| Complementary |
| Assembly style | With heat sink |
| Function available | Integrated bypass |
| Supply voltage limits | 99…528 V |
| Supply frequency | 50...60 Hz - 5...5 % |
| Network frequency | 47.5...63 Hz |
| [Uc] Control circuit voltage | 110 V AC +/- 10 % at 30 mA; 24 V AC/DC +/- 10 % at 25 mA; 240 V AC +/- 10 % at 65 mA |
| Starting time | 1 s / 100; 5 s / 20; Adjustable from 1 to 5 s |
| Starting torque | 30...80 % of starting torque of motor connected directly on the line supply |
| Discrete output current | 2 A DC-13; 3 A AC-15 |
| Tightening torque | 0.8 N.m |
| Marking | CE |
| Operating position | Vertical +/- 10 degree |
| Height | 100 mm |
| Width | 23 mm |
| Depth | 100 mm |
| Net weight | 0.16 kg |
| Compatibility code | ATS01N1 |
| Power range | 0.55…1 kW at 200…240 V 3 phases; 1.1…2 kW at 380…440 V 3 phases; 0.55…1 kW at 200…240 V 1 phase; 1.1…2 kW at 200…240 V 3 phases; 2.2…3 kW at 380…440 V 3 phases |
| Motor starter type | Soft starter |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | EN/IEC 60947-4-2 |
| Product certifications | C-Tick; CCC; CSA; UL; GOST |
| IP degree of protection | IP20 |
| Pollution degree | 2 conforming to EN/IEC 60947-4-2 |
| Vibration resistance | 1 gn (f= 13…150 Hz) conforming to EN/IEC 60068-2-6; 1.5 mm peak to peak (f= 3…13 Hz) conforming to EN/IEC 60068-2-6 |
| Shock resistance | 15 gn for 11 ms conforming to EN/IEC 60068-2-27 |
| Relative humidity | 5…95 % without condensation or dripping water conforming to EN/IEC 60068-2-3 |
| Ambient air temperature for operation | -10…40 °C (without derating); 40…50 °C (with current derating of 2 % per °C) |
| Ambient air temperature for storage | -25…70 °C conforming to EN/IEC 60947-4-2 |
| Operating altitude | 1000 m with current derating of 2.2 % per additional 100 m |
| Logistical informations |
| Country of origin | DE |
| Main |
| Range of product | Altistart 01 |
| Product destination | Asynchronous motors |
| Product or component type | Soft starter |
| Product specific application | Simple machine |
| Device short name | ATS01 |
| Network number of phases | 1 phase |
| [Us] rated supply voltage | 110...480 V - 10...10 % |
| Motor power kW | 3 kW, 3 phases at 400 V; 0.75 kW, 3 phases at 230 V; 1.1 kW, 3 phases at 230 V; 2.2 kW, 3 phases at 400 V; 0.75 kW, 1 phase at 230 V |
| Motor power hp | 1 hp, 3 phases at 230 V; 2 hp, 3 phases at 460 V; 3 hp, 3 phases at 460 V; 0.5 hp, 3 phases at 210 V; 1.5 hp, 3 phases at 230 V |
| IcL starter rating | 6 A |
| Utilisation category | AC-53B conforming to EN/IEC 60947-4-2 |
| Current consumption | 30 A at nominal load |
| Type of start | Start with voltage ramp |
| Power dissipation in W | 1 W at full load and at end of starting; 31 W in transient state |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 2.5 cm |
| Package 1 Width | 10.3 cm |
| Package 1 Length | 10.5 cm |
| Package 1 Weight | 178.0 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 36 |
| Package 2 Height | 15.0 cm |
| Package 2 Width | 30.0 cm |
| Package 2 Length | 40.0 cm |
| Package 2 Weight | 6.715 kg |
...12A, 0.37 ... 5.5 kW, Power: 200 .. 480 V 3-phase, single-ph. Activation.
3 ..85A, 45KW ... 0.37, Network: 200 .. 480 V 3-phase, zweiph. Control.
The starter allows the soft start AC motors and prevents current peaks in the startup phase and mechanical load surges. Easy start, By-pass integrated, optional alarm outputs or control voltage internally or externally, boost function for high starting torque. Altistart 01 soft start 110 .. 480 V, 3-phase AC, 50/60 Hz, internal control voltage, single-ph. Driving motor 230 V power: 0.75 kW motor 400 V power: 2.2 kW Rated current IU: 6 A Type: ATS01N106FT