Further information for Schneider Electric A9Z25480 residual current circuit breaker 4-pole 80A
Additional features
Network frequency
50/60 Hz
[Ue] Rated operational voltage
400 - 415 V AC 50/60 Hz
Earth fault trip technology
Voltage-independent
Rated breaking force and rated power
Idm 1500 A; IM 1500 A
Conditional rated short-circuit current
10 kA
[Ui] Rated insulation voltage
500 V AC 50/60 Hz
[Uimp] Rated impulse voltage withstand
6 kV
Control type
Toggle switch
Mounting mode
Plug-in
Mounting bracket
35 mm DIN rail
9-mm pitch
8
Height
91 mm
Width
72 mm
Depth
73 mm
Product weight
370 g
Colour
White (RAL 9003)
Mechanical life
20000 cycles
Electrical lifetime
10000 cycles
Description of locking options
Padlock
Connections - terminals
Double terminal front side 1…35 mm² solid; Double terminal front side 1…25 mm² fine-stranded; Double terminal front side 1…25 mm² fine-stranded with ferrule; Double terminal rear side 1…25 mm² solid; Double terminal rear side 1…16 mm² fine-stranded; Double terminal rear side 1…16 mm² fine-stranded with ferrule
Wire stripping length
14 mm for top or bottom connection
[M] tightening torque
3.5 Nm top or bottom
Contact position indicator
Contractual warranty
Warranty (in months)
18
Main features
Product series
Acti9
Product name
Acti9 iID
Product or component type
Residual current circuit breaker (RCCB)
Device short name
iID
Pole description
4P
Neutral position
Left
[In] Rated current
80 A
Type of network
AC
Earth fault sensitivity
300 mA
Earth fault protection time delay
Selective
Earth fault protection class
Type A
Mounting
Standards
EN/IEC 61008-1; EN/IEC 61008-2-1
Degree of protection (IP)
IP20 corresponds to IEC 60529; IP40 (modular housing) corresponds to IEC 60529
Pollution degree
3
Electromagnetic compatibility
8/20 µs impulse resistance, 3,000 A corresponds to EN/IEC 61008-1
Operating ambient temperature
-25…60 °C
Ambient temperature during storage
-40…85 °C
Packaging units
VPE 1 type
PCE
Number of devices per package
1
VPE 1 height
7,500 cm
VPE 1 width
8,200 cm
VPE 1 length
9,800 cm
Packaging weight (Lbs)
370,000 g
VPE 2 type
S03
VPE 2 quantity
27
VPE 2 height
30,000 cm
VPE 2 width
30,000 cm
VPE 2 length
40,000 cm
VPE 2 weight
10,477 kg
Residual current circuit breaker Acti 9 iID, 1.5kA (IEC/EN 61008-1). 4-pole, nominal current 80A, earth fault sensitivity 300mA, earth fault protection class type A, selective, operating voltage (Ue) 400V AC, insulation voltage (Ui) 500V AC. Guarantees additional protection in the event of direct contact (= 30mA). Fault protection in the event of indirect contact, e.g. in the event of insulation faults (= 100mA, = 300mA). Fault protection in construction power distribution boards (500mA). Switching and disconnecting circuits. Snap action for low-wear switching of the contacts. With mechanical front-side fault indication display (VisiTrip) to indicate trips due to overload or short circuit. Safe contact display (VisiSafe) of the residual current circuit breaker, with a green display to ensure that there is no voltage on the output side. Test button for regular function testing. Double connection terminals for connecting cables or phase rails on both sides. Easy removal of the individual device with the phase rail installed, thanks to the fastening element accessible from the front. Selective version - to ensure correct differentiation between the different residual current circuit breakers and the tripping of the device closest to the defect. Additional auxiliary modules that can be added in series (optional) - undervoltage release (iMN), overvoltage release (iMSU), shunt release (iMX), auxiliary switch for status reporting (iOF), fault reporting switch (iSD). Tool-free installation on the left side of the device. Color RAL 9003. The residual current circuit breaker iID meets the following standards - IEC/EN 61008-1 and IEC/EN 60947-2. This series is also VDE certified!