| Complementary |
| Discrete input number | 7 |
| Discrete input type | STO safe torque off, 24 V DC, impedance: 1.5 kOhm; DI1...DI6 logic inputs, 24 V DC (30 V); DI5 programmable as pulse input: 0…30 kHz, 24 V DC (30 V) |
| Discrete input logic | Positive logic (source); Negative logic (sink) |
| Discrete output number | 3 |
| Discrete output type | Open collector DQ+ 0…1 kHz 30 V DC 100 mA; Open collector DQ- 0…1 kHz 30 V DC 100 mA |
| Analogue input number | 3 |
| Analogue input type | AI1 voltage: 0...10 V DC, impedance: 30 kOhm, resolution 10 bits; AI2 bipolar differential voltage: +/- 10 V DC, impedance: 30 kOhm, resolution 10 bits; AI3 current: 0...20 mA (or 4-20 mA, x-20 mA, 20-x mA or other patterns by configuration), impedance: 250 Ohm, resolution 10 bits |
| Analogue output number | 1 |
| Analogue output type | Software-configurable current AQ1: 0...20 mA impedance 800 Ohm, resolution 10 bits; Software-configurable voltage AQ1: 0...10 V DC impedance 470 Ohm, resolution 10 bits |
| Relay output type | Configurable relay logic R1A 1 NO electrical durability 100000 cycles; Configurable relay logic R1B 1 NC electrical durability 100000 cycles; Configurable relay logic R1C; Configurable relay logic R2A 1 NO electrical durability 100000 cycles; Configurable relay logic R2C |
| Maximum switching current | Relay output R1A, R1B, R1C on resistive load, cos phi = 1: 3 A at 250 V AC; Relay output R1A, R1B, R1C on resistive load, cos phi = 1: 3 A at 30 V DC; Relay output R1A, R1B, R1C, R2A, R2C on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC; Relay output R1A, R1B, R1C, R2A, R2C on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC; Relay output R2A, R2C on resistive load, cos phi = 1: 5 A at 250 V AC; Relay output R2A, R2C on resistive load, cos phi = 1: 5 A at 30 V DC |
| Minimum switching current | Relay output R1A, R1B, R1C, R2A, R2C: 5 mA at 24 V DC |
| Method of access | Slave CANopen |
| 4 quadrant operation possible | True |
| Asynchronous motor control profile | Voltage/frequency ratio, 5 points; Flux vector control without sensor, standard; Voltage/frequency ratio - Energy Saving, quadratic U/f; Flux vector control without sensor - Energy Saving; Voltage/frequency ratio, 2 points |
| Synchronous motor control profile | Vector control without sensor |
| Maximum output frequency | 0.599 kHz |
| Acceleration and deceleration ramps | Linear; U; S; CUS; Ramp switching; Acceleration/deceleration ramp adaptation; Acceleration/deceleration automatic stop with DC injection |
| Motor slip compensation | Automatic whatever the load; Adjustable 0...300 %; Not available in voltage/frequency ratio (2 or 5 points) |
| Switching frequency | 2...16 kHz adjustable; 4...16 kHz with derating factor |
| Nominal switching frequency | 4 kHz |
| Braking to standstill | By DC injection |
| Brake chopper integrated | True |
| Line current | 47.3 A at 380 V (heavy duty); 33.3 A at 500 V (heavy duty) |
| Maximum input current | 47.3 A |
| Maximum output voltage | 500 V |
| Apparent power | 28.8 kVA at 500 V (heavy duty) |
| Network frequency | 50...60 Hz |
| Relative symmetric network frequency tolerance | 5 % |
| Prospective line Isc | 22 kA |
| Base load current at high overload | 4 A |
| Power dissipation in W | Fan: 452.0 W at 380 V, switching frequency 4 kHz |
| With safety function Safely Limited Speed (SLS) | True |
| With safety function Safe brake management (SBC/SBT) | False |
| With safety function Safe Operating Stop (SOS) | False |
| With safety function Safe Position (SP) | False |
| With safety function Safe programmable logic | False |
| With safety function Safe Speed Monitor (SSM) | False |
| With safety function Safe Stop 1 (SS1) | True |
| With sft fct Safe Stop 2 (SS2) | False |
| With safety function Safe torque off (STO) | True |
| With safety function Safely Limited Position (SLP) | False |
| With safety function Safe Direction (SDI) | False |
| Protection type | Input phase breaks: drive; Overcurrent between output phases and earth: drive; Overheating protection: drive; Short-circuit between motor phases: drive; Thermal protection: drive |
| Width | 180 mm |
| Height | 404.0 mm |
| Depth | 232.0 mm |
| Net weight | 6.9 kg |
| Transient overtorque | 170…200 % of nominal motor torque |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Operating position | Vertical +/- 10 degree |
| Product certifications | CE; ATEX; NOM; GOST; EAC; RCM; KC |
| Marking | CE; ATEX; UL; CSA; EAC; RCM |
| Standards | IEC 61800-5-1 |
| Electromagnetic compatibility | Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2; Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3; Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4; 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5; Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6; Voltage dips and interruptions immunity test conforming to IEC 61000-4-11 |
| Environmental class (during operation) | Class 3C3 according to IEC 60721-3-3; Class 3S2 according to IEC 60721-3-3 |
| Maximum acceleration under shock impact (during operation) | 150 m/s² at 11 ms |
| Maximum acceleration under vibrational stress (during operation) | 10 m/s² at 13...200 Hz |
| Maximum deflection under vibratory load (during operation) | 1.5 mm at 2...13 Hz |
| Permitted relative humidity (during operation) | Class 3K5 according to EN 60721-3 |
| Volume of cooling air | 156.0 m3/h |
| Overvoltage category | III |
| Regulation loop | Adjustable PID regulator |
| Speed accuracy | +/- 10 % of nominal slip 0.2 Tn to Tn |
| Pollution degree | 2 |
| Ambient air transport temperature | -25…70 °C |
| Ambient air temperature for operation | -10…50 °C without derating; 50…60 °C with derating factor |
| Ambient air temperature for storage | -25…70 °C |
| Logistical informations |
| Country of origin | ID |
| Main |
| Range of product | Altivar Machine ATV320 |
| Product or component type | Variable speed drive |
| Product specific application | Complex machines |
| Variant | Standard version |
| Format of the drive | Book |
| Mounting mode | Wall mount |
| Communication port protocol | Modbus serial; CANopen |
| Option card | Communication module, CANopen; Communication module, EtherCAT; Communication module, Profibus DP V1; Communication module, PROFINET; Communication module, Ethernet Powerlink; Communication module, EtherNet/IP; Communication module, DeviceNet |
| [Us] rated supply voltage | 380...500 V - 15...10 % |
| nominal output current | 33.0 A |
| Motor power kW | 15.0 kW for heavy duty |
| Motor power hp | 20 hp |
| EMC filter | Class C3 EMC filter integrated |
| IP degree of protection | IP20 |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 23.000 cm |
| Package 1 Width | 27.000 cm |
| Package 1 Length | 41.500 cm |
| Package 1 Weight | 8.742 kg |
| Unit Type of Package 2 | S06 |
| Number of Units in Package 2 | 4 |
| Package 2 Height | 75.000 cm |
| Package 2 Width | 60.000 cm |
| Package 2 Length | 80.000 cm |
| Package 2 Weight | 47.430 kg |
The ATV320D15N4B frequency converter from Schneider Electric is a variable speed drive from the Altivar Machine ATV320 series, specifically designed for use in complex machinery. It features a rated power of 15.0 kW (20 hp) and is designed for a nominal voltage of 380 to 500 V at 50/60 Hz. The unit is book-sized and intended for surface mounting, with dimensions of 180 mm (width) × 404 mm (height) × 232 mm (depth), including the supplied EMC plate for customer installation. The IP20 protection rating ensures protection against solid foreign objects and splashing water, but not against dust or prolonged water exposure.
The frequency converter is suitable for operating asynchronous and synchronous motors in open-loop mode. It is particularly used in applications requiring precise speed control, smooth start-up and braking processes, and high operational safety. The integrated safety technology includes five functions: safe torque off (STO), safe stop 1 (SS1), safe limited speed (SLS), safe guard door interlock (GDL), and safe maximum speed (SMS). These functions enable use in safety-critical applications in accordance with applicable standards.
The converter features 7 discrete inputs, one of which is configured as an STO safety input (24 V DC, impedance 1.5 kOhm). The remaining inputs (DI1 to DI6) are configurable as logic inputs (24 V DC, 30 V), with DI5 additionally usable as a pulse input (0–30 kHz). The logic of the inputs can operate in either positive (source) or negative (sink) logic. Three discrete outputs (Open Collector) are available, each capable of switching up to 100 mA at 30 V DC. Frequency control is achieved via three analog inputs: AI1 (0–10 V DC, 30 kOhm), AI2 (±10 V DC, 30 kOhm), and AI3 (0–20 mA, 250 Ohm), with AI3 also configurable for other current ranges such as 4–20 mA. One analog output (AQ1) is software-configurable for voltage (0–10 V DC, 470 Ohm) or current (0–20 mA, 800 Ohm). Additionally, two configurable relay outputs (R1A, R1B, R2A, R2C) are integrated, with an electrical life of 100,000 cycles. The maximum switching currents are 3 A at 250 V AC or 30 V DC for R1A/B/C, and 5 A at 250 V AC or 30 V DC for R2A/C.
The ATV320D15N4B supports various control profiles, including U/f characteristics (2- and 5-point), energy-saving mode, quadratic U/f characteristic, and sensorless vector control (SVC). The SVC control enables high speed accuracy and stability, especially under load fluctuations. Four-quadrant operation is possible thanks to the integrated braking module, eliminating the need for additional components for braking functions. The maximum output frequency is 599 Hz. Acceleration and deceleration ramps can be configured as linear, U-shaped, S-shaped, or according to a user-defined profile (CUS). Motor slip compensation is available, although not with U/f characteristics (2- or 5-point). Ramp behavior can also be automatically adjusted, for example via DC injection during automatic stop.
The converter is designed for operation on IT networks and features an integrated EMC filter of class C3, which can be deactivated. Communication is supported via serial interfaces (Modbus) and CANopen. Optional communication modules for EtherCAT, Profibus DP V1, Profinet, Ethernet Powerlink, EtherNet/IP, and DeviceNet can be retrofitted. Suitable accessories include power contactors (e.g. LC1D32BL, LC1D32V7) and option cards such as VW3-A3607 (Profibus DPv1), VW3A3627 (Profinet), or VW3-A3601 (EtherCAT). Line reactors (e.g. VW3A4554) and EMC filters (e.g. VW3A4425) are also available to improve electromagnetic compatibility.
The unit is intended for surface mounting and is supplied with an EMC plate to be installed by the customer. Installation is carried out on a 3-phase network with a voltage of 380 to 500 V. The integrated safety technology requires no additional safety modules, as the STO, SS1, SLS, GDL, and SMS functions are already implemented in the device. Commissioning is performed via Plug & Drive, with the converters pre-configured to cover common applications. Configurations can be loaded, edited, and secured using tools such as the commissioning software SoMove, decentralized terminals, or configuration tools Simple-Loader and Multi-Loader.
The ATV320D15N4B offers high operational safety through integrated safety functions, flexible control via diverse input and output options, and simple commissioning. Support for various control profiles allows adaptation to different drive requirements. The integrated braking module reduces system costs, as no additional braking resistors are required. The deactivatable EMC filter function provides flexibility in network integration, especially in environments where EMC requirements are lower. Communication capability via multiple protocols (Modbus, CANopen, EtherCAT, Profinet, etc.) enables integration into existing automation systems.