| Complementary |
| Device connection | In line |
| Overload current | 400 % Ie for 13 s |
| On-load factor | 50 % |
| Operating cycles/hour | 10 cyc/h |
| [Us] control circuit voltage | 110...230 V AC 50...60 Hz - 15...10 % |
| Apparent power | 70 VA |
| Integrated motor overload protection | True |
| motor thermal protection class | Class 10E |
| Protection type | Phase failure: mains; Thermal protection: mains; Thermal protection: starter; Current overload: motor; Motor underload: motor; Excessive acceleration time: motor; Motor phase loss detection: motor; Protection against line phase inversion: mains; External thermal protection: motor; Short-circuit between motor phase and earth: motor |
| current limiting %In (5 x Ie maximum) | 150…700 % |
| Rated current pwr loss specification | 590 A |
| Power loss static current independent | 19 W |
| Power loss per device current dependent | 122 W |
| Power loss during starting | 5655 W during starting at 40 °C at 400% In |
| Standards | EN/IEC 60947-4-2; UL 60947-4-2; IEC 60664-1 |
| Product certifications | cULus; CE; UKCA; CCC; RCM; EAC; KC |
| Marking | CULus; CE; UKCA; CCC; RCM; EAC; KC |
| [Uc] control circuit voltage | 24 V DC |
| Discrete input number | 4 |
| Discrete input type | (STOP) digital input, 4.4 kOhm; (RUN) digital input, 4.4 kOhm; (DI3) digital input, 4.4 kOhm; (DI4) digital input, 4.4 kOhm |
| Input compatibility | STOP: digital input level 1 PLC conforming to EN/IEC 61131-2; RUN: digital input level 1 PLC conforming to EN/IEC 61131-2; DI3: digital input level 1 PLC conforming to EN/IEC 61131-2; DI4: digital input level 1 PLC conforming to EN/IEC 61131-2 |
| Discrete input logic | Digital input STOP at State 0: 0...< 5 V and 11 V, >= 5 mA; Digital input RUN at State 0: 0...< 5 V and 11 V, >= 5 mA; Digital input DI3 at State 0: 0...< 5 V and 11 V, >= 5 mA; Digital input DI4 at State 0: 0...< 5 V and 11 V, >= 5 mA |
| Relay output number | 2 |
| Relay output type | Relay outputs R1A, R1C NO; Relay outputs R1B, R1C NC; Relay outputs R2A, R2C NO |
| Minimum switching current | 100 mA at 12 V DC for relay outputs |
| Maximum switching current | Relay outputs 2 A / 250 V AC for AC-15 100000 cycles following IEC 60947-5-1; Relay outputs 2 A / 30 V DC for DC-13 150000 cycles following IEC 60947-5-1 |
| Analogue input number | 1 |
| Analogue input type | PTC1 : PTC temperature probe; PTC2 : PTC temperature probe |
| Analogue output number | 1 |
| Analogue output type | Current output AQ1 : 0...20 mA/4...20 mA , impedance< 500 Ohm; Voltage output AQ1 : 0...10 V , impedance> 470 Ohm |
| Connector type | 1 RJ45; Open style |
| Physical interface | 2-wire RS 485 - connector(s): RJ45; 2-wire RS 485 - connector(s): open style (DO, D1, PE, COM) |
| Transmission frame | RTU : 1 RJ45; RTU : open style (DO, D1, PE, COM) |
| Transmission rate | 4.8…38.4 kbps for Modbus serial RJ45; 0.3...115.2 kbps for Modbus serial open style (DO, D1, PE, COM) |
| Data format | 8 bits, odd, even or no parity, 1 or 2 bits to stop for Modbus serial RJ45; 8 bits, configurable odd, even or no parity for Modbus serial open style (DO, D1, PE, COM) |
| Number of addresses | 0…247 for Modbus serial |
| Method of access | Slave Modbus serial |
| Type of polarization | No impedance for Modbus serial |
| Display screen available | True |
| Operating position | Vertical +/- 10 degree |
| Height | 455 mm |
| Width | 304 mm |
| Depth | 296.5 mm |
| Net weight | 24.50 kg |
| internal bypass | True |
| Function available | Single direction; Pre-heating; Power monitoring; Condition monitoring; User management; Ports and services hardening; Security event logging; Cybersecure firmware update; Small motor test |
| material declaration | True |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Electromagnetic compatibility | Conducted and radiated emissions level A conforming to IEC 60947-4-2; Electrostatic discharge level 3 conforming to IEC 61000-4-2; Immunity to radiated radio-electrical interference level 3 conforming to IEC 61000-4-3; Immunity to electrical transients level 4 conforming to IEC 61000-4-4; Voltage/current impulse level 3 conforming to IEC 61000-4-5; Damped oscillating waves level 3 conforming to IEC 61000-4-18; Immunity to conducted disturbances radio-frequency level 3 conforming to IEC 61000-4-6 |
| Pollution degree | Level 3 |
| [Uimp] rated impulse withstand voltage | 6 kV |
| [Ui] rated insulation voltage | 600 V |
| Environmental class (during operation) | Class 3C3 according to IEC 60721-3-3; Class 3S3 according to IEC 60721-3-3 |
| Ambient air temperature for operation | -25…40 °C (without derating); 40…60 °C (with current derating of 1 % per °C above 40 °C) |
| Ambient air temperature for storage | -40…70 °C |
| Ambient air transport temperature | -40…70 °C |
| Operating altitude | 2000...4800 m with current derating 1 % per 100 m above 2000 m |
| Relative humidity | 5…95 % without condensation or dripping water conforming to EN/IEC 60068-2-3 |
| Maximum deflection under vibratory load (during operation) | 1.5 mm at 2...13 Hz |
| Maximum deflection under vibratory load (during storage) | 1.75 mm at 2...9 Hz |
| Maximum deflection under vibratory load (during transport) | 1.75 mm at 2...9 Hz |
| Maximum acceleration under vibrational stress (during operation) | 1 gn at 13…200 Hz |
| Maximum acceleration under vibratory load (during storage) | 1 gn at 9…200 Hz; 1.5 gn at 200…500 Hz |
| Maximum acceleration under vibratory load (during transport) | 1 gn at 9…200 Hz; 1.5 gn at 200…500 Hz |
| Maximum acceleration under shock impact (during operation) | 15 gn at 11 ms |
| Maximum acceleration under shock load (during storage) | 10 gn at 11 ms |
| Maximum acceleration under shock load (during transport) | 10 gn at 11 ms |
| Main |
| Range of product | Altivar Soft Starter ATS430 |
| Product or component type | Soft starter |
| Product destination | Asynchronous motors |
| Product specific application | Standard industrial machines |
| Device short name | ATS430 |
| Network number of phases | 3 phases |
| Utilisation category | AC-3A; AC-53a |
| Ue power supply voltage | 208...600 V AC (- 15...10 %) |
| power supply frequency | 50...60 Hz - 20...20 % |
| [Ie] rated operational current | Normal duty: 590 A in line (at |
| Service factor at Ie | 100 |
| Torque control | True |
| IP degree of protection | IP00 |
| Motor power kW | 160 kW at 230 V in line normal duty; 315 kW at 400 V in line normal duty; 355 kW at 440 V in line normal duty; 400 kW at 500 V in line normal duty; 400 kW at 525 V in line normal duty |
| Motor power hp | 200 hp at 230 V normal duty; 400 hp at 460 V normal duty; 500 hp at 575 V normal duty |
| Communication port protocol | Modbus serial |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 53.000 cm |
| Package 1 Width | 40.000 cm |
| Package 1 Length | 60.000 cm |
| Package 1 Weight | 32.500 kg |