| Complementary |
| Assembly style | With heat sink |
| Function available | Internal bypass |
| Supply voltage limits | 177…660 V |
| Supply frequency | 50...60 Hz - 10...10 % |
| Network frequency | 45...66 Hz |
| Device connection | In the motor supply line |
| [Uc] control circuit voltage | 110 V - 15...10 % 50/60 Hz |
| Control circuit consumption | 20 W |
| Discrete output number | 2 |
| Discrete output type | Relay outputs R1 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O; Relay outputs R2 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O |
| Minimum switching current | 100 mA at 12 V DC (relay outputs) |
| Maximum switching current | 5 A 250 V AC resistive 1 relay outputs; 5 A 30 V DC resistive 1 relay outputs; 2 A 250 V AC inductive 0.4 20 ms relay outputs; 2 A 30 V DC inductive 7 ms relay outputs |
| Discrete input number | 3 |
| Discrete input type | (LI1, LI2, LI3) logic, 5 mA 20 kOhm |
| Discrete input voltage | 110 V |
| Discrete input logic | Positive logic LI1, LI2, LI3 at State 0: < 20 V and 79 V |
| Output current | 0.4...1 Icl adjustable |
| PTC probe input | 750 Ohm |
| Communication port protocol | Modbus |
| Connector type | 1 RJ45 |
| Communication data link | Serial |
| Physical interface | RS485 multidrop |
| Transmission rate | 4800, 9600 or 19200 bps |
| Installed device | 31 |
| Protection type | Phase failure: line; Thermal protection: motor; Thermal protection: starter |
| Marking | CE |
| Type of cooling | Forced convection |
| Operating position | Vertical +/- 10 degree |
| Height | 455 mm |
| Width | 304 mm |
| Depth | 339.7 mm |
| Net weight | 50 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Electromagnetic compatibility | Conducted and radiated emissions level A conforming to IEC 60947-4-2; Damped oscillating waves level 3 conforming to IEC 61000-4-12; Electrostatic discharge level 3 conforming to IEC 61000-4-2; Immunity to electrical transients level 4 conforming to IEC 61000-4-4; Immunity to radiated radio-electrical interference level 3 conforming to IEC 61000-4-3; Voltage/current impulse level 3 conforming to IEC 61000-4-5 |
| Standards | IEC 60947-4-2 |
| Product certifications | C-Tick; CCC; UL; CSA; GOST |
| Vibration resistance | 1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6; 1.5 mm (f= 2…13 Hz) conforming to IEC 60068-2-6 |
| Shock resistance | 15 gn for 11 ms conforming to IEC 60068-2-27 |
| Noise level | 56 dB |
| Pollution degree | Level 2 conforming to IEC 60664-1 |
| Relative humidity | 0…95 % without condensation or dripping water conforming to IEC 60068-2-3 |
| Ambient air temperature for operation | -10…40 °C (without derating); 40…60 °C (with current derating 2.2 % per °C) |
| Ambient air temperature for storage | -25…70 °C |
| Operating altitude | 1000...< 2000 m with current derating of 2.2 % per additional 100 m |
| Logistical informations |
| Country of origin | CN |
| Main |
| Range of product | Altistart 22 |
| Product or component type | Soft starter |
| Product destination | Asynchronous motors |
| Product specific application | Pumps and fans |
| Component name | ATS22 |
| Network number of phases | 3 phases |
| [Us] rated supply voltage | 208...600 V - 15...10 % |
| Motor power hp | 150 hp 208 V; 350 hp 460 V; 400 hp 575 V |
| Factory setting current | 414 A |
| Power dissipation in W | 218 W for standard applications |
| Utilisation category | AC-53a |
| Type of start | Start with torque control (current limited to 3.5 In) |
| IcL starter rating | 480 A for connection in the motor supply line for standard applications |
| IP degree of protection | IP00 |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 50.0 cm |
| Package 1 Width | 40.0 cm |
| Package 1 Length | 60.0 cm |
| Package 1 Weight | 39.25 kg |
This Altistart 22 soft starter can power three-phase asynchronous motors in mains connection with a power of 480 amps, a rated power of 150 to 400 HP and a rated voltage of 230 to 575VAC. This soft start/soft stop unit is designed to enable smooth starting and stopping of simple and complex machines such as centrifugal and piston pumps, fans, screw compressors and conveyors. It has a PTC thermal probe input to detect motor overheating as well as several other motor monitoring functions. It also offers an integrated bypass and is compatible with SoMove software, which allows the saving and transfer of configuration settings.