| Complementary |
| Overload current profile | 300 % Ie for 5 s |
| On-load factor | 70 % |
| Operating cycles/hour | 13 cyc/h |
| Minimum motor current | 20 % Ie |
| Device connection | In line |
| [Us] control circuit voltage | 24 V DC +/- 10 % |
| Control power | 21.6 W starting and stopping; 3 W steady state |
| Integrated motor overload protection | False |
| Protection type | Phase failure: mains; Thermal protection: starter; Bypass error: starter; Control voltage Us: starter |
| Rated current pwr loss specification | 65 A |
| Power loss static current independent | 3 W |
| Power loss per device current dependent | 16 W |
| Power loss during starting | 397 W 300 % Ie |
| Standards | EN/IEC 60947-4-2; UL 60947-4-2; IEC 60664-1 |
| Product certifications | CE; UKCA; CCC; RCM; EAC; UL |
| Marking | CE; CCC; UKCA; RCM; EAC |
| [Uc] control circuit voltage | 24 V DC |
| Discrete input number | 3 |
| Discrete input type | (DI) digital input, 10 kOhm; (DI2) digital input, 10 kOhm; (BOOST) digital input, 10 kOhm |
| Input compatibility | Discrete input level 1 PLC conforming to EN/IEC 61131-2 |
| Discrete input logic | Digital input at State 0: 0...< 5 V and 13 V, >= 0.5 mA |
| Relay output number | 1 |
| Relay output type | Relay outputs R1A, R1C NO |
| Minimum switching current | 2.5 mA at 24 V DC for relay outputs |
| Maximum switching current | On resistive load for relay outputs : 1 A 250 V AC 400000 cycles; On resistive load for relay outputs : 1 A 30 V DC 400000 cycles; On inductive load for relay outputs : 1 A 250 V AC cos phi = 0.4 100000 cycles; On inductive load for relay outputs : 1 A 30 V DC cos phi = 0.4 100000 cycles |
| Discrete output number | 1 |
| Discrete output type | Non programmable digital output DQ1 |
| Display type | 1 LED (green) for control power energized; 1 LED (yellow and red) for motor operation phases, errors |
| Display screen available | False |
| Operating position | Vertical +/- 30 degree |
| Height | 166 mm |
| Width | 55 mm |
| Depth | 165 mm |
| Net weight | 1.3 kg |
| Suitable for mounting onto standard rails | True |
| Function available | Deceleration voltage ramp; Boost |
| internal bypass | True |
| material declaration | True |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Pollution degree | Level 2 |
| environmental class (during operation) | Without salt mist: 3C3 conforming to IEC 60721-3-3; 3S3 conforming to IEC 60721-3-3 |
| [Uimp] rated impulse withstand voltage | 4 kV |
| [Ui] rated insulation voltage | 480 V |
| Ambient air temperature for operation | -10…40 °C (without derating); 40…60 °C (with current derating 1.5 % per °C) |
| Ambient air temperature for storage | -25…70 °C |
| Ambient air transport temperature | -40…70 °C |
| Operating altitude | 0...1000 m without derating; 1000...4000 m 1 % per 100 m |
| Relative humidity | 5…95 % non condensing without dripping water conforming to IEC 60068-2-3 |
| Maximum acceleration under vibrational stress (during operation) | 10 m/s² at 9...200 Hz |
| Maximum acceleration under vibratory load (during storage) | 10 m/s² at 9...200 Hz |
| Maximum acceleration under vibratory load (during transport) | 10 m/s² at 9...200 Hz |
| Maximum deflection under vibratory load (during operation) | 3 mm at 2-9 Hz |
| Maximum deflection under vibratory load (during storage) | 3 mm at 2-9 Hz |
| Maximum deflection under vibratory load (during transport) | 3 mm at 2-9 Hz |
| Maximum acceleration under shock impact (during operation) | 100 m/s² at 11 ms |
| Maximum acceleration under shock load (during storage) | 100 m/s² at 11 ms |
| Maximum acceleration under shock load (during transport) | 100 m/s² at 11 ms |
| Logistical informations |
| Country of origin | DE |
| Main |
| Range of product | Altivar Soft Starter ATS130 |
| Product or component type | Soft starter |
| Product destination | Asynchronous motors |
| Product specific application | Simple machine |
| Device short name | ATS130 |
| Network number of phases | 3 phases |
| Utilisation category | AC-53A |
| Ue power supply voltage | 200...480 V - 15...10 % |
| power supply frequency | 50...60 Hz +/- 5 Hz |
| [Ie] rated operational current | 65 A in line (at |
| Service factor at Ie | 100 |
| Torque control | False |
| IP degree of protection | IP20 |
| Motor power kW | 18.5 kW at 230 V normal duty; 30 kW at 400 V normal duty; 37 kW at 440 V normal duty |
| Motor power hp | 20 hp at 200 V normal duty; 20 hp at 208 V normal duty; 20 hp at 230 V normal duty; 40 hp at 460 V normal duty; 50 hp at 480 V normal duty |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 6.000 cm |
| Package 1 Width | 27.000 cm |
| Package 1 Length | 27.500 cm |
| Package 1 Weight | 1.510 kg |
| Unit Type of Package 2 | S06 |
| Number of Units in Package 2 | 40 |
| Package 2 Height | 75.000 cm |
| Package 2 Width | 60.000 cm |
| Package 2 Length | 80.000 cm |
| Package 2 Weight | 69.500 kg |
Dieser Sanftanlasser gehört zur Reihe Altivar ATS130 Sanftanlasser, die für das Starten und Stoppen von Asynchronmotoren mit Spannungen von 200 bis 480 V vorgesehen sind. Mit einem Betriebsnennstrom von 65A unter Normallast versorgt er je nach Netzspannung Motoren von 18,5 bis 37kW. Das kompakte Design bietet mechanische und elektrische Flexibilität bei der Konstruktion von Schalttafeln. ATS130 ist wartungsfrei und ermöglicht ein optimiertes Motormanagement, insbesondere in Kombination mit dem Motorschutzschalter TeSys Deca. Everlink-Leistungsklemmen und Feder-Steuerklemmen sind standardmäßig enthalten, wodurch ein jährliches Nachziehen der Kabel vermieden wird. Der ATS130 Softstarter hat die gleiche Breite (55mm) wie der TeSys Deca Frame 3 Motorschutzschalter. Die Abmessungen betragen 55 mm (Breite) x 165 mm (Tiefe) x 179 mm (Höhe), und das Gewicht beträgt 1,26 kg. Der Altivar Sanftanlasser ATS130 ist für Pumpen, Lüfter, Kompressoren, Förderanlagen und andere einfache Maschinen konzipiert. Der Sanftanlasser entspricht der Norm IEC/EN60947-4-1 und hat die Zertifizierungen CE, cULus, UKCA, CCC und RCM erhalten. Es ist möglich, einen Befestigungssatz für die Montage des Motorschutzschalters TeSys Deca frame 3 oder einen Lüfter hinzuzufügen, um die Anzahl der Starts pro Stunde zu erhöhen. Mehrere Sanftanlasser ATS130 können nebeneinander auf einer Rückwand oder auf einer DIN-Schiene montiert werden und sind mit einer Schranktiefe von 200 mm kompatibel. Der Altivar Sanftanlasser ATS130 ist wartungsfrei und erhöht die Betriebseffizienz während der Entwicklung, Fertigung und Inbetriebnahme.