms |
| Maximum acceleration under vibrational stress (during operation) | 10 m/s² at 13...200 Hz |
| Maximum deflection under vibratory load (during operation) | 1.5 mm at 2...13 Hz |
| Permitted relative humidity (during operation) | Class 3K5 according to EN 60721-3 |
| Volume of cooling air | 9.4 m3/h |
| Overvoltage category | III |
| Regulation loop | Adjustable PID regulator |
| Speed accuracy | +/- 10 % of nominal slip 0.2 Tn to Tn |
| Pollution degree | 2 |
| Ambient air transport temperature | -25…70 °C |
| Ambient air temperature for operation | -10…50 °C without derating; 50…60 °C with derating factor |
| Ambient air temperature for storage | -25…70 °C |
| Logistical informations |
| Country of origin | ID |
| Main |
| Range of product | Altivar Machine ATV320 |
| Product or component type | Variable speed drive |
| Product specific application | Complex machines |
| Variant | Standard version; With disconnect switch |
| Format of the drive | Book |
| Mounting mode | Cabinet mount |
| Communication port protocol | Modbus serial; CANopen |
| Option card | Communication module, CANopen; Communication module, EtherCAT; Communication module, Profibus DP V1; Communication module, PROFINET; Communication module, Ethernet Powerlink; Communication module, EtherNet/IP; Communication module, DeviceNet |
| [Us] rated supply voltage | 380...500 V - 15...10 % |
| nominal output current | 3.0 A |
| Motor power kW | 1.1 kW for heavy duty |
| Motor power hp | 1.5 hp |
| EMC filter | Class C2 EMC filter integrated |
| IP degree of protection | IP20 |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 8.300 cm |
| Package 1 Width | 27.500 cm |
| Package 1 Length | 32.500 cm |
| Package 1 Weight | 2.328 kg |
| Unit Type of Package 2 | S06 |
| Number of Units in Package 2 | 24 |
| Package 2 Height | 75.000 cm |
| Package 2 Width | 60.000 cm |
| Package 2 Length | 80.000 cm |
| Package 2 Weight | 73.264 kg |
The ATV320U11N4B frequency converter from Schneider Electric belongs to the Altivar Machine ATV320 series and is designed as a variable-speed drive for use in complex machines. The device is book-sized and intended for mounting in an enclosure. It features integrated safety technology with five functions: safe torque off (STO), safe hold 1 (SS1), safe limited speed (SLS), safe guarded door interlock (GDL), and safe maximum speed (SMS). These functions enable safe operation in applications requiring high machine safety standards. The converter is suitable for operation on IT networks and includes an integrated EMC filter of category C2, which can be deactivated. Additionally, an EMC plate for customer-side mounting is supplied.
Applications
The ATV320U11N4B is designed for industrial applications involving complex machines, particularly in systems requiring precise speed control and safe operating sequences. It is suitable for operating asynchronous and synchronous motors in open-loop mode, with sensorless vector control (SVC) ensuring high speed quality and stability. The integrated control enables four-quadrant operation, allowing braking without additional components. The maximum output frequency is 599 Hz, enabling flexible adaptation to various drive requirements.
Functions and Equipment in Detail
The device has seven discrete inputs, one of which is configured as an STO safety input (24 V DC). The remaining inputs (DI1 to DI6) are logic inputs available at 24 V DC (30 V), with DI5 additionally configurable as a pulse input (0…30 kHz). The discrete outputs include three open-collector outputs (DQ+ and DQ-), capable of switching up to 100 mA at 30 V DC. There are three analog inputs: AI1 for voltage (0–10 V DC), AI2 for bipolar differential voltage (±10 V DC), and AI3 for current (0–20 mA, configurable). One analog output (AQ1) is software-configurable for current (0–20 mA) or voltage (0–10 V DC). The relay outputs (R1A, R1B, R1C, R2A, R2C) are configurable and have an electrical life of 100,000 cycles. The maximum switching current is 3 A at 250 V AC or 30 V DC for R1A/B/C, and 5 A for R2A/C with resistive load.
Technology Explained Simply
The frequency converter operates with a rated voltage of 380 to 500 V (±10 %) and a nominal output current of 3.0 A. The motor power is 1.1 kW (1.5 hp) in heavy-duty operation. The integrated EMC technology (Class C2) ensures low electromagnetic emission and is suitable for industrial environments. Control is performed via various profiles: U/f characteristic (5-point, energy-saving mode, quadratic), sensorless vector flux control (standard and energy-saving mode), and for synchronous motors, also vector-oriented without encoder. Acceleration and deceleration ramps are configurable as linear, U-shaped, S-shaped, CUS-shaped, or via ramp switching. Motor slip compensation is automatically and load-independent activatable, with settings from 0 to 300 %.
Compatibility and Accessories
The ATV320U11N4B supports various communication protocols, including Modbus serial and CANopen. Optional communication modules for EtherCAT, Profibus DP V1, Profinet, Ethernet Powerlink, EtherNet/IP, and DeviceNet can be retrofitted. Suitable accessories include line reactors (e.g. VW3-A4551), power contactors (e.g. LC1D09BL), brake resistors (e.g. VW3A7730), and various option cards for industrial networks (e.g. VW3-A3607 for Profibus DP, VW3A3627 for Profinet). Configuration is done using tools such as the commissioning software SoMove, decentralized terminals, or configuration tools like Simple-Loader and Multi-Loader.
Mounting and Installation
The frequency converter is designed for mounting in an enclosure and is supplied in book format. Dimensions are 45 mm (width) × 325 mm (height) × 245 mm (depth). The integrated EMC plate allows for easy installation at the customer site. Commissioning is done via Plug & Drive, with devices pre-configured to quickly start common applications. Configuration can be performed using various software tools, allowing settings to be saved, loaded, and edited.
Operational Advantages
The ATV320U11N4B offers high operational safety through integrated safety functions and flexible control via various control profiles. The integrated EMC technology and the ability to deactivate the filter expand application possibilities. The wide range of inputs and outputs enables flexible connection to various control systems. The support for 4-quadrant operation without additional components reduces system complexity. Intuitive operation and the Plug-&-Drive function shorten commissioning time. Configuration options via various tools allow for centralized or decentralized control of the system.
Protection Rating (IP)
The frequency converter has an IP20 protection rating, making it suitable for use in enclosed enclosures. The IP20 rating protects against finger contact and solid foreign objects, but not against water or dust. Additional protective measures are required for outdoor or humid environments.
Communication Protocols
Integrated communication is via Modbus serial and CANopen. Optional communication modules for EtherCAT, Profibus DP V1, Profinet, Ethernet Powerlink, EtherNet/IP, and DeviceNet are available, enabling connection to various industrial networks. Access method is as a slave in the CANopen network.
Control Profiles
For asynchronous motors, various control profiles are available: U/f characteristic (5-point, energy-saving mode, quadratic), sensorless vector flux control (standard and energy-saving mode). For synchronous motors, sensorless vector flux control without encoder is available. Ramp control includes linear, U-shaped, S-shaped, CUS-shaped ramps, ramp switching, and automatic stop with DC brake.
Analog and Digital Interfaces
The three analog inputs (AI1: 0–10 V DC, AI2: ±10 V DC, AI3: 0–20 mA) allow connection to sensors and measuring devices. The analog output (AQ1) is software-configurable for current (0–20 mA) or voltage (0–10 V DC). The seven discrete inputs (including STO) and three discrete outputs (open collector) offer flexible connection to control and safety systems. The relay outputs (R1A/B/C, R2A/C) are configurable and suitable for various load types.
Energy Efficiency and Operation
The frequency converter supports energy-saving functions, particularly in U/f energy-saving mode and with sensorless vector flux control. The integrated EMC technology (Class C2) ensures low electromagnetic emission, enabling operation in IT networks. The maximum output frequency of 599 Hz and the various ramp control options allow precise adaptation to different drive requirements. The integrated braking function enables 4-quadrant operation without additional components.
Commissioning and Configuration
Commissioning is performed via Plug & Drive, with devices pre-configured to quickly start common applications. Configuration can be done using various software tools, allowing settings to be saved, loaded, and edited. Support from tools such as SoMove, Simple-Loader, and Multi-Loader enables centralized or decentralized control of the system.