| Complementary |
| Assembly style | With heat sink |
| Function available | Internal bypass |
| Supply voltage limits | 195…484 V |
| Supply frequency | 50...60 Hz - 10...10 % |
| Network frequency | 45...66 Hz |
| Device connection | To the motor delta terminals; In the motor supply line |
| [Uc] control circuit voltage | 230 V - 15...10 % 50/60 Hz |
| Control circuit consumption | 20 W |
| Discrete output number | 2 |
| Discrete output type | Relay outputs R1 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O; Relay outputs R2 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O |
| Minimum switching current | 100 mA at 12 V DC (relay outputs) |
| Maximum switching current | 5 A 250 V AC resistive 1 relay outputs; 5 A 30 V DC resistive 1 relay outputs; 2 A 250 V AC inductive 0.4 20 ms relay outputs; 2 A 30 V DC inductive 7 ms relay outputs |
| Discrete input number | 3 |
| Discrete input type | (LI1, LI2, LI3) logic, 5 mA 4.3 kOhm |
| Discrete input voltage | 24 V |
| Discrete input logic | Positive logic LI1, LI2, LI3 at State 0: < 5 V and 11 V, >= 5 mA |
| Output current | 0.4...1 Icl adjustable |
| PTC probe input | 750 Ohm |
| Communication port protocol | Modbus |
| Connector type | 1 RJ45 |
| Communication data link | Serial |
| Physical interface | RS485 multidrop |
| Transmission rate | 4800, 9600 or 19200 bps |
| Installed device | 31 |
| Protection type | Phase failure: line; Thermal protection: motor; Thermal protection: starter |
| Marking | CE |
| Type of cooling | Forced convection |
| Operating position | Vertical +/- 10 degree |
| Height | 295 mm |
| Width | 145 mm |
| Depth | 207 mm |
| Net weight | 12 kg |
| Motor power range AC-3 | 15…25 kW at 200…240 V 3 phases; 30…50 kW at 380…440 V 3 phases |
| Motor starter type | Soft starter |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Electromagnetic compatibility | Conducted and radiated emissions level A conforming to IEC 60947-4-2; Damped oscillating waves level 3 conforming to IEC 61000-4-12; Electrostatic discharge level 3 conforming to IEC 61000-4-2; Immunity to electrical transients level 4 conforming to IEC 61000-4-4; Immunity to radiated radio-electrical interference level 3 conforming to IEC 61000-4-3; Voltage/current impulse level 3 conforming to IEC 61000-4-5 |
| Standards | IEC 60947-4-2 |
| Product certifications | CCC; CSA; UL; GOST; C-Tick |
| Vibration resistance | 1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6; 1.5 mm (f= 2…13 Hz) conforming to IEC 60068-2-6 |
| Shock resistance | 15 gn for 11 ms conforming to IEC 60068-2-27 |
| Noise level | 45 dB |
| Pollution degree | Level 2 conforming to IEC 60664-1 |
| Relative humidity | 0…95 % without condensation or dripping water conforming to IEC 60068-2-3 |
| Ambient air temperature for operation | -10…40 °C (without derating); 40…60 °C (with current derating 2.2 % per °C) |
| Ambient air temperature for storage | -25…70 °C |
| Operating altitude | 1000...< 2000 m with current derating of 2.2 % per additional 100 m |
| Logistical informations |
| Country of origin | ID |
| Main |
| Range of product | Altistart 22 |
| Product or component type | Soft starter |
| Product destination | Asynchronous motors |
| Product specific application | Pumps and fans |
| Component name | ATS22 |
| Network number of phases | 3 phases |
| [Us] rated supply voltage | 230...440 V - 15...10 % |
| Motor power kW | 22 kW 230 V; 45 kW 400 V; 45 kW 440 V |
| Factory setting current | 81 A |
| Power dissipation in W | 66 W for standard applications |
| Utilisation category | AC-53A |
| Type of start | Start with torque control (current limited to 3.5 In) |
| IcL starter rating | 88 A for connection in the motor supply line for standard applications |
| IP degree of protection | IP20 |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 23.000 cm |
| Package 1 Width | 30.800 cm |
| Package 1 Length | 35.800 cm |
| Package 1 Weight | 8.170 kg |
| Unit Type of Package 2 | P06 |
| Number of Units in Package 2 | 6 |
| Package 2 Height | 75.000 cm |
| Package 2 Width | 60.000 cm |
| Package 2 Length | 80.000 cm |
| Package 2 Weight | 63.184 kg |
Starter, ATS22, control voltage 230V, rated current 88A 440V. Product range: Altistart 22 - Product or component type: Soft starters - Application: asynchronous motors - product-specific application: Applications under normal and difficult ambient conditions - Component name: ATS22 - Number of mains phases: 3 phases - Motor Power (kW): 22 kW at 230 V, 45 kW at 400 V, 45 kW at 440 V - factory setting current: 81 A - Use category: AC-53A - Startup type: Start with speed control (on 3.5 In limited current). Your benefit: starter 17-590 A. The new Altistart 22 offers: - Space saving because of the built-in bypass contactor - Easy wiring - protect your electrical system - reducing your operating costs .. Applications: - Pumps - Fans - Compressors - conveyor. .