| Complementary |
| Discrete input number | 4 |
| Discrete output number | 2 |
| Analogue input number | 1 |
| Analogue output number | 1 |
| Relay output number | 1 |
| Physical interface | 2-wire RS 485 |
| Connector type | 1 RJ45 |
| Continuous output current | 2.4 A at 4 kHz |
| Method of access | Server Modbus serial |
| Speed drive output frequency | 0.5…400 Hz |
| Speed range | 1…20 |
| Sampling duration | 20 ms, tolerance +/- 1 ms for logic input; 10 ms for analogue input |
| Linearity error | +/- 0.3 % of maximum value for analogue input |
| Frequency resolution | Analog input: converter A/D, 10 bits; Display unit: 0.1 Hz |
| Time constant | 20 ms +/- 1 ms for reference change |
| Transmission rate | 9.6 kbit/s; 19.2 kbit/s; 38.4 kbit/s |
| Transmission frame | RTU |
| Number of addresses | 1…247 |
| Data format | 8 bits, configurable odd, even or no parity |
| Communication service | Read holding registers (03) 29 words; Write single register (06) 29 words; Write multiple registers (16) 27 words; Read/write multiple registers (23) 4/4 words; Read device identification (43) |
| Type of polarization | No impedance |
| 4 quadrant operation possible | False |
| Asynchronous motor control profile | Sensorless flux vector control; Voltage/frequency ratio (V/f); Quadratic voltage/frequency ratio |
| Maximum output frequency | 4 kHz |
| Transient overtorque | 150…170 % of nominal motor torque depending on drive rating and type of motor |
| Acceleration and deceleration ramps | Linear from 0 to 999.9 s; S; U |
| Motor slip compensation | Adjustable; Preset in factory |
| Switching frequency | 2...16 kHz adjustable; 4...16 kHz with derating factor |
| Nominal switching frequency | 4 kHz |
| Braking to standstill | By DC injection |
| Brake chopper integrated | False |
| Line current | 5.9 A at 100 V (heavy duty); 4.9 A at 120 V (heavy duty) |
| Maximum input current | 4.9 A |
| Maximum output voltage | 240 V |
| Apparent power | 1.2 kVA at 240 V (heavy duty) |
| Maximum transient current | 3.6 A during 60 s (heavy duty); 4.0 A during 2 s (heavy duty) |
| Network frequency | 50...60 Hz |
| Relative symmetric network frequency tolerance | 5 % |
| Prospective line Isc | 1 kA |
| Base load current at high overload | 2.4 A |
| Power dissipation in W | Natural: 27.0 W |
| With safety function Safely Limited Speed (SLS) | False |
| With safety function Safe brake management (SBC/SBT) | False |
| With safety function Safe Operating Stop (SOS) | False |
| With safety function Safe Position (SP) | False |
| With safety function Safe programmable logic | False |
| With safety function Safe Speed Monitor (SSM) | False |
| With safety function Safe Stop 1 (SS1) | False |
| With sft fct Safe Stop 2 (SS2) | False |
| With safety function Safe torque off (STO) | False |
| With safety function Safely Limited Position (SLP) | False |
| With safety function Safe Direction (SDI) | False |
| Protection type | Line supply overvoltage; Line supply undervoltage; Overcurrent between output phases and earth; Overheating protection; Short-circuit between motor phases; Against input phase loss in three-phase; Thermal motor protection via the drive by continuous calculation of I²t |
| Tightening torque | 0.8 N.m |
| Insulation | Electrical between power and control |
| Quantity per set | Set of 1 |
| Width | 72 mm |
| Height | 143 mm |
| Depth | 121.2 mm |
| Net weight | 0.7 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Operating altitude | > 1000...2000 m with current derating 1 % per 100 m; |
| Operating position | Vertical +/- 10 degree |
| Product certifications | NOM; CSA; C-Tick; UL; GOST; RCM; KC |
| Marking | CE |
| Standards | UL 508C; UL 618000-5-1; IEC 61800-5-1; IEC 61800-3 |
| Assembly style | With heat sink |
| Electromagnetic compatibility | Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4; Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2; Immunity to conducted disturbances level 3 conforming to IEC 61000-4-6; Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3; Surge immunity test level 3 conforming to IEC 61000-4-5; Voltage dips and interruptions immunity test conforming to IEC 61000-4-11 |
| Environmental class (during operation) | Class 3C3 according to IEC 60721-3-3; Class 3S2 according to IEC 60721-3-3 |
| Maximum acceleration under shock impact (during operation) | 150 m/s² at 11 ms |
| Maximum acceleration under vibrational stress (during operation) | 10 m/s² at 13...200 Hz |
| Maximum deflection under vibratory load (during operation) | 1.5 mm at 2...13 Hz |
| Overvoltage category | Class III |
| Regulation loop | Adjustable PID regulator |
| Electromagnetic emission | Radiated emissions environment 1 category C2 conforming to IEC 61800-3 2...16 kHz shielded motor cable; Conducted emissions with integrated EMC filter environment 1 category C1 conforming to IEC 61800-3 2, 4, 8, 12 and 16 kHz shielded motor cable |
| Vibration resistance | 1 gn (f = 13…200 Hz) conforming to IEC 60068-2-6; 1.5 mm peak to peak (f = 3…13 Hz) - drive unmounted on symmetrical DIN rail - conforming to IEC 60068-2-6 |
| Shock resistance | 15 gn conforming to IEC 60068-2-27 for 11 ms |
| Relative humidity | 5…95 % without condensation conforming to IEC 60068-2-3; 5…95 % without dripping water conforming to IEC 60068-2-3 |
| Noise level | 0 dB |
| Pollution degree | 2 |
| Ambient air transport temperature | -25…70 °C |
| Ambient air temperature for operation | -10…40 °C without derating; 40…60 °C with current derating 2.2 % per °C |
| Ambient air temperature for storage | -25…70 °C |
| Logistical informations |
| Country of origin | ID |
| Main |
| Range of product | Altivar 12 |
| Product or component type | Variable speed drive |
| Product specific application | Simple machine |
| Mounting mode | Cabinet mount |
| Communication port protocol | Modbus |
| Supply frequency | 50/60 Hz +/- 5 % |
| [Us] rated supply voltage | 200...240 V - 15...10 % |
| nominal output current | 2.4 A |
| Motor power kW | 0.37 kW |
| Motor power hp | 0.55 hp |
| EMC filter | Integrated |
| IP degree of protection | IP20 |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 11.500 cm |
| Package 1 Width | 20.000 cm |
| Package 1 Length | 18.700 cm |
| Package 1 Weight | 1.052 kg |
| Unit Type of Package 2 | S06 |
| Number of Units in Package 2 | 45 |
| Package 2 Height | 75.000 cm |
| Package 2 Width | 60.000 cm |
| Package 2 Length | 80.000 cm |
| Package 2 Weight | 59.530 kg |
The ATV12H037M2 frequency converter from Schneider Electric belongs to the Altivar 12 series and is a variable speed drive specifically designed for use in simple industrial machines as well as in certain machines in the consumer goods sector. It features a motor power of 0.37 kW (0.55 hp) and is designed for a supply voltage of 200 to 240 V single-phase at a frequency of 50/60 Hz. The compact design with integrated heatsink allows for installation in an enclosure and easy setup following the Plug & Drive principle. Factory pre-set, the converter can be put into operation immediately without requiring extensive commissioning.
The ATV12H037M2 is designed for applications in simple machines where precise speed control is required. It is suitable for applications such as conveyor systems, pumps, fans, or small machine tools. The robust construction ensures reliable operation even under demanding environmental conditions, including continuous operation at ambient temperatures up to 50 °C.
The converter provides a rated output current of 2.4 A and a maximum output voltage of 240 V. The output frequency of the speed controller can be set between 0.5 and 400 Hz, with a speed control range of 1 to 20 enabling flexible adaptation to different drive requirements. The acceleration and deceleration ramps are linearly adjustable and can be configured between 0 and 999.9 seconds. Motor slip compensation is factory-set and can be adjusted according to application needs. Braking is achieved via DC injection, with no integrated brake chopper.
The converter operates with vector-oriented flux control without a sensor, as well as in voltage/frequency mode (U/f) with a quadratic characteristic curve. The switching frequency is adjustable between 2 and 16 kHz, with power derating required at frequencies from 4 to 16 kHz. The rated switching frequency is 4 kHz. The integrated EMC filtering ensures low electromagnetic emission and enhances compatibility in industrial environments. The protection class IP20 protects against contact with fingers and vertical dripping water, but not against dust or splashing water.
The ATV12H037M2 features a serial interface with 2-wire RS485 and an RJ45 connector. Communication is via the Modbus protocol with a transmission speed of 9.6, 19.2, or 38.4 Kbit/s in RTU format. Access is via a Modbus server. For configuration and commissioning, various tools are available, including the SoMove software, SoMove Mobile, decentralized terminals, and configuration tools such as Simple-Loader and Multi-Loader. Configuration can also be saved and loaded in de-energized state using the Multi-Loader, without removing the device from its packaging. Suitable accessories include power contactors from the LC1K series, line reactors (e.g. VW3-A4551), motor protection circuit breakers (e.g. GV2ME14), and EMC connection plates (e.g. VW3A9523).
Mounting is in an enclosure, with vertical mounting suitable for ambient temperatures up to 50 °C. Installation requires qualified personnel familiar with safety regulations and the operating instructions. Before commissioning, it must be ensured that the supply voltage is compatible with the converter’s voltage range. Work on the device must only be carried out when de-energized and after proper discharge of the DC bus capacitors.
The ATV12H037M2 is characterized by high operational reliability and easy handling. The integrated functions and factory pre-settings reduce commissioning time. The ability to save and load configurations in de-energized state simplifies maintenance and replacement. The robust design and capability to operate continuously at 50 °C make the converter suitable for demanding industrial applications. Communication via Modbus enables integration into higher-level control systems.