| Additional features |
| Degree of protection | UL Type 1 corresponds to UL 61800-5-1 (control panel integration); UL Type 12 corresponds to UL 61800-5-1 (control panel integration) |
| Potential line Isc | 50 kA |
| Apparent power | 223 kVA at 380 - 480 V normal operation; 181 kVA at 380 - 480 V heavy-duty operation |
| Continuous output current | 302 A at 2.5 kHz for normal operation; 250 A at 2.5 kHz for heavy-duty operation |
| Clock frequency | 2.5 - 8 kHz with derating factor; 2 - 8 kHz adjustable |
| Permissible temporary current increase | 1.1 x In for 60 s (normal operation); 1.5 x In for 60 s (heavy-duty operation) |
| Width | 230 mm |
| Height | 1705 mm |
| Depth | 510 mm |
| Product weight | 155 kg |
| Text | CE |
| Contractual warranty |
| Warranty (in months) | 18 |
| Main features |
| Product series | Altivar Process Modular |
| Device short name | APM |
| Product or component type | Power module |
| Product application | Synchronous motors; asynchronous motors |
| Mounting mode | Mounting in control cabinet |
| Kit composition | 1 power module; 1 power supply; 3 fuse holders; 2 holders with nuts; screws and washers for fuse |
| EMC filter | Integrated with 300 m corresponds to IEC 61800-3 Category C3 |
| Degree of protection (IP) | IP00 corresponds to IEC 61800-5-1; IP21 corresponds to IEC 61800-5-1 (for control cabinet integration); IP54 corresponds to IEC 61800-5-1 (for control cabinet integration) |
| Supply frequency | 50 - 60 Hz -5 - 5 % |
| Number of power phases | 3 phases |
| [UH,nom] Rated operating voltage | 380 - 480 V -10 - +10 % |
| Motor power (kW) | 160 kW at 380 - 480 V (normal operation); 132 kW at 380 - 480 V (heavy-duty operation) |
| Motor power (HP) | 250 hp at 480 V normal operation; 200 hp at 480 V heavy-duty operation |
| Mounting |
| Insulation resistance | > 1 MOhm 500 V DC for 1 minute to ground |
| Operating position | Vertical +/- 10 degrees |
| Electromagnetic compatibility | Electrostatic discharge immunity test Level 3 according to IEC 61000-4-2; Immunity test against radiated high-frequency electromagnetic fields Level 3 according to IEC 61000-4-3; Electrical fast transient burst immunity test Level 4 according to IEC 61000-4-4; 1.2/50 μs - 8/20 μs surge immunity test Level 3 according to IEC 61000-4-5; Conducted radio-frequency electromagnetic field immunity test Level 3 according to IEC 61000-4-6 |
| Pollution degree | 2 corresponds to IEC 61800-5-1 |
| Vibration resistance | 1.5 mm peak to peak (f= 2…13 Hz) complies with IEC 60068-2-6; 0.5 gn (f= 13…200 Hz) complies with IEC 60068-2-6 |
| Shock resistance | 7 gn for 11 ms corresponds to IEC 60068-2-27 |
| Relative humidity | 5…95 % condensation not permitted corresponds to IEC 60068-2-3 |
| Operating ambient temperature | -10…40 °C (without power derating); 40…50 °C (with power derating factor) |
| Ambient temperature during storage | -40…70 °C |
| Operating altitude | = 4,800 m with current reduction over 1000m |
| Environmental properties | Chemical resistance Class 3C3 according to IEC 60721-3-3; Dust resistance Class 3S3 according to IEC 60721-3-3 |
| Standards | IEC 61800-3; IEC 61800-5-1; IEC 61000-3-12; IEC 60721-3; IEC 61508; IEC 13849-1 |
| Product certifications | TÜV; cUL |
| Packaging units |
| VPE 1 type | PCE |
| Number of devices per package | 1 |
| VPE 1 height | 68,000 cm |
| VPE 1 width | 74,000 cm |
| VPE 1 length | 135,000 cm |
| Packaging weight (Lbs) | 185,000 kg |
Standard power supply module, Altivar Process Modular, 110-160 kW, 380-480 V, IP00.