Further information for Schneider Electric A9Z24425 residual current circuit breaker 4-pole 25A
Additional features
Network frequency
50/60 Hz
[Ue] Rated operational voltage
400 - 415 V AC 50/60 Hz
Earth fault trip technology
Voltage-independent
Rated breaking force and rated power
Idm 1500 A; IM 1500 A
Conditional rated short-circuit current
10 kA
[Ui] Rated insulation voltage
500 V AC 50/60 Hz
[Uimp] Rated impulse voltage withstand
6 kV
Control type
Toggle switch
Mounting mode
Plug-in
Mounting bracket
35 mm DIN rail
9-mm pitch
8
Height
91 mm
Width
72 mm
Depth
73 mm
Product weight
370 g
Colour
White (RAL 9003)
Mechanical life
20000 cycles
Electrical lifetime
15000 cycles
Description of locking options
Padlock
Connections - terminals
Double terminal front side 1…35 mm² solid; Double terminal front side 1…25 mm² fine-stranded; Double terminal front side 1…25 mm² fine-stranded with ferrule; Double terminal rear side 1…25 mm² solid; Double terminal rear side 1…16 mm² fine-stranded; Double terminal rear side 1…16 mm² fine-stranded with ferrule
Wire stripping length
14 mm for top or bottom connection
[M] tightening torque
3.5 Nm top or bottom
Contact position indicator
Contractual warranty
Warranty (in months)
18
Main features
Product series
Acti9
Product name
Acti9 iID
Product or component type
Residual current circuit breaker (RCCB)
Device short name
iID
Pole description
4P
Neutral position
Left
[In] Rated current
25 A
Type of network
AC
Earth fault sensitivity
300 mA
Earth fault protection time delay
Instantaneous
Earth fault protection class
Type A
Mounting
Standards
EN/IEC 61008-1; EN/IEC 61008-2-1
Degree of protection (IP)
IP20 corresponds to IEC 60529; IP40 (modular housing) corresponds to IEC 60529
Pollution degree
3
Electromagnetic compatibility
8/20 µs impulse resistance, 250 A according to EN/IEC 61008-1
Operating ambient temperature
-25…60 °C
Ambient temperature during storage
-40…85 °C
Packaging units
VPE 1 type
PCE
Number of devices per package
1
VPE 1 height
7,500 cm
VPE 1 width
8,000 cm
VPE 1 length
10,000 cm
Packaging weight (Lbs)
377,400 g
VPE 2 type
S03
VPE 2 quantity
27
VPE 2 height
30,000 cm
VPE 2 width
30,000 cm
VPE 2 length
40,000 cm
VPE 2 weight
10,614 kg
VPE 3 type
P12
VPE 3 quantity
216
VPE 3 height
45,000 cm
VPE 3 width
80,000 cm
VPE 3 length
120,000 cm
VPE 3 weight
96,910 kg
Fehlerstromschutzschalter Acti 9 iID, 1,5kA (IEC/EN 61008-1). 4-polig, Nennstrom 25A, Erdschlussempfindlichkeit 300mA, Erdschluss-Schutzklasse Typ A, Betriebsspannung (Ue) 400V AC, Isolationsspannung (Ui) 500V AC. Gewährleistet den Zusatzschutz bei direktem Berühren (= 30mA). Fehlerschutz bei indirektem Berühren, z.B. bei Isolationsfehlern (= 100mA, = 300mA). Fehlerschutz in Baustromverteilern (500mA). Schalten und Trennen von Stromkreisen. Sprungschaltung für verschleißarmes Schalten der Kontakte. Mit mechanischer frontseitiger Fehlermeldeanzeige (VisiTrip) zur Anzeige von Auslösungen durch Überlast oder Kurzschluss. Sichere Kontaktanzeige (VisiSafe) des Fehlerstromschutzschalters, bei grüner Anzeige Sicherheit der Spannungsfreiheit auf der Abgangsseite. Prüftaste für die regelmäßige Prüfung der Funktion. Doppel-Anschlussklemmen für beidseitigen Anschluss von Kabeln oder Phasenschienen. Einfache Entnahme des Einzelgerätes bei installierter Phasenschiene, dank des frontseitig erreichbaren Befestigungselementes. Zusätzlich anreihbare Hilfsmodule (optional)- Unterspannungsauslöser (iMN), Überspannungsauslöser (iMSU), Arbeitsstromauslöser (iMX), Hilfsschalter zur Statusmeldung (iOF), Fehlermeldeschalter (iSD). Werkzeuglose Montage linksseitig am Gerät. Farbton RAL 9003. Der Fehlerstromschutzschalter iID erfüllt folgende Normen- IEC/EN 61008-1 und IEC/EN 60947-2. Des Weiteren ist diese Baureihe VDE zertifiziert!.