Further information for Schneider Electric A9Z61263 RCD 2P 63A 30mA
Complementary
Device location in system
Outgoer; Group incomer
Network frequency
50 Hz
[Ue] rated operational voltage
230 V AC 50 Hz
Residual current tripping technology
Voltage independent
Rated breaking and making capacity
Idm 1500 A; Im 1500 A
Rated conditional short-circuit current
10 kA
[Ui] rated insulation voltage
250 V
[Uimp] rated impulse withstand voltage
6 kV
Control type
Toggle
Local signalling
ON/OFF indication; LED (green) for presence of voltage; Trip indicator
Mounting mode
Clip-on
Mounting support
35 mm DIN rail
9 mm pitches
8
Height
88 mm
Width
72 mm
Depth
73 mm
Net weight
350 g
Colour
White (RAL 9003)
Mechanical durability
20000 cycles
Electrical durability
15000 cycles
Locking options description
Padlocking device
Connections - terminals
Double terminal front 1…35 mm² rigid; Double terminal front 1…25 mm² flexible; Double terminal front 1…25 mm² flexible with ferrule; Double terminal back 1…25 mm² rigid; Double terminal back 1…16 mm² flexible; Double terminal back 1…16 mm² flexible with ferrule
Wire stripping length
14 mm for top or bottom connection
Tightening torque
3.5 N.m top or bottom
Contact position indicator
Contractual warranty
Warranty (in months)
18
Environment
Standards
EN/IEC 61008-1; EN/IEC 61008-2-1; IEC/EN 62423
Product certifications
CCC; KC
IP degree of protection
IP20 conforming to IEC 60529; IP40 (modular enclosure) conforming to IEC 60529
IK degree of protection
IK05
Pollution degree
3
Overvoltage category
IV
Electromagnetic compatibility
8/20 µs impulse withstand, 3 kA conforming to EN/IEC 61008-1
Operating altitude
0...2000 m
Ambient air temperature for operation
-25…60 °C
Ambient air temperature for storage
-40…85 °C
Logistical informations
Country of origin
ES
Main
Range
Acti9
Product name
Acti9 iID
Product or component type
Residual current circuit breaker (RCCB)
Device short name
iID
Device application
Photovoltaic; Lift
Poles description
2P
Neutral position
Left
[In] rated current
63 A
Network type
AC
Earth-leakage sensitivity
30 mA
Earth-leakage protection time delay
Instantaneous
Earth-leakage protection class
Type B-SI (Super Immunised)
Quality labels
VDE; NF; IMQ; KEMA
Packing Units
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
8.500 cm
Package 1 Width
7.500 cm
Package 1 Length
9.800 cm
Package 1 Weight
362.000 g
Unit Type of Package 2
S03
Number of Units in Package 2
27
Package 2 Height
30.000 cm
Package 2 Width
30.000 cm
Package 2 Length
40.000 cm
Package 2 Weight
10.254 kg
Residual current circuit breaker, all-current sensitive Acti 9 iID. 2-pole, nominal current 63A, type B-SI, nominal residual current 30mA, operating voltage (Ue) 230 AC, 50Hz, insulation voltage 250V AC. Snap action for low-wear switching of the contacts. With mechanical front-side fault signal indicator (VisiTrip) to indicate tripping due to residual current. Safe contact indicator (VisiSafe) of the residual current circuit breaker, green indicator ensures that there is no voltage on the output side. Test button for regular function testing. Double connection terminals for connecting cables or phase rails on both sides. Easy removal of the individual device when the phase rail is installed, thanks to the fastening element accessible from the front. Additional auxiliary modules that can be added (optional) undervoltage release (iMN), overvoltage release (iMSU), shunt release (iMX), auxiliary switch for status reporting (iOF), fault reporting switch (iSD). Type B-SI has integrated SI technology, which offers greater resistance to electrical interference. Protects against smooth DC fault currents in 1- or 3-phase supply networks caused by frequency converters, inverters &, emergency power supply. Color RAL 9003. Meets the following standards IEC/EN 61008-2-1,IEC/EN 62423,IEC 61543,VDE 0664.