Complementary
Apparent power23.2 kVA at 380 V
Continuous output current37 A at 380 V; 37 A at 460 V
Maximum transient current40.7 A for 60 s
Speed drive output frequency0.5…200 Hz
Speed range1…10
Speed accuracy+/- 10 % of nominal slip 0.2 Tn to Tn
Local signalling1 LED (red) for DC bus energized
IsolationElectrical between power and control
Type of cableWithout mounting kit: 1 wire(s)IEC cable at 45 °C, copper 90 °C / XLPE/EPR; Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 70 °C / PVC; With UL Type 1 kit: 3 wire(s)UL 508 cable at 40 °C, copper 75 °C / PVC
Electrical connectionVIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES: terminal 2.5 mm² / 14 AWG; L1/R, L2/S, L3/T: terminal 16 mm² / 4 AWG; U/T1, V/T2, W/T3: terminal 25 mm² / 3 AWG
Tightening torque0.6 N.m (VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES); 2.2 N.m, 19.5 lb.in (L1/R, L2/S, L3/T); 5.4 N.m, 48 lb.in (U/T1, V/T2, W/T3)
SupplyInternal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %
Sampling duration2 ms +/- 0.5 ms F discrete; 2 ms +/- 0.5 ms R discrete; 2 ms +/- 0.5 ms RES discrete; 3.5 ms +/- 0.5 ms VIA analog; 22 ms +/- 0.5 ms VIB analog
Response timeFM 2 ms, tolerance +/- 0.5 ms for analog output(s); FLA, FLC 7 ms, tolerance +/- 0.5 ms for discrete output(s); FLB, FLC 7 ms, tolerance +/- 0.5 ms for discrete output(s); RY, RC 7 ms, tolerance +/- 0.5 ms for discrete output(s)
Accuracy+/- 0.6 % (VIA) for a temperature variation 60 °C; +/- 0.6 % (VIB) for a temperature variation 60 °C; +/- 1 % (FM) for a temperature variation 60 °C
Linearity errorVIA: +/- 0.15 % of maximum value for input; VIB: +/- 0.15 % of maximum value for input; FM: +/- 0.2 % for output
Analogue output typeFM switch-configurable voltage 0...10 V DC, impedance: 7620 Ohm, resolution 10 bits; FM switch-configurable current 0...20 mA, impedance: 970 Ohm, resolution 10 bits
Discrete output typeConfigurable relay logic: (FLA, FLC) NO - 100000 cycles; Configurable relay logic: (FLB, FLC) NC - 100000 cycles; Configurable relay logic: (RY, RC) NO - 100000 cycles
Minimum switching current3 mA at 24 V DC for configurable relay logic
Maximum switching current5 A at 250 V AC on resistive load - cos phi = 1 - L/R = 0 ms (FL, R); 5 A at 30 V DC on resistive load - cos phi = 1 - L/R = 0 ms (FL, R); 2 A at 250 V AC on inductive load - cos phi = 0.4 - L/R = 7 ms (FL, R); 2 A at 30 V DC on inductive load - cos phi = 0.4 - L/R = 7 ms (FL, R)
Discrete input typeF programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm; R programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm; RES programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm
Discrete input logicPositive logic (source) (F, R, RES), = 11 V (state 1); Negative logic (sink) (F, R, RES), >= 16 V (state 0)
Dielectric strength3535 V DC between earth and power terminals; 5092 V DC between control and power terminals
Insulation resistance>= 1 mOhm 500 V DC for 1 minute
Frequency resolutionDisplay unit: 0.1 Hz; Analog input: 0.024/50 Hz
Communication serviceRead device identification (43); Read holding registers (03) 2 words maximum; Write multiple registers (16) 2 words maximum; Write single register (06); Monitoring inhibitable; Time out setting from 0.1 to 100 s
Option cardCommunication card for LonWorks
Specific applicationHVAC
Discrete output number2
Analogue input number2
Analogue input typeVIA switch-configurable voltage: 0...10 V DC 24 V max, impedance: 30000 Ohm, resolution 10 bits; VIB configurable voltage: 0...10 V DC 24 V max, impedance: 30000 Ohm, resolution 10 bits; VIB configurable PTC probe: 0...6 probes, impedance: 1500 Ohm; VIA switch-configurable current: 0...20 mA, impedance: 250 Ohm, resolution 10 bits
Analogue output number1
Physical interface2-wire RS 485
Connector type1 RJ45; 1 open style
Transmission rate9600 bps or 19200 bps
Transmission frameRTU
Number of addresses1…247
Data format8 bits, 1 stop, odd even or no configurable parity
Type of polarizationNo impedance
Asynchronous motor control profileVoltage/frequency ratio, 5 points; Voltage/frequency ratio, 2 points; Flux vector control without sensor, standard; Voltage/frequency ratio, automatic IR compensation (U/f + automatic Uo); Voltage/frequency ratio - Energy Saving, quadratic U/f
Torque accuracy+/- 15 %
Transient overtorque120 % of nominal motor torque +/- 10 % for 60 s
Acceleration and deceleration rampsLinear adjustable separately from 0.01 to 3200 s; Automatic based on the load
Motor slip compensationNot available in voltage/frequency ratio motor control; Adjustable; Automatic whatever the load
Switching frequency6...16 kHz adjustable; 8...16 kHz with derating factor
Nominal switching frequency8 kHz
Braking to standstillBy DC injection
Network frequency47.5...63 Hz
Prospective line Isc22 kA
Protection typeOverheating protection: drive; Thermal power stage: drive; Short-circuit between motor phases: drive; Input phase breaks: drive; Overcurrent between output phases and earth: drive; Overvoltages on the DC bus: drive; Break on the control circuit: drive; Against exceeding limit speed: drive; Line supply overvoltage and undervoltage: drive; Line supply undervoltage: drive; Against input phase loss: drive; Thermal protection: motor; Motor phase break: motor; With PTC probes: motor
Width310 mm
Height665 mm
Depth315 mm
Net weight45 kg
Contractual warranty
Warranty (in months)18
Environment
Pollution degree2 conforming to IEC 61800-5-1
Vibration resistance1.5 mm (f= 3…13 Hz) conforming to IEC 60068-2-6; 1 gn (f= 13…200 Hz) conforming to EN/IEC 60068-2-8
Shock resistance15 gn for 11 ms conforming to IEC 60068-2-27
Environmental characteristicClasses 3C1 conforming to IEC 60721-3-3; Classes 3S2 conforming to IEC 60721-3-3
Noise level60.2 dB conforming to 86/188/EEC
Operating altitude1000...3000 m limited to 2000 m for the Corner Grounded distribution network with current derating 1 % per 100 m;
Relative humidity5…95 % without condensation conforming to IEC 60068-2-3; 5…95 % without dripping water conforming to IEC 60068-2-3
Ambient air temperature for operation-10…40 °C (without derating); 40…50 °C (with derating factor)
Operating positionVertical +/- 10 degree
Product certificationsUL; NOM 117; CSA; C-Tick
MarkingCE
Assembly styleWith heat sink
Electromagnetic compatibilityElectrostatic discharge immunity test level 3 conforming to IEC 61000-4-2; Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3; Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4; 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5; Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6; Voltage dips and interruptions immunity test conforming to IEC 61000-4-11
Regulation loopAdjustable PI regulator
Ambient air temperature for storage-25…70 °C
Logistical informations
Country of originFR
Main
Device short nameATV212
Product destinationAsynchronous motors
Network number of phases3 phases
Motor power kW18.5 kW
Motor power hp25 hp
Supply voltage limits323…528 V
Supply frequency50...60 Hz - 5...5 %
Line current27.6 A at 480 V; 34.5 A at 380 V
Range of productAltivar 212
Product or component typeVariable speed drive
Product specific applicationPumps and fans in HVAC
Communication port protocolMETASYS N2; LonWorks; Modbus; APOGEE FLN; BACnet
[Us] rated supply voltage380...480 V - 15...10 %
EMC filterClass C1 EMC filter integrated
IP degree of protectionIP55
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height39.000 cm
Package 1 Width40.000 cm
Package 1 Length80.000 cm
Package 1 Weight45.000 kg
Ausrichtung auf Zentralisiertes Technisches Management - Sofortiger Überblick über den Energieverbrauch. Störungserkennung und zeitnahe Eingriffsmöglichkeiten: Antriebsriehmenbruch, Trockenlaufen der Pumpe, Phasenausfall, Versorgungsausfall usw. Vorbeugende Wartung zur Kostenminimierung und Anlagenoptimierung: Störungshinweise, Betriebszeiten usw. Anbindung an Gebäude -Managementsysteme über eingebettete Protokolle. Ausrichtung auf Benutzerfreundlichkeit - Tools zur Installation, Konfiguration und Überwachung der Anlage (dezentrales Grafikterminal in 6 Sprachen, Multi -Loader, Bluetooth und SoMove Mobile). Kompakte Bauweise. Einfache Wartung. Ausrichtung auf Schutzfunktionen - Garantierte Dauerbetriebssicherheit. Fest integrierte Gebäude funktionen (Brandschutzmodus, Registerüberwachung, mechanische Schutzfunktion usw. Integrierte EMV -Filter, Oberwellenschutztechnik (THDI ~ 30%).
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/953489
qrcode für Schneider Electric ATV212WD18N4C frequency converter 18.5 kW IP54