Additional features
Network frequency
50/60 Hz
[Ue] Rated operational voltage
230 - 240 V AC 50/60 Hz
Earth fault trip technology
Voltage-independent
Rated breaking force and rated power
Idm 1500 A; IM 1500 A
Conditional rated short-circuit current
10 kA
[Ui] Rated insulation voltage
500 V AC 50/60 Hz
[Uimp] Rated impulse voltage withstand
6 kV
Control type
Toggle switch
Mounting mode
Plug-in
Mounting bracket
35 mm DIN rail
9-mm pitch
4
Height
91 mm
Width
36 mm
Depth
73 mm
Product weight
210 g
Colour
White (RAL 9003)
Mechanical life
20000 cycles
Electrical lifetime
15000 cycles
Description of locking options
Padlock
Connections - terminals
Double terminal front side 1…35 mm² solid; Double terminal front side 1…25 mm² fine-stranded; Double terminal front side 1…25 mm² fine-stranded with ferrule; Double terminal rear side 1…25 mm² solid; Double terminal rear side 1…16 mm² fine-stranded; Double terminal rear side 1…16 mm² fine-stranded with ferrule
Wire stripping length
14 mm for top or bottom connection
[M] tightening torque
3.5 Nm top or bottom
Contact position indicator
Contractual warranty
Warranty (in months)
18
Main features
Product series
Acti9
Product name
Acti9 iID
Product or component type
Residual current circuit breaker (RCCB)
Device short name
iID
Pole description
2P
Neutral position
Left
[In] Rated current
25 A
Type of network
AC
Earth fault sensitivity
30 mA
Earth fault protection time delay
Instantaneous
Earth fault protection class
Type A-SI (Superimmunized)
Mounting
Standards
EN/IEC 61008-1; EN/IEC 61008-2-1
Degree of protection (IP)
IP20 corresponds to IEC 60529; IP40 (modular housing) corresponds to IEC 60529
Pollution degree
3
Electromagnetic compatibility
8/20 µs impulse resistance, 3,000 A corresponds to EN/IEC 61008-1
Operating ambient temperature
-25…60 °C
Ambient temperature during storage
-40…85 °C
Packaging units
VPE 1 type
PCE
Number of devices per package
1
VPE 1 height
4,000 cm
VPE 1 width
8,600 cm
VPE 1 length
10,200 cm
Packaging weight (Lbs)
242,000 g
VPE 2 type
S03
VPE 2 quantity
54
VPE 2 height
30,000 cm
VPE 2 width
30,000 cm
VPE 2 length
40,000 cm
VPE 2 weight
13,897 kg
Residual current circuit breaker Acti 9 iID. 2-pole, nominal current 25A, type A, SI, nominal residual current 30mA, operating voltage (Ue) 230-240V AC, insulation voltage (Ui) 500V AC. SI version prevents unwanted tripping in systems where high availability is required. Technology of the trip unit - thermomagnetic. Additional auxiliary modules that can be connected in series (optional) - display of switch position, fault tripping, shunt release, undervoltage release, overvoltage release. Color RAL 9003. The ID residual current circuit breaker meets the following standards - IEC/EN 61008-1. This series is also VDE certified!