Further information for Schneider Electric A9Z24225 residual current circuit breaker 2-pole 25A
Complementary
Network frequency
50/60 Hz
[Ue] rated operational voltage
230...240 V AC 50/60 Hz
Residual current tripping technology
Voltage independent
Rated breaking and making capacity
Idm 1500 A; Im 1500 A
Rated conditional short-circuit current
10 kA
[Ui] rated insulation voltage
500 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage
6 kV
Control type
Toggle
Mounting mode
Clip-on
Mounting support
35 mm DIN rail
9 mm pitches
4
Height
91 mm
Width
36 mm
Depth
73 mm
Net weight
210 g
Colour
White (RAL 9003)
Mechanical durability
20000 cycles
Electrical durability
15000 cycles
Locking options description
Padlocking device
Connections - terminals
Double terminal front 1…35 mm² rigid; Double terminal front 1…25 mm² flexible; Double terminal front 1…25 mm² flexible with ferrule; Double terminal back 1…25 mm² rigid; Double terminal back 1…16 mm² flexible; Double terminal back 1…16 mm² flexible with ferrule
Wire stripping length
14 mm for top or bottom connection
Tightening torque
3.5 N.m top or bottom
Contact position indicator
Contractual warranty
Warranty (in months)
18
Environment
Standards
EN/IEC 61008-1; EN/IEC 61008-2-1
IP degree of protection
IP20 conforming to IEC 60529; IP40 (modular enclosure) conforming to IEC 60529
Pollution degree
3
Electromagnetic compatibility
8/20 µs impulse withstand, 250 A conforming to EN/IEC 61008-1
Ambient air temperature for operation
-25…60 °C
Ambient air temperature for storage
-40…85 °C
Main
Range
Acti9
Product name
Acti9 iID
Product or component type
Residual current circuit breaker (RCCB)
Device short name
iID
Poles description
2P
Neutral position
Left
[In] rated current
25 A
Network type
AC
Earth-leakage sensitivity
300 mA
Earth-leakage protection time delay
Instantaneous
Earth-leakage protection class
Type A
Packing Units
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
8.500 cm
Package 1 Width
4.000 cm
Package 1 Length
10.000 cm
Package 1 Weight
220.000 g
Unit Type of Package 2
S03
Number of Units in Package 2
54
Package 2 Height
30.000 cm
Package 2 Width
30.000 cm
Package 2 Length
40.000 cm
Package 2 Weight
12.334 kg
Residual current circuit breaker Acti 9 iID, 1.5kA (IEC/EN 61008-1). 2-pole, nominal current 25A, earth fault sensitivity 300mA, earth fault protection class type A, operating voltage (Ue) 230V AC, insulation voltage (Ui) 500V AC. Guarantees additional protection in the event of direct contact (= 30mA). Fault protection in the event of indirect contact, e.g. in the event of insulation faults (= 100mA, = 300mA). Fault protection in construction power distribution boards (500mA). Switching and disconnecting circuits. Snap action for low-wear switching of the contacts. With mechanical front-side fault indication display (VisiTrip) to indicate tripping due to overload or short circuit. Safe contact display (VisiSafe) of the residual current circuit breaker, with a green display to ensure that there is no voltage on the output side. Test button for regular function testing. Double connection terminals for connecting cables or phase rails on both sides. Easy removal of the individual device with an installed phase rail, thanks to the fastening element accessible from the front. Additional auxiliary modules that can be connected in series (optional) - undervoltage release (iMN), overvoltage release (iMSU), shunt release (iMX), auxiliary switch for status reporting (iOF), fault reporting switch (iSD). Tool-free installation on the left side of the device. Color RAL 9003. The residual current circuit breaker iID meets the following standards - IEC/EN 61008-1 and IEC/EN 60947-2. This series is also VDE certified!