Further information for Schneider Electric ABE7S16E2E1 relay plug-in 48 VDC
Complementary
Terminal block type
Removable
Supply voltage limits
19…30 V DC (PLC end) conforming to IEC 61131-2
Protection type
Internal fuse 1 A 5 x 20 mm fast blow PLC end; Adjustable by external fuse fast blow sensor end
Fixing mode
By clips (35 mm symmetrical DIN rail); By screws (solid plate with fixing kit)
Current per channel
0.013 A
Current state 1 guaranteed
>= 6 mA (sensor end)
Voltage state 1 guaranteed
>= 30 V for sensor end
Maximum switching current
15 mA (PLC end)
Minimum switching current
1 mA for PLC end
[Uimp] rated impulse withstand voltage
2.5 kV conforming to IEC 60947-1
[Ui] rated insulation voltage
2000 V
Installation category
II conforming to IEC 60664-1
Tightening torque
0.6 N.m with flat Ø 3.5 mm screwdriver
Net weight
0.37 kg
Isolation PLC/operative part
Contractual warranty
Warranty (in months)
18
Environment
Dielectric strength
2000 V at 50/60 Hz conforming to IEC 60947-1
Product certifications
CSA; UL; DNV; GL; EAC
Standards
IEC 61131-2 Type 2
IP degree of protection
IP2X conforming to IEC 60529
Resistance to incandescent wire
750 °C conforming to IEC 60695-2-11
Shock resistance
15 gn for 11 ms conforming to IEC 60068-2-27
Vibration resistance
2 gn (f= 10…150 Hz) conforming to IEC 60068-2-6
Resistance to electrostatic discharge
4 kV (contact) level 3 conforming to IEC 61000-4-2; 8 kV (air) level 3 conforming to IEC 61000-4-2
Resistance to radiated fields
10 V/m (26000000…1000000000 Hz) conforming to IEC 61000-4-3 level 3
Resistance to fast transients
2 kV level 3 conforming to IEC 61000-4-4
Ambient air temperature for operation
-5…60 °C conforming to IEC 61131-2
Ambient air temperature for storage
-40…80 °C conforming to IEC 61131-2
Pollution degree
2 conforming to IEC 60664-1
Logistical informations
Country of origin
LV
Main
Range of product
Modicon ABE7
Product or component type
Solid state input relay sub-base
[Us] rated supply voltage
24 V DC (PLC end); 48 V DC (sensor end)
Number of channels
16
Number of terminal per channel
2
Connections - terminals
Screw type terminals, 1 x 0.09...1 x 1.5 mm², 0.09…1.5 mm² (28 AWG...16 AWG) flexible with cable end; Screw type terminals, 1 x 0.14...1 x 2.5 mm², 0.14…2.5 mm² (26 AWG...12 AWG) solid; Screw type terminals, 1 x 0.14...1 x 2.5 mm², 0.14…2.5 mm² (26 AWG...14 AWG) flexible without cable end; Screw type terminals, 2 x 0.09...2 x 0.75 mm², 0.09…0.75 mm² (28 AWG...20 AWG) flexible with cable end; Screw type terminals, 2 x 0.2...2 x 2.5 mm², 0.2…2.5 mm² (24 AWG...14 AWG) solid
Packing Units
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
7.0 cm
Package 1 Width
8.3 cm
Package 1 Length
21.1 cm
Package 1 Weight
446.0 g
Unit Type of Package 2
S03
Number of Units in Package 2
16
Package 2 Height
30.0 cm
Package 2 Width
30.0 cm
Package 2 Length
40.0 cm
Package 2 Weight
7.63 kg
Advantys Telefast pre-wired distribution board means simplicity to streamline the wiring of your devices in your automation system.