| Complementary |
| Input voltage limits | 85...132 V AC; 170...264 V AC |
| Inrush current | 30 A |
| Power factor | 0.68 at 240 V AC; 0.69 at 120 V AC |
| Efficiency | 88 % |
| Output voltage adjustment | 24...28.8 V adjustable |
| Power dissipation in W | 57.6 W |
| Provided equipment | Power factor correction filter conforming to IEC 61000-3-2 |
| Output protection type | Against overload, protection technology: manual or automatic reset; Against overvoltage, protection technology: 30...32 V, manual reset; Against short-circuits, protection technology: manual or automatic reset; Against undervoltage, protection technology: tripping if U < 21.6 V; Thermal, protection technology: automatic reset |
| Connections - terminals | Removable screw terminal block: 2 x 2.5 mm², for diagnostic relay; Screw type terminals: 3 x 0.5...3 x 4 mm², (22 AWG...12 AWG) for input connection; Screw type terminals: 1 x 0.5...1 x 4 mm², (22 AWG...12 AWG) for input ground connection; Screw type terminals: 4 x 0.5...4 x 4 mm², (22 AWG...12 AWG) for output connection |
| Status LED | 1 LED (green and red) output voltage; 1 LED (green, red and orange) output current |
| Depth | 145 mm |
| Height | 125 mm |
| Width | 146 mm |
| Net weight | 1.6 kg |
| Output coupling | Series; Parallel |
| Marking | CE |
| Mounting support | 35 x 7.5 mm symmetrical DIN rail; 35 x 15 mm symmetrical DIN rail |
| Operating position | Vertical |
| Supply | SELV conforming to IEC 60950-1; SELV conforming to IEC 60204-1; SELV conforming to IEC 60364-4-41 |
| Dielectric strength | 2500 V with between input and ground; 3000 V with between input and output; 500 V with between output and ground |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | CSA C22.2 No 60950-1; UL 508; EN/IEC 62368-1 |
| Product certifications | CCSAus; EAC; KC; RCM; UL |
| Environmental characteristic | EMC conforming to IEC 61000-6-1; EMC conforming to IEC 61000-6-3; EMC conforming to EN 55024; EMC conforming to IEC 61000-6-4; EMC conforming to EN/IEC 61204-3; Safety conforming to IEC 60950-1; Safety conforming to EN/IEC 61204-3 |
| Operating altitude | 2000 m |
| IP degree of protection | IP20 conforming to IEC 60529; IP10 |
| Ambient air temperature for operation | 50…60 °C with derating factor mounting position A < 2000 m; -25…50 °C without derating mounting position A < 2000 m |
| Logistical informations |
| Country of origin | PH |
| Main |
| Range of product | Modicon Power Supply |
| Product or component type | Power supply |
| Power supply type | Regulated switch mode |
| Nominal input voltage | 100...120 V AC single phase, terminal(s): N-L1; 200...240 V AC phase to phase, terminal(s): L1-L2 |
| Rated power in W | 480 W |
| Output voltage | 24 V DC |
| Power supply output current | 20 A |
| Permissible temporary current boost | 1.5 x In (for 4 s) |
| Anti-harmonic filter | Low frequency harmonic currents |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 20.000 cm |
| Package 1 Width | 18.500 cm |
| Package 1 Length | 19.500 cm |
| Package 1 Weight | 2.811 kg |
| Unit Type of Package 2 | P06 |
| Number of Units in Package 2 | 36 |
| Package 2 Height | 75.000 cm |
| Package 2 Width | 60.000 cm |
| Package 2 Length | 80.000 cm |
| Package 2 Weight | 114.956 kg |
The Modicon ABL8 Universal series of switch mode power supplies are ideal for most industrial applications and are designed in particular for DC voltage supply in automation applications. The ABL8 product family impresses with its compact and robust design and includes power supplies with an output voltage of 24V DC. This 1-/2-phase power supply with a nominal output of 480W has an input voltage of 100-240V AC and an output voltage of 24V DC/20A. The output voltage can be adjusted from 24-28.8V DC. In addition, this power supply has an overload capacity of an additional 50% power thanks to a boost function. The behavior in the event of a short circuit can be set between manual and automatic reset. In addition, this device has a diagnostic relay for undervoltage reporting and 2 LEDs for status reporting. The metal housing is mounted by snapping it onto a top hat rail and has a release lever. Suitable for international use due to the large number of existing product standards and certifications. Thanks to the Green Premium ecolabel, you can obtain detailed information on material content, environmental impact and circular economy that supports your sustainability goals.